Plan Review Notes
Plan Review Notes For Permit 20090622
Permit Number 20090622
Review Stop P
Sequence Number 3
Notes
Date Text
2021-05-26 06:34:201) SHT. A-2 - LABEL THE EQUIPMENT ON THE EQUIPMENT
 SCHEDULE. THE PLAN SHOWS LETTERS FOR EACH PIECE OF
 EQUIPMENT. WPB AMEND. TO FBC SEC. 107.2.1.
 2) SHT. A-1 - THE CODE COMPLIANCE TABLE LISTS THIS
 OCCUPANCY AS B BUT THE CODE COMPLIANCE TABLE ON SHT.
 LS-1 LISTS THE OCCUPANCY AS AN A-2. CLARIFY.
 3) SINCE THE OCCCUPANT LOAD IS NOW OVER 15, TWO TOILET
 ROOMS WILL BE REQUIRED PER FBC-PLUMBING SEC.403.2.
 4) SHT. P-1 - THE TOILET ROOM FLOOR PLAN SHOWS THE
 CENTER OF THE LAVATORY AT 1 FOOT FROM THE SIDE WALL. A
 MINIMUM OF 15 INCHES IS REQUIRED PER FBC-PLUMBING
 SEC.405.3.1.
 5) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 TANKLESS WATER HEATER. WPB AMEND. TO FBC SEC. 107.2.1.
 6) SIZE ALL SECTIONS OF THE WATER RISER. OVERHEAD
 SECTIONS ARE MISSING SIZES.
 7) THE MOP SINK IS NOT VENTED. FBC-PLUMBING SEC.901.2.
 8) THHE PREP SINK SHALL BEE INDIRECTLY WASTED.
 FBC-PLUMBING SEC.802.1.8.
 9) SUBMIT SIZING CALCULATIONS FOR THE GREASE
 INTERCEPTOR PER FBC-PLUMBING SEC.1003.2.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  