Plan Review Notes
Plan Review Notes For Permit 20090622
Permit Number 20090622
Review Stop P
Sequence Number 2
Notes
Date Text
2021-03-25 13:32:4603/25/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
  
  
 1. PLEASE PROVIDE DETAILS FOR THE ACCESSIBILITY
 RESTROOM AS FOLLOW;
 A. THE PLANS SHOW NEW WALLS FOR THE TOILET ROOM. SINCE
 NEW WALLS WILL BE CONSTRUCTED THE GRAB BARS WILL HAVE
 TO MEET THE REQUIREMENTS FOR NEW CONSTRUCTION. PLEASE
 SHOW THE HEIGHT OF THE GRAB BARS THAT SHALL BE LOCATED
 33-36 INCHES ABOVE THE FINISH FLOOR MEASURED TO THE TOP
 OF THE GRIPPING SURFACE PER THE 2020 FBC-ACCESSIBILITY
 SEC. 609.4.
  
 B. PLEASE GIVE DIMENSIONS FOR FIXTURE CLEARANCES FOR
 LAV AND TOILET PER THE 2020 FBC ACC SEC. 606.2. 2 CLEAR
 FLOOR SPACE. THE CLEAR FLOOR SPACE SHALL BE 60? INCHES
 MINIMUM MEASURED PERPENDICULAR FROM THE SIDEWALL AND
 56? INCHES MINIMUM MEASURED PERPENDICULAR FROM THE REAR
 WALL PER THE 2017 FBC ACC. SEC. 604.3.1.
  
 C. MIRRORS SHALL BE LOCATED WITH THE BOTTOM EDGE OF THE
 REFLECTING SURFACE 40 INCHES? MAXIMUM ABOVE THE FINISH
 FLOOR 2020 FBC-ACCESS. SEC.603.3.
  
 D. PLEASE SHOW THE LOCATION OF THE GRAB BARS THAT SHALL
 COMPLY WITH 2020 FBC-ACCESS. SECS.604.5.1, 604.5.2.
  
 E. PLEASE PROVIDE THE KNEE AND TOE CLEARANCES FOR THE
 LAVATORY PER THE 2020 FBC ACC SEC. 306.1 TOE CLEARANCE.
  
 F. PROVIDE LAVS HEIGHT OF 34? INCHES MAXIMUM PER THE
 2020 FBC ACC SEC. 606.3.
  
 G. THE TOILET PAPER DISPENSERS SHALL BE 7? INCHES
 MINIMUM AND 9? INCHES MAXIMUM IN FRONT OF THE WATER
 CLOSET MEASURED TO THE CENTERLINE OF DISPENSER PER THE
 2017 FBC ACC SEC. 604.7.
  
 H. SHOW THE FLUSH CONTROLS FOR THE WATER CLOSET. THE
 FLUSH CONTROLS SHALL COMPLY WITH FBC-ACCESS. SEC.
 604.6. HANDICAP CAP WATER CLOSET FLUSH CONTROL SHALL BE
 HAND OPERATED OR AUTOMATIC AND SHALL BE 36? INCHES
 MAXIMUM ABOVE THE FINISH FLOOR AND ON THE OPEN SIDE PER
 THE 2017 FBC ACC SEC. 604.9.5.
  
 I. THE FAUCET SHALL COMPLY WITH FBC-ACCESS. SEC.606.4,
 309.
  
 K. LAVATORY WATER SUPPLY AND DRAINPIPES UNDER SIDE
 SHALL BE INSULATED OR OTHERWISE CONFIGURED TO PROTECT
 AGAINST CONTACT PER THE 2017 FBC ACC SEC. 606.5.
  
 L. THE TOILET SEATS NEED TO BE 17? INCHES TO 19? INCHES
 MAXIMUM MEASURED TO THE TOP OF THE SEAT PER THE 2017
 FBC ACC SEC. 604.4 SEATS.
  
 2. THE FLOOR DRAIN IN THE TOILET ROOM CANNOT DISCHARGE
 TO THE GREASE INTERCEPTOR PER THE 2020 FBC-PLUMBING
 SEC. 1003.2.
  
 3. SUBMIT SPECIFICATIONS/DETAILS ON THE TYPE OF GREASE
 INTERCEPTOR TO BE INSTALLED AND MANUFACTURER'S
 SPECIFICATIONS AND SIZING CALCULATIONS FOR THE GREASE
 INTERCEPTOR PER THE 2020 FBC-PLUMBING SEC. 1003.2.
  
 4. SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE YOGURT
 MACHINES PER THE WPB AMEND. TO FBC SEC. 107.2.1.
  
 5. THE TRAP SEAL IN THE FLOOR DRAINS SHALL BE PROTECTED
 PER THE 2020 FBC-PLUMBING SEC.1002.4.1.
  
 6. THE GREASE INTERCEPTOR SHALL HAVE A SAMPLING PORT ON
 THE DISCHARGE SIDE OF THE INTERCEPTOR. A 4-INCH TWO-WAY
 CLEANOUT WILL SUFFICE, SHOW THIS ON THE RISER DIAGRAM
 PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 7. PLEASE PROVIDE UNDER CODES, THE YEAR, PLUMBING AND
 ACCESSIBILITY REFERENCED USED PER THE WPB AMENDMENTS TO
 THE FBC SEC. 101.4 REFERENCED CODES.
  
 8. THE SERVICE SINK (MOP SINK) SURROUNDING THE WALL
 SHALL BE NON-ABSORBENT SURFACE IN ACCORDANCE WITH THE
 2020 FBC BUILDING SEC. 1210.2.2 AND 2017 FBC SEC. P
 310.3. PLEASE MAKE A NOTE ON THIS SHEET.
  
 9. ON SHEET A2, THERE IS A DETAIL WITH DIFFERENT
 APPLIANCES AND NO REFERENCE OR NUMBERS TO THEM. IF ANY
 OF THESE ARE A COFFEE MAKER/ICE MAKER REQUIRE AN INLINE
 VACUUM BREAKER THAT COMPLIES WITH THE ASSE 1024
 NON-CARBONATED.
  
 10. PLEASE PROVIDE HOT WATER AND COLD THAT ARE NOT SHOW
 AND ITS SOURCE, SIZING, DISTRIBUTION, WATER HAMMER,
 WITHIN ACCORDANCE 2017 FBC P SEC. 604, PLEASE PROVIDE A
 LAYOUT AND RISER WPB AMENDMENTS TO THE FBC 107.5.1.3
 (13) PLUMBING RISER DIAGRAM REQUIRED.
  
 11. IN THE KITCHEN AREA THERE IS A THREE-COMPARTMENT
 SINK PLEASE PROVIDE DETAIL ON THE DRAINS TO AN INDIRECT
 WASTE INDEPENDENTLY FORM EACH OTHER PER THE 2017 FBC
 SEC. P 802.1.1.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  