Plan Review Notes
Plan Review Notes For Permit 20090622
Permit Number 20090622
Review Stop B
Sequence Number 3
Notes
Date Text
2021-05-10 08:59:55WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20090622
 ADD: 428 CLEMATIS ST.
 CONT: FOREMOST GENERAL CONTRACTING INC.
 TEL: 954-953-7991
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE: MON. MAY 10TH/ / 2021
 ACTION: DENIED
  
 1) LIFE SAFETY PLAN LS1 & A2:
 1A) 3RD REVIEW. THIS TENANT SPACE THE DESIGNER OF
 RECORD LABELS AS AN A2 OCCUPANCY FOR THE 3RD REVIEW.
 PLEASE REVIEW IN THE 2017 FBC-B SECTION 303.1.2 SMALL
 ASSEMBLY SPACES A ROOM WITH LESS THAN 750 SQ. FT. AND
 OCCUPANT LOAD OF 50 IS TO BE CLASSIFIED AS AN BUSINESS
 OCCUPANCY. UPDATE PLANS.
  
 1B)NOTE ONLY FOR OCCUPANT LOAD DESIGN. THE OCCUPANT
 LOAD FACTOR TAKEN FOR THE BUSINESS OCCUPANCY IS TAKEN
 AT 100 GROSS AREA. FLOOR AREA, GROSS. THE FLOOR AREA
 WITHIN THE INSIDE PERIMETER OF THE EXTERIOR WALLS OF
 THE BUILDING UNDER CONSIDERATION, EXCLUSIVE OF VENT
 SHAFTS AND COURTS, WITHOUT DEDUCTION FOR CORRIDORS,
 STAIRWAYS, CLOSETS, THE THICKNESS OF INTERIOR WALLS,
 COLUMNS OR OTHER FEATURES. THE FLOOR AREA OF A
 BUILDING, OR PORTION THEREOF, NOT PROVIDED WITH
 SURROUNDING EXTERIOR WALLS SHALL BE THE USABLE AREA
 UNDER THE HORIZONTAL PROJECTION OF THE ROOF OR FLOOR
 ABOVE.
  
 1C)(1) ? 1C)(4) COMPLIED.
 .
  
 1C)(5) 2ND REQUEST. HAD COMPLIED. STANDING AND SEATING
 AREA 364 SQ. FT. LESS THAN 750 SQ. FT. CONSIDERED
 BUSINESS OCCUPANCY. 364/ 100=4 OCCUPANTS.
 PLEASE NOTE SHEET A2 SHOWS 5 INDOOR SEATS AND 8
 SEASONAL SEATS.
  
 1C)(6) COMPLIED. THE TOTAL OCCUPANT LOAD FOR EGRESS
 WOULD BE 10 PLUS , BUT FOR PLUMBING FIXTURE YOU COUNT
 THE EXTERIOR SEASONAL SEATING (8) THE OCCUPANT LOAD
 WOULD BE 18 OCCUPANTS. IN THE 2017 FBC-B TABLE 1006.2.1
 SPACES WITH ONE EXIT ACCESS DOORWAY WITHOUT FIRE
 SPRINKLERS ALLOWS 100 FEET COMMON PATH OF TRAVEL WHEN
 THERE IS AN OCCUPANT LOAD OF 30 OR LESS.
  
 1D) COMPLIED. PLEASE CORRECT WITHIN THE BLOCK LABELED
 OCCUPANT LOAD CALCULATION THE STATEMENT READS: NUMBER
 OF REQUIRED EXITS 2, NUMBER OF EXITS 2.
  
 1E) COMPLIED. PLEASE REVIEW IN THE 2017 FBC-B TABLE
 1006.2.1 SPACES WITH ONE EXIT OR EXIT ACCESS DOORWAY,
 THIS TABLE IS TO BE USED ONLY AT GRADE LEVEL!!!! FOR A
 BUSINESS OCCUPANCY, WITHOUT SPRINKLERS, 30 OR LESS
 OCCUPANTS THE COMMON PATH OF EGRESS TRAVEL IS 100 FT.
 PLEASE USE THIS LANGUAGE TO CORRECT COMMENT (1D) FOR
 CODE COMPLIANCE.
  
 2) SHEET A2 THE FLOOR PLAN SHOWS SEATING AND COUNTER
 SALES AREA & CASHIER, BUT THE PLAN DOES NOT SHOW
 ACCESSIBLE ELEMENTS:
 2A) COMPLIED.
  
 2B) 3RD REQUEST. THE ENTRANCE ALSO NEEDS TO SHOW
 COMPLIANCE WITH: ACCESS. CODE 404.2.4 MANEUVERING
 CLEARANCES. DOORS.
 MINIMUM MANEUVERING CLEARANCES AT DOORS AND GATES SHALL
 COMPLY WITH 404.2.4. MANEUVERING CLEARANCES SHALL
 EXTEND THE FULL WIDTH OF THE DOORWAY AND THE REQUIRED
 LATCH SIDE FOR SIDE CLEARANCE 18 INCHES. FIGURE
 404.2.4.1(A).
  
 2C-2J) COMPLIED.
 2K) EXISTING RESTROOM ELEVATIONS DO NOT PROVIDE WALL
 FINISHES. 2017 FBC-B 1210.2.2. WALLS & PARTITIONS. THIS
 COMMENT IS A RESULT OF THE BUILDING OFFICIAL
 INTERPRETATION. IN RESTROOMS EPOXY PAINT IS NO LONGER
 CONSIDERED A SMOOTH HARD, NON-ABSORBENT SURFACE. WALLS
 & PARTITIONS WITHIN 2 FEET OF SERVICE SINKS, URINALS,
 AND WATER CLOSETS SHALL HAVE A SMOOTH, HARD,
 NON-ABSORBENT SURFACE TO A HEIGHT OF NOT LESS THAN 4
 FEET ABOVE THE FLOOR, EXCEPT FOR STRUCTURAL ELEMENTS,
 THE MATERIAL USED IN SUCH WALLS SHALL BE OF A TYPE THAT
 IS NOT ADVERSELY AFFECTED BY MOISTURE.
  
 2K) 2017 FBC-B 1210.2.2. WALLS & PARTITIONS. THIS
 COMMENT IS A RESULT OF THE BUILDING OFFICIAL
 INTERPRETATION ON 06/2020. IN BATHROOMS, RESTROOMS &
 SERVICE SINK AREAS EPOXY PAINT IS NO LONGER CONSIDERED
 A SMOOTH HARD, NON-ABSORBENT SURFACE.
  
 2K)(1) FBC-B2509.1. WET AREAS. SHOWERS AND PUBLIC
 TOILET WALLS SHALL COMPLY WITH 1210.2.
  
 2K)(2) FBC-B1210.2. FINISH MATERIALS. WALLS, FLOORS AND
 PARTITIONS IN TOILET AND BATHROOMS SHALL COMPLY WITH
 SECTIONS 1210.1 THROUGH 1210.4.
  
 2L-2N) COMPLIED.
  
  
 3) COMPLIED.
  
 4) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  