| 2020-11-02 15:46:26 | SFR ADDITION |
| | REVIEWED BY ROGER MCPHERSON |
| | 561-805-6716 |
| | [email protected]. |
| | CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1 |
| | AMENDMENTS |
| | |
| | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 |
| | 1) PRODUCT APPROVAL PROVIDED FOR THE SINGLE HUNG |
| | WINDOWS HAS EXPIRED (17-1018.08) - PLEASE PROVIDE AN |
| | UPDATED COPY. |
| | 2) ON THE PRODUCT APPROVAL FOR THE TILE ROOFING - |
| | PLEASE CIRCLE THE ATTACHMENT METHOD TO BE USED - IF |
| | USING ADHESIVE PLEASE PROVIDE THE PRODUCT APPROVAL FOR |
| | THE ADHESIVE. |
| | 3) PLEASE PROVIDE A COMPLETE (FRONT PAGES AND THE |
| | INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE |
| | PRODUCT APPROVAL FOR THE FLAT DECK ROOFING = PLEASE |
| | CIRCLE THE ROOFING SYSTEM TO BE USED IN THE PRODUCT |
| | APPROVAL - IF NEEDED PLEASE PROVIDE SIGNED AND SEALED |
| | ADDITIONAL ATTACHMENT DETAILS FROM AN ARCHITECT OR |
| | ENGINEER FOR THE ROOF ZONES 2 AND 3 WHICH MAY REQUIRE A |
| | HIGHER WIND PRESSURE - SEE NOTES ON THE PRODUCT |
| | APPROVAL. |
| | 4) PLEASE PROVIDE A COMPLETE (FRONT PAGES AND THE |
| | INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE |
| | PRODUCT APPROVAL FOR THE FRENCH DOORS AND THE SLIDING |
| | GLASS DOORS. |
| | 5) PLEASE SHOW THE REQUIRED TERMITE PROTECTION PER FBC |
| | R318 |
| | 6) PLEASE SHOW THE LOCATION OF THE ATTIC ACCESS IN THE |
| | TRUSSED ROOF FBC R807 |
| | 7) PLEASE SHOW THE ATTIC VENTILATION IN ALL ADDED ROOF |
| | SECTIONS TO COMPLY WITH FBC R806.1 |
| | 8) 2X6 AND 2X10 JOIST = R30 INSULATION SHOWN IN THE |
| | ROOF JOIST MAY NOT PROVIDE THE CORRECT "R" VALUE DUE TO |
| | COMPRESSION. REVISE THE ENERGY CALCS. IF NEEDED. |
| | 9) 2X6 AND 2X8 JOIST R30 BAT INSULATION WILL NOT |
| | PROVIDE THE 1 ? CLEARANCE PER R806.3 VENT AND |
| | INSULATION CLEARANCE. |
| | WHERE EAVE OR CORNICE VENTS ARE INSTALLED, INSULATION |
| | SHALL NOT BLOCK THE FREE FLOW OF AIR. NOT LESS THAN A |
| | 1-INCH (25 MM) SPACE SHALL BE PROVIDED BETWEEN THE |
| | INSULATION AND THE ROOF SHEATHING AND AT THE LOCATION |
| | OF THE VENT. |
| | 10) PLEASE SHOW THE REQUIRED SMOKE ALARMS PER FBC |
| | R314.2.2 |
| | 11) CANNOT RELOCATE AN EXISTING WINDOW FBC EXISTING |
| | BUILDING 1103.1 - UNLESS YOU CAN PROVIDE AN UPDATED |
| | PRODUCT APPROVAL FOR THE RELOCATED WINDOW. |
| | 12) PLEASE SHOW THE LOT DRAINAGE ON THE SITE |
| | PLAN/SURVEY - SHOW CUT SECTIONS FOR ANY CREATED WATER |
| | RETENTION AREAS, SWALES ETC. |
| | |
| | |
| | |