| Plan Review Notes For Permit 20090711 |
| Permit Number |
20090711 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2020-10-29 17:42:41 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | FLORIDA BUILDING CODE 2017 6TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | | NFPA 70 2014 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | | | | 1) IDENTIFICATION. WHERE A BUILDING OR STRUCTURE IS | | | SUPPLIED BY MORE THAN ONE SERVICE, OR ANY COMBINATION | | | OF BRANCH CI RCUITS, FEEDERS, AND SERVICES, A PERMANENT | | | PLAQUE OR DIRECTORY SHALL BE INSTALLED AT EACH SERVICE | | | DISCONNECT LOCATION DENOTING ALL OTHER SERVICES, | | | FEEDERS, AND BRANCH CIRCUITS SUPPLYING THAT BUILDING OR | | | STRUCTURE AND THE AREA SERVED BY EACH. | | | | | | 2) 250.58 COMMON GROUNDING ELECTRODE WHERE AN AC SYSTEM | | | IS CONNECTED TO A GROUNDING ELECTRODE IN OR AT A | | | BUILDING OR STRUCTURE, THE SAME ELECTRODE SHALL BE USED | | | TO GROUND CONDUCTOR ENCLOSURES AND EQUIPMENT IN OR ON | | | THAT BUILDING OR STRUCTURE. WHERE SEPARATE SERVICES, | | | FEEDERS, OR BRANCH CIR CUITS SUPPLY A BUILDING AND ARE | | | REQUIRED TO BE CONNECTED TO A GROUNDING ELECTRODE(S), | | | THE SAME GROUNDING ELECTRODE(S) SHALL BE USED. TWO OR | | | MORE GROUNDING ELECTRODES THAT ARE BONDED TOGETHER | | | SHALL BE CONSIDERED AS A SINGLE GROUNDING ELECTRODE | | | SYSTEM IN THIS SENSE. | | | | | | 3) CIRCUIT A-24 TO BE GFCI PROTECTED WITHIN 6" OF A | | | SINK. | | | | | | 4) CIRCUIT A-4 NOT SHOWN ON PLAN NEEDS TO BE GFCI | | | PROTECTED 422.52 |
|