| 2021-01-14 16:00:46 | 2ND REVIEW FBC-2017 RES. FUEL GAS |
| | PERMIT- 20090652 |
| | 1/14/2020 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) GAS RISER: BASED ON THE SUBMITTED PE PIPE SIZING |
| | TABLE 402.4(21) FBC FG, THE 1-1/4 IN.PE PIPE IS |
| | UNDERSIZED TO SUPPLY THE NEW TOTAL LOAD OF 875,000 BTU |
| | LOAD AT 110 FT. DEVELOPED LENGTH AS INDICATED ON THE |
| | RISER. PLEASE NOTE THE 110 FT. LENGTH DOES NOT APPEAR |
| | TO MATCH THE MEASURMENTS ON THE RISER WHICH APPEAR TO |
| | INDICATE 80 FT. TOTAL LENGTH.THE 1-1/4 IS ALSO |
| | UNDERSIZED TO PROVIDE THE EXISTING LOAD OF 615 BTU |
| | BASED ON THE TABLE. |
| | |
| | 2) GAS RISER: THE NEW 1 IN. PIPE IS LARGE ENOUGH TO |
| | SUPPLY THE 260,000 BTU GENERATOR LOAD IF THE NEW PIPE |
| | IS DIRECTLY CONNECTED TO THE METER AND NOT TEEING OFF |
| | FROM THE EXISTING 1-1/4 IN. PIPE. PLEASE PROVIDE A |
| | DETAIL SHOWING THE PIPING CONNECTIONS AT THE METER. |
| | COMMENTS 3 & 4 BELOW PERTAIN TO THE EXISTING PIPING |
| | WHICH APPEARS TO NOT BE SIZED PROPERLY. |
| | |
| | 3) GAS RISER: PLEASE PROVIDE THE LENGTH OF THE PE PIPE |
| | RUN FROM THE METER TO THE CSST TEE- SECTION G2413.4.1 |
| | FBC RES. |
| | |
| | 4) GAS RISER: BASED ON THE SUBMITTED CSST PIPE SIZING |
| | TABLE 402.4(15) THE 1 IN. (31 EHD) IS UNDERSIZED TO |
| | SUPPLY THE INTERIOR 270,000 BTU LOAD AT 110 FT. |
| | DEVELOPED LENGTH. ACCORDING TO THE TABLE, AN EHD 46 |
| | PIPE IS REQUIRED. |
| | |
| | 5) THE SUBMITTED SURVEY IS APPEARS TO BE A PHOTO IMAGE |
| | WITH PRINT TOO SMALL TO READ AND PRINT WHEN ENLARGED |
| | FOR REVIEW BECOMES BLURRY AND ILLEGIBLE. PLEASE PROVIDE |
| | THE SURVEY IN A FORMAT THAT CAN BE REVIEWED FOR |
| | COMPLIANCE- SECTION 107.2.1 WPB. PLEASE MARK THE SURVEY |
| | TO SHOW GENERATOR'S LOCATION AND CLEARANCE DISTANCES TO |
| | THE BUILDING, ADJACENT PROPERTY LINES, AND AIR INTAKES |
| | AND OPERABLE OPENINGS INTO THE BUILDING- SEE SEC. 4.1.4 |
| | NFPA 37, AND SEC. R303.5.1 FBC RES. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |