2020-11-17 09:26:44CODES IN EFFECT
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 REVIEW STATUS: FAILED. PLEASE SEE COMMENTS BELOW:
  
 1) ELECTRICAL RISER DIAGRAM: FEEDER TO RAYCAP PANEL. IS
 IT 2#3 PLUS 1#10 GROUND? PLEASE CORRECT.
 2) PANEL SCHEDULES: POWER PANEL BREAKER SHOWS A 30 AMPS
 BREAKER FOR FEEDER TO RAYCAP PANEL BUT RAYCAP PANEL HAS
 A 60 A MAIN BREAKER. ALSO, FEEDER TO RAYCAP PANEL SEEMS
 TO BE #10 IN RISER DIAGRAM. PLEASE CLARIFY AND CORRECT
 FOR CONSISTENCY.
 3) POLE ELEVATION TYPICAL: PLEASE FILL IN CONDUCTOR
 SIZE WHERE IT STATES ?INSTALL (3) ## THWN WIRE.
  
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  