| 2021-04-28 07:56:37 | 3RD REVIEW FBC-2017 RES. FUEL GAS |
| | PERMIT- 20090652 |
| | 4/28/2021 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) THE RISER SHOWS TWO GAS PIPING OUTLETS AT THE METER |
| | HOWEVER METERS TYPICALLY HAVE ONE INLET AND ONE OUTLET. |
| | PLEASE REVISE THE RISER TO SHOW THE TYPE AND SIZE OF |
| | THE MAIN OUTLET PIPE AND LENGTH OF THE PIPE FROM THE |
| | METER TOP THE TEE WHERE THE PE RISER IS CONNECTING. |
| | PLEASE NOTE THAT THE PIPE MUST BE SIZED LARGE ENOUGH TO |
| | SUPPLY THE INCREASED GAS LOAD OF 875,000 BTUS AT A |
| | TOTAL DEVELOPED LENGTH OF 110 FT- SECTION G2413.4.1 FBC |
| | RES. |
| | |
| | A) PLEASE SHOW THE DELIVERY PRESSURE AT THE METER AND |
| | PRESSURE DROP FOR THE SYSTEM- G2413.2 & G2413.5. |
| | |
| | B) LIST ALL PIPE SIZING TABLES ON THE RISER DRAWING- |
| | G2413.4. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL/PLUMBING PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |