| 2020-11-03 14:25:38 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | FLORIDA BUILDING CODE 2017 6TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | | NFPA 70 2014 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | 1) CABANA SERVED BY MORE THAN ONE BRANCH CIRCUIT, | | | | | | A BUILDING OR OTHER STRUCTURE THAT IS SERVED BY A | | | BRANCH CIRCUIT OR FEEDER ON THE LOAD SIDE OF A SERVICE | | | DISCONNECTING MEANS SHALL BE SUPPLIED BY ONLY ONE | | | FEEDER OR BRANCH CIRCUIT. NEC 225.30 | | | | | | PROVIDE GROUNDING ELECTRODE SYSTEM AS REQUIRED FOR A | | | BUILDING OR STRUCTURE SUPPLIED BY A FEEDER OR BRANCH | | | CIRCUIT. NEC 250.32; FBC RE3607.3 | | | | | | FEEDERS THAT SUPPLY A SEPARATE STRUCTURE REQUIRE A | | | DISCONNECTING MEANS AT THE BUILDING OR SEPARATE | | | STRUCTURE SUPPLIED. PROVIDE EITHER A MAIN DISCONNECT OR | | | MAIN BREAKER FOR PANEL A. NEC 225.31, 225.32 | | | |
|