2020-10-14 10:57:211) SHT. P200 - THE HOSE BIBB ON THE EXTERIOR REQUIRES
 AN INDIVIDUAL SHUTOFF VVALVE PER FBC-PLUMBING SEC.
 606.2.
 2) SHT. P200 - THE ICE MAKER ON THE REFRIGERATORR SHALL
 BE EQUIPPED WITH AND AIR ARRESTOR ANND A BACKFLOW
 DEVICE PER 604.9 & 608..3.
 3) SUBMIT MANUFACTURER'S SPECIFICATIOONS FOR THE SUMP &
 PUMP FOR THE BREAK ROOM SINK. WPB AMEND. TO FBC SEC.
 107.2.1.
 4) SUBMIT MANUFACTURER'S SPECS FOR THE SEP CABINET. A
 BACKFLOW PREVENTION DEVICE MAY BE REQUIRED FOR THE
 WATER CONNECTION.FBC-PLUMBING SEC. 608..3.
 5) SUBMIT MANUFACTURER'S SPECIICATIONS/ INSTALLATION
 DOCUMENTS FOR THE SIEMANS CHILLED WATER EQUIPMENT.WPB
 AMEND. TO FBC SEC. 107.2.1.
  