| 2021-06-24 11:16:11 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION |
| | SERVICES/ BUILDING DIVISION |
| | 2017 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 20090622 |
| | ADD: 428 CLEMATIS ST. |
| | CONT: FOREMOST GENERAL CONTRACTING INC. |
| | TEL: 954-953-7991 |
| | E-MAIL: [email protected] |
| | |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 4TH REVIEW |
| | DATE: THURS. JUNE 24TH / / 2021 |
| | ACTION: DENIED |
| | |
| | 1) LIFE SAFETY PLAN LS1 & A2: THE OCCUPANT LOAD |
| | CALCULATIONS INDICATE 32 OCCUPANTS, BUT THE PLANS KEEP |
| | STATING FOR BUSINESS OCCUPANCY YOU ARE ALLOWED COMMON |
| | PATH OF TRAVEL FOR BUSINESS OCCUPANCY 100 FEET MAXIMUM |
| | 30 OCCUPANTS. THIS IS TAKEN FROM THE 2017 FBC-BUILDING |
| | TABLE 1006.1.2. THIS IS CORRECT, BUT FOR 32 OCCUPANTS, |
| | BUSINESS OCCUPANCY, NON-SPRINKLERED YOUR COMMON PATH OF |
| | TRAVEL IS 75 FEET. FROM THE FURTHEST POINT IN THE |
| | FURTHEST RESTROOM TO THE FRONT ENTRY IS 80 FEET WHEN |
| | MEASURED TO YOUR DRAWINGS. IF YOU REDUCE YOU OCCUPANT |
| | LOAD BY TWO YOUR OCCUPANT LOAD OF 30 WOULD QUALIFY FOR |
| | COMMON PATH OF TRAVEL OF 100 FEET FOR A BUSINESS |
| | OCCUPANCY NON-SPRINKLERED AND AN OCCUPANT LOAD OF 30. |
| | |
| | 2K) 4TH REQUEST. THIS COMMENT IS A RESULT OF THE |
| | BUILDING OFFICIAL INTERPRETATION ON 06/2020. IN |
| | BATHROOMS, RESTROOMS & SERVICE SINK AREAS EPOXY PAINT |
| | IS NO LONGER CONSIDERED A SMOOTH HARD, NON-ABSORBENT |
| | SURFACE. |
| | EXISTING RESTROOM ELEVATIONS DO NOT PROVIDE WALL |
| | FINISHES. 2017 FBC-B 1210.2.2. WALLS & PARTITIONS. THIS |
| | COMMENT IS A RESULT OF THE BUILDING OFFICIAL |
| | INTERPRETATION. IN RESTROOMS EPOXY PAINT IS NO LONGER |
| | CONSIDERED A SMOOTH HARD, NON-ABSORBENT SURFACE. WALLS |
| | & PARTITIONS WITHIN 2 FEET OF SERVICE SINKS, URINALS, |
| | AND WATER CLOSETS SHALL HAVE A SMOOTH, HARD, |
| | NON-ABSORBENT SURFACE TO A HEIGHT OF NOT LESS THAN 4 |
| | FEET ABOVE THE FLOOR, EXCEPT FOR STRUCTURAL ELEMENTS, |
| | THE MATERIAL USED IN SUCH WALLS SHALL BE OF A TYPE THAT |
| | IS NOT ADVERSELY AFFECTED BY MOISTURE. |
| | |
| | 2K)(1) FBC-B2509.1. WET AREAS. SHOWERS AND PUBLIC |
| | TOILET WALLS SHALL COMPLY WITH 1210.2. |
| | |
| | 2K)(2) FBC-B1210.2. FINISH MATERIALS. WALLS, FLOORS AND |
| | PARTITIONS IN TOILET AND BATHROOMS SHALL COMPLY WITH |
| | SECTIONS 1210.1 THROUGH 1210.4. |
| | |
| | 3) COMPLIED. |
| | |
| | 4) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS |
| | REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT |
| | REVIEW CYCLE. |
| | |
| | PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID |
| | 19 |
| | IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS |
| | 561-718-9724. |
| | |
| | JAMES A. WITMER BN, PX, SFP, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT |
| | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6717 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |