Plan Review Notes
Plan Review Notes For Permit 20090717
Permit Number 20090717
Review Stop B
Sequence Number 1
Notes
Date Text
2020-11-02 15:46:26SFR ADDITION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) PRODUCT APPROVAL PROVIDED FOR THE SINGLE HUNG
 WINDOWS HAS EXPIRED (17-1018.08) - PLEASE PROVIDE AN
 UPDATED COPY.
 2) ON THE PRODUCT APPROVAL FOR THE TILE ROOFING -
 PLEASE CIRCLE THE ATTACHMENT METHOD TO BE USED - IF
 USING ADHESIVE PLEASE PROVIDE THE PRODUCT APPROVAL FOR
 THE ADHESIVE.
 3) PLEASE PROVIDE A COMPLETE (FRONT PAGES AND THE
 INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE
 PRODUCT APPROVAL FOR THE FLAT DECK ROOFING = PLEASE
 CIRCLE THE ROOFING SYSTEM TO BE USED IN THE PRODUCT
 APPROVAL - IF NEEDED PLEASE PROVIDE SIGNED AND SEALED
 ADDITIONAL ATTACHMENT DETAILS FROM AN ARCHITECT OR
 ENGINEER FOR THE ROOF ZONES 2 AND 3 WHICH MAY REQUIRE A
 HIGHER WIND PRESSURE - SEE NOTES ON THE PRODUCT
 APPROVAL.
 4) PLEASE PROVIDE A COMPLETE (FRONT PAGES AND THE
 INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE
 PRODUCT APPROVAL FOR THE FRENCH DOORS AND THE SLIDING
 GLASS DOORS.
 5) PLEASE SHOW THE REQUIRED TERMITE PROTECTION PER FBC
 R318
 6) PLEASE SHOW THE LOCATION OF THE ATTIC ACCESS IN THE
 TRUSSED ROOF FBC R807
 7) PLEASE SHOW THE ATTIC VENTILATION IN ALL ADDED ROOF
 SECTIONS TO COMPLY WITH FBC R806.1
 8) 2X6 AND 2X10 JOIST = R30 INSULATION SHOWN IN THE
 ROOF JOIST MAY NOT PROVIDE THE CORRECT "R" VALUE DUE TO
 COMPRESSION. REVISE THE ENERGY CALCS. IF NEEDED.
 9) 2X6 AND 2X8 JOIST R30 BAT INSULATION WILL NOT
 PROVIDE THE 1 ? CLEARANCE PER R806.3 VENT AND
 INSULATION CLEARANCE.
 WHERE EAVE OR CORNICE VENTS ARE INSTALLED, INSULATION
 SHALL NOT BLOCK THE FREE FLOW OF AIR. NOT LESS THAN A
 1-INCH (25 MM) SPACE SHALL BE PROVIDED BETWEEN THE
 INSULATION AND THE ROOF SHEATHING AND AT THE LOCATION
 OF THE VENT.
 10) PLEASE SHOW THE REQUIRED SMOKE ALARMS PER FBC
 R314.2.2
 11) CANNOT RELOCATE AN EXISTING WINDOW FBC EXISTING
 BUILDING 1103.1 - UNLESS YOU CAN PROVIDE AN UPDATED
 PRODUCT APPROVAL FOR THE RELOCATED WINDOW.
 12) PLEASE SHOW THE LOT DRAINAGE ON THE SITE
 PLAN/SURVEY - SHOW CUT SECTIONS FOR ANY CREATED WATER
 RETENTION AREAS, SWALES ETC.
  
  
  