| | 1ST REVIEW FBC-2017 RES. FUEL GAS |
| | PERMIT- 20090641 |
| | 10/22/2020 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHOW THE SEPARATION DISTANCE BETWEEN THE TWO |
| | UNDERGROUND TANKS. A 3 FT. SEPARATION IS REQUIRED PER |
| | TABLE 6.3.1.1 NFPA 58-14. |
| | |
| | 2) REVISE THE RISER DRAWING TO SHOW THE TANKS |
| | MANIFOLDED TOGETHER, AND PROVIDE A DETAIL SHOWING HOW |
| | THE PIPING INTERCONNECTION WILL BE MADE- SECTION |
| | 6.9.3.9 NFPA 58. PLEASE NOTE THAT PE PIPE CANNOT BE |
| | USED FOR PERMANENT INTERCONNECTION OF THE TANKS- |
| | SECTION 6.9.3.9B NFPA 58. |
| | |
| | 3) SHOW HOW THE REGULATOR WILL BE CONNECTED TO THE |
| | MANIFOLD- SECTION 6.8.1.1 NFPA 58. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |