| Plan Review Notes For Permit 20090622 |
| Permit Number |
20090622 |
|
| Review Stop |
P |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2021-05-26 06:34:20 | 1) SHT. A-2 - LABEL THE EQUIPMENT ON THE EQUIPMENT | | | SCHEDULE. THE PLAN SHOWS LETTERS FOR EACH PIECE OF | | | EQUIPMENT. WPB AMEND. TO FBC SEC. 107.2.1. | | | 2) SHT. A-1 - THE CODE COMPLIANCE TABLE LISTS THIS | | | OCCUPANCY AS B BUT THE CODE COMPLIANCE TABLE ON SHT. | | | LS-1 LISTS THE OCCUPANCY AS AN A-2. CLARIFY. | | | 3) SINCE THE OCCCUPANT LOAD IS NOW OVER 15, TWO TOILET | | | ROOMS WILL BE REQUIRED PER FBC-PLUMBING SEC.403.2. | | | 4) SHT. P-1 - THE TOILET ROOM FLOOR PLAN SHOWS THE | | | CENTER OF THE LAVATORY AT 1 FOOT FROM THE SIDE WALL. A | | | MINIMUM OF 15 INCHES IS REQUIRED PER FBC-PLUMBING | | | SEC.405.3.1. | | | 5) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE | | | TANKLESS WATER HEATER. WPB AMEND. TO FBC SEC. 107.2.1. | | | 6) SIZE ALL SECTIONS OF THE WATER RISER. OVERHEAD | | | SECTIONS ARE MISSING SIZES. | | | 7) THE MOP SINK IS NOT VENTED. FBC-PLUMBING SEC.901.2. | | | 8) THHE PREP SINK SHALL BEE INDIRECTLY WASTED. | | | FBC-PLUMBING SEC.802.1.8. | | | 9) SUBMIT SIZING CALCULATIONS FOR THE GREASE | | | INTERCEPTOR PER FBC-PLUMBING SEC.1003.2. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | |
|