| 2020-09-29 13:16:37 | 2ND REVIEW FBC-2017 RES. |
| | PERMIT- 20090696 |
| | 9/29/2020 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) THE SELECTED RHEEM RTEX-24 IS UNDERSIZED FOR THE |
| | REQUIRED HOT WATER GPM FLOW TO THE FIXTURES. THE |
| | MANUFACTURER'S TEMPERATURE RISE CHART AND INSTALLATION |
| | MANUAL FOR THE SELECTED RHEEM RTEX-24 SHOWS A MAX 5.0 |
| | GPM FLOW AT A 33-DEGREE F TEMPERATURE RISE FROM THE |
| | COLD INLET TEMPERATURE TO HOT WATER OUTLET TEMPERATURE. |
| | PLEASE NOTE THAT RHEEM MANUFACTURER USES A 70 DEGREE |
| | COLD WATER TEMPERATURE FOR OUR REGION, AND HOT WATER AT |
| | A TEMPERATURE OF 110 DEGREES F SHALL BE PROVIDED TO THE |
| | FIXTURES WHERE REQUIRED- SECTION P2801.1 FBC RES. IT |
| | APPEARS BY THE SPECS THAT THE RTEX-27 CAN SUPPLY MAX |
| | 5.0 GPM AT A 37-DEGREE TEMP. RISE, AND THE RTEX-36 CAN |
| | SUPPLY MAX 6.0 GPM AT A TEMP. RISE OF 41 DEGREES. BASED |
| | ON THE MANUFACTURER'S SPECS, IN ORDER TO SUPPLY A |
| | MINIMUM OF 6.0 GPM HOT WATER FLOW, IT APPEARS THE |
| | RTEX-36 WOULD BE THE CODE COMPLIANT CHOICE. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |