| Date |
Text |
| 2020-10-21 11:42:57 | 1ST REVIEW FBC-2017 RES. FUEL GAS |
| | PERMIT- 20090652 |
| | 10/21/2020 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) GAS RISER DRAWING: PLEASE PROVIDE A COMPLETE RISER |
| | DRAWING THAT INCLUDES THE INTERIOR GAS APPLIANCES |
| | INSTALLED UNDER PERMIT 98003449 INCLUDING THE WATER |
| | HEATER, DRYER, AND COOKTOP- SECTIONS G2412.3 & G2412.4 |
| | FBC RES. |
| | |
| | A) SHOW THE CORRECT TOTAL LOAD AND THE INDIVIDUAL LOADS |
| | OF THE SYSTEM- SECTIONS G2412.3, G2412.4, & G2413.2 FBC |
| | RES. PLEASE NOTE THE GENERATOR SPECS INDICATE A FULL |
| | LOAD CAPACITY OF 260,000 BTUH FOR NATURAL GAS. |
| | |
| | B) PROVIDE THE TOTAL LENGTH DEVELOPED LENGTH OF THE |
| | PIPING FROM THE METER TO THE MOST REMOTE OUTLET, AND |
| | THE INDIVIDUAL BRANCH LENGTHS- SECTIONS G2413.4.1 AND |
| | G2413.4.2 FBC RES. |
| | |
| | C) INDICATE THE INPUT GAS PRESSURE FOR THE GENERATOR |
| | PER MANUFACTURER'S SPECIFICATIONS AT THE OUTLET SIDE OF |
| | THE REGULATOR. PLEASE SUBMIT MARKED UP OR HIGHLIGHTED |
| | SPECS FOR THE REGULATOR SHOWING THE SELECTED MODEL, THE |
| | MAX INLET AND OUTLET SIZE AND PRESSURES, SPRING DATA, |
| | AND ORIFICE SIZE- SECTION G2421. |
| | D) SHOW THE REQUIRED PIPE UNIONS FOR RIGID PIPING |
| | WITHIN 1 FT. OF EITHER SIDE OF THE REGULATOR- SECTION |
| | G2421.2(7). |
| | |
| | 2) PROVIDE A MARKED UP OR HIGHLIGHTED COPY OF THE |
| | PROPERTY SURVEY SHOWING THE GENERATOR'S LOCATION AND |
| | CLEARANCE DISTANCES TO THE BUILDING, ADJACENT PROPERTY |
| | LINES, AND AIR INTAKES AND OPERABLE OPENINGS INTO THE |
| | BUILDING- SEE SEC. 4.1.4 NFPA 37, AND SEC. R303.5.1 FBC |
| | RES. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL/PLUMBING PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |