| 2020-10-27 08:08:27 | PLAN REVIEW GENERATOR / BUILDING |
| | |
| | CHRISTOPHER S. THROOP, C.B.O. |
| | PLANS EXAMINER BUILDING - PX3169 |
| | PLANS EXAMINER 1&2 FAMILY - SFP306 |
| | CONSTRUCTION SERVICES DIVISION |
| | TEL: 561-805-6726 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | CODES IN EFFECT: |
| | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | |
| | 1ST REVIEW |
| | |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | RE: PRE-CAST GENERATOR PAD ENGINEERING: |
| | |
| | 1.GENERATOR PAD ENGINEERING IS BASED ON VULT OF 186MPH |
| | AND VASD OF 144MPH, RISK CATEGORY III AND EXPOSURE |
| | CATEGORY D. |
| | |
| | PROVIDE GENERATOR PAD DESIGN USING THE EXISTING SITE |
| | CONDITIONS: |
| | |
| | ASSUMED DESIGN CRITERIA FOR THIS SITE: VULT OF 170MPH, |
| | (FIGURE R301.2(4) ) VASD OF 132MPH (TABLE R301.2.1.3) |
| | RISK CATEGORY II AND EXPOSURE CATEGORY C. |
| | |
| | 2.PROPOSED PRE-CAST PAD DEMENSIONS ARE 33.75 X 49 |
| | INCHES. |
| | GENERATOR DEMENSIONS FROM SPEIFICATIONS PROVIDED ARE |
| | 29.6 X 48.1 INCHES. |
| | ANCHORS REQUIRE A MINIMUM OF 3 INCH EDGE DISTANCE. |
| | IT APPEARS THE PROPOSED PAD IS TOO SMALL. |
| | |
| | 3.PROVIDE LOCATION OF GENERATOR ON SURVEY. PROVIDE |
| | DEMENSIONS TO PROPERTY LINES, TO STRUCTURE AND TO |
| | OPENINGS IN STRUCTURE. |
| | |
| | R303.5.1 INTAKE OPENINGS: MECHANICAL AND GRAVITY |
| | OUTDOOR AIR INTAKE OPENINGS SHALL BE LOCATED NOT LESS |
| | THAN 10 FEET (3048 MM) FROM ANY HAZARDOUS OR NOXIOUS |
| | CONTAMINANT, SUCH AS VENTS, CHIMNEYS, PLUMBING VENTS, |
| | STREETS, ALLEYS, PARKING LOTS AND LOADING DOCKS. |
| | |