| Date |
Text |
| 2021-05-06 16:09:06 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| | MANUAL REVISED 2017 |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION |
| | FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH |
| | EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | 20090644 2508 N AUSTRALIAN AVE |
| | |
| | |
| | 3RD REVIEW |
| | PLUMBING COMMENTS: DENIED |
| | |
| | |
| | 1.3RD REQUEST: PER WPB FBC 107.2.1, PROVIDE A FINANCIAL |
| | VALUATION OF THE PROJECT. SEE WPB FBC SECTION 109 FEES. |
| | RESPONSE IS THAT CONTRACTOR TO PROVIDE VALUATION. THAT |
| | VALUATION DOES NOT SEEM TO BE IN ANY OF THE SUBMITTED |
| | INFORMATION. PLEASE PROVIDE. |
| | |
| | 2.PER WPB FBC 107.2.1, SIZE ALL VERTICAL WASTE AND ALL |
| | VENTS ON SANITARY RISER DIAGRAM. |
| | |
| | 3.RELOCATED MOP SINK APPEARS TO BE FLOOR MOUNTED (SEE |
| | PLAN P-3). PER WPB FBC 107.2.1, PLEASE CONFIRM AND |
| | PROVIDE FAUCET INFORMATION. DOES THE SPOUT HAVE A HOSE |
| | THREAD CONNECTION? PROVIDE BACKFLOW PROTECTION AS |
| | REQUIRED IN FBC PL SECTION 608. |
| | |
| | 4.PER WPB FBC 107.2.1, SHOW ON ALL ELEVATION VIEWS OF |
| | ACCESSIBLE WATER CLOSETS PLAN SHEETS P-2 AND P-3, FLUSH |
| | CONTROLS TO BE ON OPEN SIDE OF WATER CLOSET PER FBC ACC |
| | 604.6, NOT ADJACENT TO SIDE WALL AS IS CURRENTLY SHOWN. |
| | |
| | 5.PER WPB FBC 107.2.1, CLARIFY AND RECONCILE URINAL |
| | ELEVATION MEASUREMENTS ON P-2 AND P-3. |
| | |
| | 6.MEASUREMENTS TO GRAB BAR FROM FINISH FLOOR SHALL BE |
| | TO THE TOP OF GRAB BAR, NOT THE CENTER PER FBC ACC |
| | 609.4. |
| | |
| | 7.PER WPB FBC 107.2.1, PROVIDE SPEC/SCHEDULE FOR THREE |
| | COMPARTMENT SINK AND HAND SINK AND FAUCET IN |
| | STORAGE/BREAK ROOM. PER FBC ACC 603, THE HAND SINK |
| | SHALL BE INSTALLED WITH THE FRONT OF THE HIGHER OF THE |
| | RIM OR COUNTER SURFACE 34 INCHES MAXIMUM ABOVE THE |
| | FINISH FLOOR OR GROUND PER FBC ACC 606.3, ADDITIONALLY |
| | SHOW TOE AND KNEE CLEARANCE AS REQUIRED BY FBC ACC |
| | 306.2 AND 306.3 FOR FORWARD APPROACH. PER FBC ACC |
| | 605.5, WATER SUPPLY & DRAINPIPES UNDER LAVATORIES AND |
| | SINKS SHALL BE INSULATED OR OTHERWISE CONFIGURED TO |
| | PROTECT AGAINST CONTACT. |
| | |
| | 8.REGARDING P-1; NOTE 468.3.5.12 HOT WATER, PER WPB FBC |
| | 107.2.1, ADD "PER FBC PL 416.5, SAID MIXING VALVE SHALL |
| | CONFORM TO ASSE 1070." |
| | |
| | 9.HOT WATER DISTRIBUTION APPEARS TO BE EXCESSIVELY |
| | OVERSIZED. ACCORDING TO YOUR CALCULATIONS THE LOAD ON |
| | THE HOT WATER SYSTEM IS 9.75 WSFU. FBC PL TABLE |
| | E103.3(3) INDICATES A DEMAND OF 14.6 GPM POSSIBLY |
| | ALLOWING 3/4 INCH PIPING, DECREASING TO 1/2 INCH AS THE |
| | DEMAND DROPS (SEE FBC PL FIGURE 103.3(2) BETWEEN 5 FPS |
| | AND 10 FPS). PLEASE NOTE THAT FBC EC C404.5 LIMITS THE |
| | VOLUME OF WATER THAT MAY TRAVEL THROUGH A HOT WATER |
| | PIPE AND PROVIDES MEANS TO CALCULATE THE MAXIMUM PIPE |
| | SIZE TO ELIMINATE THE AMOUNT OF COLD WATER DISCHARGED |
| | BEFORE HOT WATER REACHES THE OUTLET, THUS REDUCING |
| | ENERGY USAGE AS WELL AS THE WASTING OF WATER. PER WPB |
| | FBC 107.2.1, NOTE THE GPM FOR THE HOT WATER DEMAND. |
| | REVISIT AND SIZE THE HOT WATER DISTRIBUTION |
| | ACCORDINGLY. |
| | |
| | 10.PER FBC PL E607.5 AND FBC EC C404.4.2, INSULATE THE |
| | FIRST 8 FEET OF OUTLET PIPING FROM TANK TYPE WATER |
| | HEATER. PER WPB FBC 107.2.1, SPECIFY THE INSULATION TO |
| | COMPLY WITH FBC EC TABLE C403.2.10. |
| | |
| | 11.WATER DISTRIBUTION PLAN VIEW AT EXISTING WATER |
| | HEATER SHOWS 2 INCH COLD WATER FROM EXISTING WATER |
| | SUPPLY LINE. PER WPB FBC 107.2.1, CLARIFY AS THERE IS |
| | NOTHING ELSE IN THE DRAWINGS TO INDICATE THIS. |
| | |
| | 12.IT IS NOTED THAT THE WATER HEATER IS EXISTING. |
| | PLEASE BE ADVISED THAT IF ANY WORK OR MODIFICATION TO |
| | THE PIPING TO THE WATER HEATER IS MADE THEN THE |
| | REQUIREMENTS OF FBC PL CHAPTERS 5 AND 6 SHALL BE MET. |
| | PER WPB FBC 107.2.1, A DETAIL OF WATER HEATER SHOWING |
| | HEATER SHALL BE PROVIDED SHOWING HEATER W/STORAGE |
| | CAPACITY, PIPING INCLUDING CW, HW, VALVES (INCLUDING |
| | VACUUM RELIEF VALVE IF APPLICABLE FBC PL 504.2) , |
| | THERMAL EXPANSION CONTROL DEVICE (INCLUDING SIZE), T&P |
| | DISCHARGE (INCLUDING TERMINATION) AND WATER HEATER PAN |
| | AND DRAIN (INCLUDING TERMINATION) PER WPB FPC 107.2.1; |
| | COMPLY WITH FBC PL 607.3, 503.1, 504.1, 504.4, 504.4.1, |
| | 504.5, 504.6, 504.7, 504.7.1 AND 504.7.2. |
| | |
| | 13.REGARDING THE WATER COOLER TEMPORARY USAGE DUE TO |
| | COVID 19, PROVIDE ACCESSIBLE FLAT BOTTOM CUP |
| | DISPENSER(S) STOCKED AT THE WATER COOLER. THE |
| | DISPENSER(S) SHOULD REMAIN IN PLACE AFTER DRINKING |
| | FOUNTAINS HAVE BEEN INSTALLED TO ACCOMMODATE YOUNGER |
| | CHILDREN. PLAN SHEET P-2/DETAIL 5 SHOWS OPTIONAL |
| | DISPENSER. IT IS RECOMMENDED YOU REMOVE THE WORD |
| | "OPTIONAL", ADD "ACCESSIBLE FLAT BOTTOM CUP DISPENSER" |
| | AND SHOW ACCESSIBILITY AS REQUIRED IN FBC ACC CHAPTER |
| | 3. |
| | |
| | 14.REGARDING P-1, PLUMBING NOTE 1, THE PREVAILING CODE |
| | FOR THIS PROJECT IS FBC 2017, NOT 2020. PER WPB FBC |
| | 107.2.1, CLARIFY. |
| | |
| | 15.PER WPB FBC 107.2.1, REVISE PLUMBING NOTE 11 BY |
| | REPLACING THE DESIGNATED M COPPER WITH L AS PER COPPER |
| | & COPPER ALLOY TUBE AND PIPE STANDARDS PUBLISHED BY THE |
| | COPPER DEVELOPMENT ASSOCIATION STATES "SEAMLESS COPPER |
| | WATER TUBE IS MANUFACTURED IN SIZES 1/4 INCH THROUGH 12 |
| | INCH NOMINAL. TYPES K AND L ARE MANUFACTURED IN DRAWN |
| | TEMPER (HARD) 1/4 INCH THROUGH 12 INCH AND ANNEALED |
| | TEMPER (SOFT) COILS 1/4 INCH THROUGH 2 INCH WHILE TYPE |
| | M IS ONLY MANUFACTURED IN DRAWN (HARD) TEMPER 1/4 INCH |
| | THROUGH 12 INCH." |
| | |
| | 16.PER WPB FBC 107.2.1, PROVIDE NOTE "ALL COMPONENTS IN |
| | THE DOMESTIC WATER SYSTEM SHALL BE LEAD FREE." |
| | |
| | 17.PER WPB FBC 107.2.1, PROVIDE SPECIFICATION FOR |
| | PLUMBING VALVES. |
| | |
| | 18.PER WPB FBC 107.2.1, PROVIDE SPECIFICATION AND |
| | DETAIL FOR PIPE HANGERS. SPECIFY SPACING TO COMPLY WITH |
| | FBC PL TABLE 308.5. |
| | |
| | 19.PER FBC PL E607.5 AND FBC EC C404.4.2, INSULATE THE |
| | FIRST 8 FEET OF OUTLET PIPING FROM TANK TYPE WATER |
| | HEATER. PER WPB FBC 107.2.1, SPECIFY THE INSULATION TO |
| | COMPLY WITH FBC EC TABLE C403.2.10. |
| | |
| | 20.PER WPB FBC 107.2.1, SIZE ALL VERTICAL WASTE AND ALL |
| | VENTS ON SANITARY RISER DIAGRAM. |
| | |
| | 21.RELOCATED MOP SINK APPEARS TO BE FLOOR MOUNTED (SEE |
| | PLAN P-3). PER WPB FBC 107.2.1, PLEASE CONFIRM AND |
| | PROVIDE FAUCET INFORMATION. DOES THE SPOUT HAVE A HOSE |
| | THREAD CONNECTION. PROVIDE BACKFLOW PROTECTION AS |
| | REQUIRED IN FBC PL SECTION 608. |
| | |
| | 22.PER WPB FBC 107.2.1, SHOW ON ALL ELEVATION VIEWS OF |
| | ACCESSIBLE WATER CLOSETS PLAN SHEETS P-2 AND P-3, FLUSH |
| | CONTROLS TO BE ON OPEN SIDE OF WATER CLOSET PER FBC ACC |
| | 604.6, NOT ADJACENT TO SIDE WALL AS IS CURRENTLY SHOWN. |
| | |
| | 23.PER WPB FBC 107.2.1, CLARIFY AND RECONCILE URINAL |
| | ELEVATION MEASUREMENTS ON P-2 AND P-3. |
| | |
| | 24.MEASUREMENTS TO GRAB BAR FROM FINISH FLOOR SHALL BE |
| | TO THE TOP OF GRAB BAR, NOT THE CENTER PER FBC ACC |
| | 609.4. |
| | |
| | 25.PER WPB FBC 107.2.1, PROVIDE SPEC/SCHEDULE FOR THREE |
| | COMPARTMENT SINK AND HAND SINK AND FAUCET IN |
| | STORAGE/BREAK ROOM. PER FBC ACC 603, THE HAND SINK |
| | SHALL BE INSTALLED WITH THE FRONT OF THE HIGHER OF THE |
| | RIM OR COUNTER SURFACE 34 INCHES MAXIMUM ABOVE THE |
| | FINISH FLOOR OR GROUND PER FBC ACC 606.3, ADDITIONALLY |
| | SHOW TOE AND KNEE CLEARANCE AS REQUIRED BY FBC ACC |
| | 306.2 AND 306.3 FOR FORWARD APPROACH. PER FBC ACC |
| | 605.5, WATER SUPPLY & DRAINPIPES UNDER LAVATORIES AND |
| | SINKS SHALL BE INSULATED OR OTHERWISE CONFIGURED TO |
| | PROTECT AGAINST CONTACT. |
| | |
| | 26.REGARDING P-1; NOTE 468.3.5.12 HOT WATER, PER WPB |
| | FBC 107.2.1, ADD "PER FBC PL 416.5, SAID MIXING VALVE |
| | SHALL CONFORM TO ASSE 1070." |
| | |
| | 27.HOT WATER DISTRIBUTION APPEARS TO BE EXCESSIVELY |
| | OVERSIZED. ACCORDING TO YOUR CALCULATIONS THE LOAD ON |
| | THE HOT WATER SYSTEM IS 9.75 WSFU. FBC PL TABLE |
| | E103.3(3) INDICATES A DEMAND OF 14.6 GPM POSSIBLY |
| | ALLOWING 3/4 INCH PIPING, DECREASING TO 1/2 INCH AS THE |
| | DEMAND DROPS (SEE FBC PL FIGURE 103.3(2) BETWEEN 5 FPS |
| | AND 10 FPS). PLEASE NOTE THAT FBC EC C404.5 LIMITS THE |
| | VOLUME OF WATER THAT MAY TRAVEL THROUGH A HOT WATER |
| | PIPE AND PROVIDES MEANS TO CALCULATE THE MAXIMUM PIPE |
| | SIZE TO ELIMINATE THE AMOUNT OF COLD WATER DISCHARGED |
| | BEFORE HOT WATER REACHES THE OUTLET, THUS REDUCING |
| | ENERGY USAGE AS WELL AS THE WASTING OF WATER. PER WPB |
| | FBC 107.2.1, NOTE THE GPM FOR THE HOT WATER DEMAND. |
| | REVISIT AND SIZE THE HOT WATER DISTRIBUTION |
| | ACCORDINGLY. |
| | |
| | 28.PER FBC PL E607.5 AND FBC EC C404.4.2, INSULATE THE |
| | FIRST 8 FEET OF OUTLET PIPING FROM TANK TYPE WATER |
| | HEATER. PER WPB FBC 107.2.1, SPECIFY THE INSULATION TO |
| | COMPLY WITH FBC EC TABLE C403.2.10. |
| | |
| | 29.WATER DISTRIBUTION PLAN VIEW AT EXISTING WATER |
| | HEATER SHOWS 2 INCH COLD WATER FROM EXISTING WATER |
| | SUPPLY LINE. PER WPB FBC 107.2.1, CLARIFY AS THERE IS |
| | NOTHING ELSE IN THE DRAWINGS TO INDICATE THIS. |
| | |
| | 30.IT IS NOTED THAT THE WATER HEATER IS EXISTING. |
| | PLEASE BE ADVISED THAT IF ANY WORK OR MODIFICATION TO |
| | THE PIPING TO THE WATER HEATER IS MADE THEN THE |
| | REQUIREMENTS OF FBC PL CHAPTERS 5 AND 6 SHALL BE MET. |
| | PER WPB FBC 107.2.1, A DETAIL OF WATER HEATER SHOWING |
| | HEATER SHALL BE PROVIDED SHOWING HEATER W/STORAGE |
| | CAPACITY, PIPING INCLUDING CW, HW, VALVES (INCLUDING |
| | VACUUM RELIEF VALVE IF APPLICABLE FBC PL 504.2) , |
| | THERMAL EXPANSION CONTROL DEVICE (INCLUDING SIZE), T&P |
| | DISCHARGE (INCLUDING TERMINATION) AND WATER HEATER PAN |
| | AND DRAIN (INCLUDING TERMINATION) PER WPB FPC 107.2.1; |
| | COMPLY WITH FBC PL 607.3, 503.1, 504.1, 504.4, 504.4.1, |
| | 504.5, 504.6, 504.7, 504.7.1 AND 504.7.2. |
| | |
| | 31.REGARDING THE WATER COOLER TEMPORARY USAGE DUE TO |
| | COVID 19, PROVIDE ACCESSIBLE FLAT BOTTOM CUP |
| | DISPENSER(S) STOCKED AT THE WATER COOLER. THE |
| | DISPENSER(S) SHOULD REMAIN IN PLACE AFTER DRINKING |
| | FOUNTAINS HAVE BEEN INSTALLED TO ACCOMMODATE YOUNGER |
| | CHILDREN. PLAN SHEET P-2/DETAIL 5 SHOWS OPTIONAL |
| | DISPENSER. IT IS RECOMMENDED YOU REMOVE THE WORD |
| | "OPTIONAL", ADD "ACCESSIBLE FLAT BOTTOM CUP DISPENSER" |
| | AND SHOW ACCESSIBILITY AS REQUIRED IN FBC ACC CHAPTER |
| | 3. |
| | |
| | 32.REGARDING P-1, PLUMBING NOTE 1, THE PREVAILING CODE |
| | FOR THIS PROJECT IS FBC 2017, NOT 2020. PER WPB FBC |
| | 107.2.1, CLARIFY. |
| | |
| | 33.PER WPB FBC 107.2.1, REVISE PLUMBING NOTE 11 BY |
| | REPLACING THE DESIGNATED M COPPER WITH L AS PER COPPER |
| | & COPPER ALLOY TUBE AND PIPE STANDARDS PUBLISHED BY THE |
| | COPPER DEVELOPMENT ASSOCIATION STATES "SEAMLESS COPPER |
| | WATER TUBE IS MANUFACTURED IN SIZES 1/4 INCH THROUGH 12 |
| | INCH NOMINAL. TYPES K AND L ARE MANUFACTURED IN DRAWN |
| | TEMPER (HARD) 1/4 INCH THROUGH 12 INCH AND ANNEALED |
| | TEMPER (SOFT) COILS 1/4 INCH THROUGH 2 INCH WHILE TYPE |
| | M IS ONLY MANUFACTURED IN DRAWN (HARD) TEMPER 1/4 INCH |
| | THROUGH 12 INCH." |
| | |
| | 34.PER WPB FBC 107.2.1, PROVIDE NOTE "ALL COMPONENTS IN |
| | THE DOMESTIC WATER SYSTEM SHALL BE LEAD FREE." |
| | |
| | 35.PER WPB FBC 107.2.1, PROVIDE SPECIFICATION FOR |
| | PLUMBING VALVES. |
| | |
| | 36.PER WPB FBC 107.2.1, PROVIDE SPECIFICATION AND |
| | DETAIL FOR PIPE HANGERS. SPECIFY SPACING TO COMPLY WITH |
| | FBC PL TABLE 308.5. |
| | |
| | 37.PER FBC PL 1002.4.1, PROVIDE TRAP SEAL PROTECTION |
| | FOR BATHROOM FLOOR DRAINS COMPLYING WITH 1002.4.1.1, |
| | 1002.4.1.2, 1002.4.1.3 OR 1002.4.1.4. IF ONE OF THE |
| | FIRST THREE METHODS ARE SELECTED SHOW FEED INTO FLOOR |
| | DRAIN AND SOURCE ON THE PLAN; PROVIDE A MANUFACTURER |
| | SPECIFICATION AND AND DETAIL. IF THE FOURTH METHOD IS |
| | CHOSEN, PROVIDE A MANUFACTURER SPECIFICATION. |
| | |
| | |
| | |
| | |
| | END OF COMMENTS. |
| | |
| | |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | ALL ELECTRONIC PLANS TO BE DIGITALLY SIGNED AND SEALED |
| | BY THE DESIGNER IN ACCORDANCE WITH FAC AND FS. |
| | |
| | |
| | |
| | JERALD SMITH |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | EMAIL [email protected] |
| | PHONE 561-246-0882 MOBILE |
| | 20090644 2508 N AUSTRALIAN AVE |