| 2021-05-10 08:59:55 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION |
| | SERVICES/ BUILDING DIVISION |
| | 2017 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 20090622 |
| | ADD: 428 CLEMATIS ST. |
| | CONT: FOREMOST GENERAL CONTRACTING INC. |
| | TEL: 954-953-7991 |
| | E-MAIL: [email protected] |
| | |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 3RD REVIEW |
| | DATE: MON. MAY 10TH/ / 2021 |
| | ACTION: DENIED |
| | |
| | 1) LIFE SAFETY PLAN LS1 & A2: |
| | 1A) 3RD REVIEW. THIS TENANT SPACE THE DESIGNER OF |
| | RECORD LABELS AS AN A2 OCCUPANCY FOR THE 3RD REVIEW. |
| | PLEASE REVIEW IN THE 2017 FBC-B SECTION 303.1.2 SMALL |
| | ASSEMBLY SPACES A ROOM WITH LESS THAN 750 SQ. FT. AND |
| | OCCUPANT LOAD OF 50 IS TO BE CLASSIFIED AS AN BUSINESS |
| | OCCUPANCY. UPDATE PLANS. |
| | |
| | 1B)NOTE ONLY FOR OCCUPANT LOAD DESIGN. THE OCCUPANT |
| | LOAD FACTOR TAKEN FOR THE BUSINESS OCCUPANCY IS TAKEN |
| | AT 100 GROSS AREA. FLOOR AREA, GROSS. THE FLOOR AREA |
| | WITHIN THE INSIDE PERIMETER OF THE EXTERIOR WALLS OF |
| | THE BUILDING UNDER CONSIDERATION, EXCLUSIVE OF VENT |
| | SHAFTS AND COURTS, WITHOUT DEDUCTION FOR CORRIDORS, |
| | STAIRWAYS, CLOSETS, THE THICKNESS OF INTERIOR WALLS, |
| | COLUMNS OR OTHER FEATURES. THE FLOOR AREA OF A |
| | BUILDING, OR PORTION THEREOF, NOT PROVIDED WITH |
| | SURROUNDING EXTERIOR WALLS SHALL BE THE USABLE AREA |
| | UNDER THE HORIZONTAL PROJECTION OF THE ROOF OR FLOOR |
| | ABOVE. |
| | |
| | 1C)(1) ? 1C)(4) COMPLIED. |
| | . |
| | |
| | 1C)(5) 2ND REQUEST. HAD COMPLIED. STANDING AND SEATING |
| | AREA 364 SQ. FT. LESS THAN 750 SQ. FT. CONSIDERED |
| | BUSINESS OCCUPANCY. 364/ 100=4 OCCUPANTS. |
| | PLEASE NOTE SHEET A2 SHOWS 5 INDOOR SEATS AND 8 |
| | SEASONAL SEATS. |
| | |
| | 1C)(6) COMPLIED. THE TOTAL OCCUPANT LOAD FOR EGRESS |
| | WOULD BE 10 PLUS , BUT FOR PLUMBING FIXTURE YOU COUNT |
| | THE EXTERIOR SEASONAL SEATING (8) THE OCCUPANT LOAD |
| | WOULD BE 18 OCCUPANTS. IN THE 2017 FBC-B TABLE 1006.2.1 |
| | SPACES WITH ONE EXIT ACCESS DOORWAY WITHOUT FIRE |
| | SPRINKLERS ALLOWS 100 FEET COMMON PATH OF TRAVEL WHEN |
| | THERE IS AN OCCUPANT LOAD OF 30 OR LESS. |
| | |
| | 1D) COMPLIED. PLEASE CORRECT WITHIN THE BLOCK LABELED |
| | OCCUPANT LOAD CALCULATION THE STATEMENT READS: NUMBER |
| | OF REQUIRED EXITS 2, NUMBER OF EXITS 2. |
| | |
| | 1E) COMPLIED. PLEASE REVIEW IN THE 2017 FBC-B TABLE |
| | 1006.2.1 SPACES WITH ONE EXIT OR EXIT ACCESS DOORWAY, |
| | THIS TABLE IS TO BE USED ONLY AT GRADE LEVEL!!!! FOR A |
| | BUSINESS OCCUPANCY, WITHOUT SPRINKLERS, 30 OR LESS |
| | OCCUPANTS THE COMMON PATH OF EGRESS TRAVEL IS 100 FT. |
| | PLEASE USE THIS LANGUAGE TO CORRECT COMMENT (1D) FOR |
| | CODE COMPLIANCE. |
| | |
| | 2) SHEET A2 THE FLOOR PLAN SHOWS SEATING AND COUNTER |
| | SALES AREA & CASHIER, BUT THE PLAN DOES NOT SHOW |
| | ACCESSIBLE ELEMENTS: |
| | 2A) COMPLIED. |
| | |
| | 2B) 3RD REQUEST. THE ENTRANCE ALSO NEEDS TO SHOW |
| | COMPLIANCE WITH: ACCESS. CODE 404.2.4 MANEUVERING |
| | CLEARANCES. DOORS. |
| | MINIMUM MANEUVERING CLEARANCES AT DOORS AND GATES SHALL |
| | COMPLY WITH 404.2.4. MANEUVERING CLEARANCES SHALL |
| | EXTEND THE FULL WIDTH OF THE DOORWAY AND THE REQUIRED |
| | LATCH SIDE FOR SIDE CLEARANCE 18 INCHES. FIGURE |
| | 404.2.4.1(A). |
| | |
| | 2C-2J) COMPLIED. |
| | 2K) EXISTING RESTROOM ELEVATIONS DO NOT PROVIDE WALL |
| | FINISHES. 2017 FBC-B 1210.2.2. WALLS & PARTITIONS. THIS |
| | COMMENT IS A RESULT OF THE BUILDING OFFICIAL |
| | INTERPRETATION. IN RESTROOMS EPOXY PAINT IS NO LONGER |
| | CONSIDERED A SMOOTH HARD, NON-ABSORBENT SURFACE. WALLS |
| | & PARTITIONS WITHIN 2 FEET OF SERVICE SINKS, URINALS, |
| | AND WATER CLOSETS SHALL HAVE A SMOOTH, HARD, |
| | NON-ABSORBENT SURFACE TO A HEIGHT OF NOT LESS THAN 4 |
| | FEET ABOVE THE FLOOR, EXCEPT FOR STRUCTURAL ELEMENTS, |
| | THE MATERIAL USED IN SUCH WALLS SHALL BE OF A TYPE THAT |
| | IS NOT ADVERSELY AFFECTED BY MOISTURE. |
| | |
| | 2K) 2017 FBC-B 1210.2.2. WALLS & PARTITIONS. THIS |
| | COMMENT IS A RESULT OF THE BUILDING OFFICIAL |
| | INTERPRETATION ON 06/2020. IN BATHROOMS, RESTROOMS & |
| | SERVICE SINK AREAS EPOXY PAINT IS NO LONGER CONSIDERED |
| | A SMOOTH HARD, NON-ABSORBENT SURFACE. |
| | |
| | 2K)(1) FBC-B2509.1. WET AREAS. SHOWERS AND PUBLIC |
| | TOILET WALLS SHALL COMPLY WITH 1210.2. |
| | |
| | 2K)(2) FBC-B1210.2. FINISH MATERIALS. WALLS, FLOORS AND |
| | PARTITIONS IN TOILET AND BATHROOMS SHALL COMPLY WITH |
| | SECTIONS 1210.1 THROUGH 1210.4. |
| | |
| | 2L-2N) COMPLIED. |
| | |
| | |
| | 3) COMPLIED. |
| | |
| | 4) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS |
| | REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT |
| | REVIEW CYCLE. |
| | |
| | PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID |
| | 19 |
| | IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS |
| | 561-718-9724. |
| | |
| | JAMES A. WITMER BN, PX, SFP, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT |
| | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6717 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |