| 2020-11-06 10:49:13 | CODES IN EFFECT |
| | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | FAC = FLORIDA ADMINISTRATIVE CODE |
| | |
| | ELECTRICAL REVIEW STATUS: FAILED. |
| | |
| | SAME COMMENTS AS PRIOR REVIEW. SEE BELOW: |
| | |
| | 1) NO ELECTRIC IS SHOWN. NOT ENOUGH INFORMATION TO MAKE |
| | A GOOD REVIEW OF THE FACILITY. |
| | |
| | 2) OUTLETS IN A DAY CARE OCCUPANCY SHALL BE TAMPER |
| | RESISTANT TYPE PER 406.12(C) |
| | |
| | 3) 406.12 TAMPER-RESISTANT RECEPTACLES TAMPER-RESISTANT |
| | RECEPTACLES SHALL BE INSTALLED AS SPECIFIED IN |
| | 406.12(A) THROUGH (C). |
| | 4) (C) CHILD CARE FACILITIES. IN ALL CHILD CARE |
| | FACILITIES, ALL NONLOCKING-TYPE 125-VOLT, 15- AND |
| | 20-AMPERE RECEPTACLES SHALL BE LISTED TAMPER-RESISTANT |
| | RECEPTACLES. |
| | |
| | 406.2 DEFINITION CHILD CARE FACILITY. A BUILDING OR |
| | STRUCTURE, OR PORTION THEREOF, FOR EDUCATIONAL, |
| | SUPERVISORY, OR PERSONAL CARE SERVICES FOR MORE THAN |
| | FOUR CHILDREN 7 YEARS OLD OR LESS. |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. |
| | |