| 2020-11-06 13:48:02 | CHANGE OF OCCUPANCY CLASSIFICATION FROM (B) TO(E) |
| | REVIEWED BY ROGER MCPHERSON |
| | 561-805-6716 |
| | [email protected] |
| | CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1 |
| | AMENDMENTS |
| | 2017 FBC EXISTING BUILDING - CHANGE OF OCCUPANCY |
| | CLASSIFICATION |
| | |
| | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 |
| | 1) OCCUPANT LOAD SHOULD BE DETERMINED BY ROOM USE PER |
| | FBC 1004 - SHOW THE USE AND THE OCCUPANT LOAD FOR EACH |
| | ROOM. |
| | 2) PLEASE SHOW ALL DOOR WIDTHS - FBC 1010.1.1 |
| | 3) PLEASE SHOW THAT DOORS THAT SWING INTO THE CORRIDOR |
| | COMPLY WITH - 1005.7.1 DOORS. |
| | DOORS, WHEN FULLY OPENED, SHALL NOT REDUCE THE REQUIRED |
| | WIDTH BY MORE THAN 7 INCHES (178 MM). DOORS IN ANY |
| | POSITION SHALL NOT REDUCE THE REQUIRED WIDTH BY MORE |
| | THAN ONE-HALF. |
| | 4) PLEASE SHOW THE GLAZING IN THE FIRE RATED CORRIDOR |
| | WALLS COMPLIES WITH FBC 716.2 |
| | 5) PLEASE SHOW THE FIRE RATING, SELF LATCHING AND SELF |
| | CLOSING OF THE CORRIDOR DOORS TO COMPLY WITH FBC 716 |
| | 6) EGRESS DOOR IN THE "MULTIPURPOSE ROOM" LEADING TO |
| | THE EGRESS CORRIDOR NEEDS TO COMPLY WITH FBC 1010.1.2.1 |
| | DIRECTION OF SWING. |
| | PIVOT OR SIDE-HINGED SWINGING DOORS SHALL SWING IN THE |
| | DIRECTION OF EGRESS TRAVEL WHERE SERVING A ROOM OR AREA |
| | CONTAINING AN OCCUPANT LOAD OF 50 OR MORE PERSONS |
| | (ASSEMBLY AT 7SQ.FT. PER PERSON = 244 OCCUPANTS) - |
| | PLEASE PROVIDE AN EXIT SIGN AT THIS LOCATION ALSO. |
| | 7) PLEASE SHOW THE CORRIDOR WALL FIRE RATING TO COMPLY |
| | WITH FBC 466.8 (FBC 708.4 CONTINUITY. FIRE PARTITIONS |
| | SHALL EXTEND FROM THE TOP OF THE FOUNDATION OR |
| | FLOOR/CEILING ASSEMBLY BELOW TO THE UNDERSIDE OF THE |
| | FLOOR OR ROOF SHEATHING, SLAB OR DECK ABOVE OR TO THE |
| | FIRE-RESISTANCE-RATED FLOOR/CEILING OR ROOF/CEILING |
| | ASSEMBLY ABOVE, AND SHALL BE SECURELY ATTACHED |
| | THERETO.) |
| | 8) PLEASE SHOW FIRE ALARMS TO COMPLY WITH - FBC 466.7 |
| | -- SHOW LOCATION OF SMOKE DETECTORS TO COMPLY WITH |
| | 466.7.2DETECTION. |
| | A SMOKE DETECTION SYSTEM SHALL BE INSTALLED IN |
| | ACCORDANCE WITH NFPA 72, WITH PLACEMENT OF DETECTORS IN |
| | EACH STORY IN FRONT OF DOORS TO THE STAIRWAYS AND IN |
| | THE CORRIDORS OF ALL FLOORS OCCUPIED BY THE DAY CARE |
| | OCCUPANCY. DETECTORS ALSO SHALL BE INSTALLED IN |
| | LOUNGES, RECREATION AREAS AND SLEEPING ROOMS IN THE DAY |
| | CARE OCCUPANCY. |
| | 9) PLEASE STATE ON THE SITE PLAN THAT THE PARKING LOT |
| | AND EXTERIOR PLAY AREA WILL BE ON A SEPARATE PERMIT. |
| | 10) ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND |
| | ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF |
| | THE PERSON |
| | RESPONSIBLE FOR THE DESIGN. FBC WPB AMENDMENTS 107.2.1 |
| | 11) PLEASE MARK ALL ARCHITECTURAL DRAWINGS BY STEVE |
| | SIEBERT FOR REFERENCE ONLY - OR PROVIDE ORIGINAL SIGNED |
| | AND SEALED DRAWINGS FROM ARCHITECT STEVE SIEBERT |
| | WITHOUT THE CITY STAMP ON THEM. |
| | 12) SHOW NEW RESTROOM TO MEET ACCESSIBILITY |
| | REQUIREMENTS FBC ACCESSIBILITY 213.2 |
| | 13) SHOW ALL REQUIRED EXIT SIGNS TO COMPLY WITH FBC |
| | 1013.1 |
| | 14) SHOW EXIT EMERGENCY LIGHTING TO COMPLY WITH FBC |
| | 1008.3 |
| | |