2020-10-29 17:42:41ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
  
 1) IDENTIFICATION. WHERE A BUILDING OR STRUCTURE IS
 SUPPLIED BY MORE THAN ONE SERVICE, OR ANY COMBINATION
 OF BRANCH CI RCUITS, FEEDERS, AND SERVICES, A PERMANENT
 PLAQUE OR DIRECTORY SHALL BE INSTALLED AT EACH SERVICE
 DISCONNECT LOCATION DENOTING ALL OTHER SERVICES,
 FEEDERS, AND BRANCH CIRCUITS SUPPLYING THAT BUILDING OR
 STRUCTURE AND THE AREA SERVED BY EACH.
  
 2) 250.58 COMMON GROUNDING ELECTRODE WHERE AN AC SYSTEM
 IS CONNECTED TO A GROUNDING ELECTRODE IN OR AT A
 BUILDING OR STRUCTURE, THE SAME ELECTRODE SHALL BE USED
 TO GROUND CONDUCTOR ENCLOSURES AND EQUIPMENT IN OR ON
 THAT BUILDING OR STRUCTURE. WHERE SEPARATE SERVICES,
 FEEDERS, OR BRANCH CIR CUITS SUPPLY A BUILDING AND ARE
 REQUIRED TO BE CONNECTED TO A GROUNDING ELECTRODE(S),
 THE SAME GROUNDING ELECTRODE(S) SHALL BE USED. TWO OR
 MORE GROUNDING ELECTRODES THAT ARE BONDED TOGETHER
 SHALL BE CONSIDERED AS A SINGLE GROUNDING ELECTRODE
 SYSTEM IN THIS SENSE.
  
 3) CIRCUIT A-24 TO BE GFCI PROTECTED WITHIN 6" OF A
 SINK.
  
 4) CIRCUIT A-4 NOT SHOWN ON PLAN NEEDS TO BE GFCI
 PROTECTED 422.52