| Plan Review Notes For Permit 20090622 |
| Permit Number |
20090622 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2021-03-03 14:58:33 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | | 1) SHEET LS 1 - THE REVISED OCCUPANCY LOAD CALCULATION | | | FOR THE STANDING/SEATING AREA IS INCORRECT PER THE FFPC | | | NFPA 101. | | | | | | PER TABLE 7.3.1.2 THE OCCUPANCY LOAD FACTOR IS 15. | | | 364/15= 24.2666 ROUNDED UP TO 25; TOTAL 30. | | | | | | PLEASE REVIEW AND CORRECT. | | | | | | | | | 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|