| 2020-09-17 16:18:06 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | 1) THERE IS INSUFFICIENT INFOORMATION PROVIDED TO |
| | CONDUCT A DETAILED LIFE SAFETY REVIEW. |
| | |
| | A CHILDCARE/DAYCARE OCCUPANCY SHALL COMPLY WITH THE |
| | REQUIREMENTS OF THE 6TH ED. OF THE FLORIDA FIRE |
| | PREVENTION CODE INCLUDING NFPA 101 AND NFPA 1; 2015 ED. |
| | |
| | 16.1 GENERAL REQUIREMENTS. |
| | 16.1.1* APPLICATION. |
| | 16.1.1.1 THE REQUIREMENTS OF THIS CHAPTER SHALL APPLY |
| | TO NEW |
| | BUILDINGS OR PORTIONS THEREOF USED AS DAY-CARE |
| | OCCUPANCIES. (SEE |
| | 1.3.1.) |
| | |
| | 16.1.1.4 THE REQUIREMENTS OF SECTIONS 16.1 THROUGH 16.5 |
| | AND |
| | SECTION 16.7 SHALL APPLY TO DAY-CARE OCCUPANCIES IN |
| | WHICH MORE |
| | THAN 12 CLIENTS RECEIVE CARE, MAINTENANCE, AND |
| | SUPERVISION BY |
| | OTHER THAN THEIR RELATIVE(S) OR LEGAL GUARDIAN(S) FOR |
| | LESS THAN 24 |
| | HOURS PER DAY. |
| | |
| | 16.1.1.6 WHERE A FACILITY HOUSES MORE THAN ONE AGE |
| | GROUP OR SELFPRESERVATION |
| | CAPABILITY, THE STRICTEST REQUIREMENTS APPLICABLE TO |
| | ANY GROUP PRESENT SHALL APPLY THROUGHOUT THE DAY-CARE |
| | OCCUPANCY |
| | OR BUILDING, AS APPROPRIATE TO A GIVEN AREA, UNLESS THE |
| | AREA HOUSING |
| | SUCH A GROUP IS MAINTAINED AS A SEPARATE FIRE AREA. |
| | |
| | PLEASE PROVIDE DETAILS |
| | |
| | |
| | |
| | |
| | 2) THE APPLICATION INDICATES AN OCCUPANCY CHANGE FROM |
| | BUSINESS TO CHILDCARE |
| | |
| | THERE APPEARS TO BE A BAND, DANCE AND OTHER PRIVATE |
| | LESSON ROOMS AND A PRE-SCHOOLD ROOM. |
| | |
| | |
| | 16.1.2 CLASSIFICATION OF OCCUPANCY. SEE 6.1.4. |
| | 16.1.2.1 GENERAL. OCCUPANCIES THAT INCLUDE PRESCHOOLS, |
| | KINDERGARTENS, AND OTHER SCHOOLS WHOSE PURPOSE IS |
| | PRIMARILY |
| | EDUCATIONAL FOR CHILDREN 24 MONTHS OF AGE OR OLDER, |
| | EVEN THOUGH |
| | THE CHILDREN WHO ATTEND SUCH SCHOOLS ARE OF PRESCHOOL |
| | AGE, SHALL |
| | COMPLY WITH THE PROVISIONS OF CHAPTER 14. |
| | |
| | |
| | PLEASE PROVIDE A DETAILED NARRATIVE OF THE NATURE OF |
| | THE CARE, PROPOSED AGES, |
| | |
| | |
| | |
| | |
| | 3) THERE ARE NO INDICATIONS OF FIRE SPRINKLER AND/OR |
| | FIRE ALARM SYSTEMS. |
| | |
| | PER NFPA 101 |
| | |
| | 16.3.4 DETECTION, ALARM, AND COMMUNICATIONS SYSTEMS. |
| | 16.3.4.1 GENERAL. DAY-CARE OCCUPANCIES, OTHER THAN |
| | DAY-CARE |
| | OCCUPANCIES HOUSED IN ONE ROOM HAVING AT LEAST ONE DOOR |
| | OPENING DIRECTLY TO THE OUTSIDE AT GRADE PLANE OR TO AN |
| | EXTERIOR |
| | EXIT ACCESS BALCONY IN ACCORDANCE WITH 7.5.3, SHALL BE |
| | PROVIDED |
| | WITH A FIRE ALARM SYSTEM IN ACCORDANCE WITH SECTION |
| | 9.6. |
| | |
| | 16.3.4.5 DETECTION. A SMOKE DETECTION SYSTEM IN |
| | ACCORDANCE |
| | WITH SECTION 9.6 SHALL BE INSTALLED IN DAY-CARE |
| | OCCUPANCIES, OTHER |
| | THAN THOSE HOUSED IN ONE ROOM HAVING AT LEAST ONE DOOR |
| | OPENING |
| | DIRECTLY TO THE OUTSIDE AT GRADE PLANE OR TO AN |
| | EXTERIOR EXIT ACCESS |
| | BALCONY IN ACCORDANCE WITH 7.5.3, AND SUCH SYSTEM SHALL |
| | COMPLY |
| | WITH BOTH OF THE FOLLOWING: |
| | (1) DETECTORS SHALL BE INSTALLED ON EACH STORY IN FRONT |
| | OF THE DOORS |
| | TO THE STAIRWAYS AND IN THE CORRIDORS OF ALL FLOORS |
| | OCCUPIED BY |
| | THE DAY-CARE OCCUPANCY. |
| | (2) DETECTORS SHALL BE INSTALLED IN LOUNGES, RECREATION |
| | AREAS, AND |
| | SLEEPING ROOMS IN THE DAY-CARE OCCUPANCY. |
| | |
| | 16.3.5 EXTINGUISHMENT REQUIREMENTS. |
| | 16.3.5.1 ANY REQUIRED SPRINKLER SYSTEMS SHALL BE IN |
| | ACCORDANCE WITH |
| | SECTION 9.7. |
| | 16.3.5.2 REQUIRED SPRINKLER SYSTEMS SHALL BE INSTALLED |
| | IN ACCORDANCE |
| | WITH 9.7.1.1(1). |
| | |
| | PLEASE REVIEW AND PROVIDE DETAILS. |
| | |
| | |
| | |
| | 4) THERE IS AN INDICATION OF SEVERAL CORRIDORS. |
| | |
| | 16.3.6 CORRIDORS. EVERY INTERIOR CORRIDOR SHALL BE |
| | CONSTRUCTED OF |
| | WALLS HAVING NOT LESS THAN A 1-HOUR FIRE RESISTANCE |
| | RATING IN |
| | ACCORDANCE WITH SECTION 8.3, UNLESS OTHERWISE PERMITTED |
| | BY ANY OF |
| | THE FOLLOWING: |
| | (1) CORRIDOR PROTECTION SHALL NOT BE REQUIRED WHERE ALL |
| | SPACES |
| | NORMALLY SUBJECT TO CLIENT OCCUPANCY HAVE NOT LESS THAN |
| | ONE |
| | DOOR OPENING DIRECTLY TO THE OUTSIDE OR TO AN EXTERIOR |
| | EXIT |
| | ACCESS BALCONY OR CORRIDOR IN ACCORDANCE WITH 7.5.3. |
| | (2) IN BUILDINGS PROTECTED THROUGHOUT BY AN APPROVED, |
| | SUPERVISED |
| | AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH SECTION |
| | 9.7, |
| | CORRIDOR WALLS SHALL NOT BE REQUIRED TO BE RATED, |
| | PROVIDED THAT |
| | SUCH WALLS FORM SMOKE PARTITIONS IN ACCORDANCE WITH |
| | SECTION |
| | 8.4. |
| | (3) WHERE THE CORRIDOR CEILING IS AN ASSEMBLY HAVING A |
| | 1-HOUR FIRE |
| | RESISTANCE RATING WHERE TESTED AS A WALL, THE CORRIDOR |
| | WALLS |
| | SHALL BE PERMITTED TO TERMINATE AT THE CORRIDOR |
| | CEILING. |
| | (4) LAVATORIES SHALL NOT BE REQUIRED TO BE SEPARATED |
| | FROM CORRIDORS, |
| | PROVIDED THAT THEY ARE SEPARATED FROM ALL OTHER SPACES |
| | BY WALLS |
| | HAVING NOT LESS THAN A 1-HOUR FIRE RESISTANCE RATING IN |
| | ACCORDANCE WITH SECTION 8.3. |
| | (5) LAVATORIES SHALL NOT BE REQUIRED TO BE SEPARATED |
| | FROM CORRIDORS, |
| | PROVIDED THAT BOTH OF THE FOLLOWING CRITERIA ARE MET: |
| | (A) THE BUILDING IS PROTECTED THROUGHOUT BY AN |
| | APPROVED, |
| | SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE |
| | WITH |
| | SECTION 9.7. |
| | (B) THE WALLS SEPARATING THE LAVATORY FROM OTHER ROOMS |
| | FORM |
| | SMOKE PARTITIONS IN ACCORDANCE WITH SECTION 8.4. |
| | WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET REVISION |
| | CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE ABOVE. |
| | ADDITIONAL COMMENTS MAY BE PROVIDED ON THE RE-SUBMITTAL |
| | OF THE ABOVE. |
| | |
| | PLEASE REIVEW AND PROVIDE DETAILS |
| | |
| | |
| | |
| | 5) THERE ARE SERVAL EXIT DOORS BUT NO OCCUPANCY LOAD |
| | CALCULATION. |
| | |
| | 16.2.2.2.2 PANIC HARDWARE OR FIRE EXIT HARDWARE. ANY |
| | DOOR IN A |
| | REQUIRED MEANS OF EGRESS FROM AN AREA HAVING AN |
| | OCCUPANT LOAD OF |
| | 100 OR MORE PERSONS SHALL BE PERMITTED TO BE PROVIDED |
| | WITH A LATCH |
| | OR LOCK ONLY IF THE LATCH OR LOCK IS PANIC HARDWARE OR |
| | FIRE EXIT |
| | HARDWARE COMPLYING WITH 7.2.1.7. |
| | |
| | 16.2.2.2.4* DOOR LATCHES. EVERY DOOR LATCH TO CLOSETS, |
| | STORAGE |
| | AREAS, KITCHENS, AND OTHER SIMILAR SPACES OR AREAS |
| | SHALL BE SUCH |
| | THAT CLIENTS CAN OPEN THE DOOR FROM INSIDE THE SPACE OR |
| | AREA. |
| | 16.2.2.2.5 BATHROOM DOORS. EVERY BATHROOM DOOR LOCK |
| | SHALL BE |
| | DESIGNED TO ALLOW OPENING OF THE LOCKED DOOR FROM THE |
| | OUTSIDE |
| | BY AN OPENING DEVICE THAT SHALL BE READILY ACCESSIBLE |
| | TO THE STAFF. |
| | |
| | PLEASE REIVEW AND PROVIDE DETAILS |
| | |
| | |
| | |
| | 6) THERE ARE WINDOWS INDICATED BUT NO DETAILES. |
| | |
| | 16.2.11.1 WINDOWS FOR RESCUE. |
| | 16.2.11.1.1 EVERY ROOM OR SPACE NORMALLY SUBJECT TO |
| | CLIENT |
| | OCCUPANCY, OTHER THAN BATHROOMS, SHALL HAVE NOT LESS |
| | THAN ONE |
| | OUTSIDE WINDOW FOR EMERGENCY RESCUE THAT COMPLIES WITH |
| | ALL OF THE |
| | FOLLOWING, UNLESS OTHERWISE PERMITTED BY 16.2.11.1.2: |
| | (1) SUCH WINDOWS SHALL BE OPENABLE FROM THE INSIDE |
| | WITHOUT THE |
| | USE OF TOOLS AND SHALL PROVIDE A CLEAR OPENING OF NOT |
| | LESS THAN |
| | 20 IN. (510 MM) IN WIDTH, 24 IN. (610 MM) IN HEIGHT, |
| | AND 5.7 |
| | FT2 (0.5 M2) IN AREA. |
| | (2) THE BOTTOM OF THE OPENING SHALL BE NOT MORE THAN 44 |
| | IN. (1120 |
| | MM) ABOVE THE FLOOR. |
| | (3) THE CLEAR OPENING SHALL ALLOW A RECTANGULAR SOLID, |
| | WITH A WIDTH |
| | AND HEIGHT THAT PROVIDES NOT LESS THAN THE REQUIRED 5.7 |
| | FT2 (0.5 |
| | M2) OPENING AND A DEPTH OF NOT LESS THAN 20 IN. (510 |
| | MM), TO |
| | PASS FULLY THROUGH THE OPENING. |
| | 16.2.11.1.2 THE REQUIREMENTS OF 16.2.11.1.1 SHALL NOT |
| | APPLY TO |
| | EITHER OF THE FOLLOWING: |
| | (1) BUILDINGS PROTECTED THROUGHOUT BY AN APPROVED, |
| | SUPERVISED |
| | AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH SECTION |
| | 9.7 |
| | (2) WHERE THE ROOM OR SPACE HAS A DOOR LEADING DIRECTLY |
| | TO AN EXIT |
| | OR DIRECTLY TO THE OUTSIDE OF THE BUILDING |
| | |
| | PLEASE REIVEW AND PROVIDE DETAILS |
| | |
| | |
| | 7) THERE ARE TWO DOORS THAT APPEAR TO OPEN OUT INTO THE |
| | REQUIRED EGRESS PATH. |
| | |
| | ONE DOOR IS INDICATED IN THE REAR CORRIDOR OPPISTE THE |
| | STAFF RESTROOM. |
| | |
| | THE OTHER IS LOCATED FROM THE FRONT CORRIDOR INTO THE |
| | LOBBY. |
| | |
| | PER NFPA 101 CHAPTER 7, MEANS OF EGRESS |
| | |
| | 7.2.1.4.3 DOOR LEAF ENCROACHMENT |
| | 7.2.1.4.3.1 DURING ITS SWING, ANY DOOR LEAF IN A MEANS |
| | OF EGRESS SHALL LEAVE NOT LESS THAN ONE-HALF OF THE |
| | REQUIRED WIDTH OF AN AISLE, A CORRIDOR, A PASSAGEWAY, |
| | OR A LANDING UNOBSTRUCTED AND SHALL NOT PROJECT NOT |
| | MORE THAN 7 IN. INTO THE REQUIRED WIDTH OF AN AISLE, A |
| | CORRIDOR, A PASSAGE WAY, OR A LANDING, WHEN FULLY OPEN, |
| | UNLESS BOTH OF THE FOLLOWING CONDITIONS ARE MET: |
| | (1) THE DOOR OPENING PROVIDES ACCESS TO A STAIR IN AN |
| | EXISTING BUILDING. |
| | (2) THE DOOR OPENING MEETS THE REQUIREMENTS THAT LIMITS |
| | PROJECTION TO NOT MORE THAN 7 IN. INTO THE REQUIRED |
| | WIDTH OF THE STAIR LANDING WHEN THE DOOR |
| | LEAF IS FULLY OPEN. |
| | |
| | PLEASE REIVEW AND CORRECT |
| | |
| | |
| | |
| | 8) THERE IS AN INDICATION OF A KITCHEN WITH A STOVE |
| | TOP. |
| | |
| | 16.3.2.3 COOKING FACILITIES SHALL BE PROTECTED IN |
| | ACCORDANCE WITH |
| | 9.2.3, UNLESS OTHERWISE PERMITTED BY 16.3.2.4 OR |
| | 16.3.2.5. |
| | |
| | 9.2.3 COMMERCIAL COOKING OPERATIONS. WHERE REQUIRED BY |
| | ANOTHER |
| | SECTION OF THIS CODE, COMMERCIAL COOKING OPERATIONS |
| | SHALL BE PROTECTED |
| | IN ACCORDANCE WITH NFPA 96, STANDARD FOR VENTILATION |
| | CONTROL AND |
| | FIRE PROTECTION OF COMMERCIAL COOKING OPERATIONS, |
| | UNLESS SUCH |
| | INSTALLATIONS ARE APPROVED EXISTING INSTALLATIONS, |
| | WHICH SHALL BE |
| | PERMITTED TO BE CONTINUED IN SERVICE. |
| | |
| | 16.3.2.4 OPENINGS SHALL NOT BE REQUIRED TO BE PROTECTED |
| | BETWEEN |
| | FOOD PREPARATION AREAS AND DINING AREAS. |
| | |
| | 16.3.2.5 APPROVED DOMESTIC COOKING EQUIPMENT USED FOR |
| | FOOD |
| | WARMING OR LIMITED COOKING SHALL NOT BE REQUIRED TO BE |
| | PROTECTED. |
| | |
| | PLEASE REVIEW AND PROVIDE DETAILS OR CORRECT PER 9.2.3 |
| | |
| | |
| | |
| | 9) THERE IS NO LIFE SAFETY PLAN |
| | |
| | 4.6.9 CONDITIONS FOR OCCUPANCY. |
| | 4.6.9.1 NO NEW CONSTRUCTION OR EXISTING BUILDING SHALL |
| | BE |
| | OCCUPIED IN WHOLE OR IN PART IN VIOLATION OF THE |
| | PROVISIONS OF THIS |
| | CODE, UNLESS THE FOLLOWING CONDITIONS EXIST: |
| | (1) A PLAN OF CORRECTION HAS BEEN APPROVED. |
| | (2) THE OCCUPANCY CLASSIFICATION REMAINS THE SAME. |
| | (3) NO SERIOUS LIFE SAFETY HAZARD EXISTS AS JUDGED BY |
| | THE |
| | AUTHORITY HAVING JURISDICTION. |
| | |
| | PLEASE PROVIDE A DETAILED LIFE SAFETY PLAN |
| | |
| | |
| | |
| | 10) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | |
| | 11) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |