Plan Review Notes
Plan Review Notes For Permit 20090622
Permit Number 20090622
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2021-03-03 14:58:33THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEET LS 1 - THE REVISED OCCUPANCY LOAD CALCULATION
 FOR THE STANDING/SEATING AREA IS INCORRECT PER THE FFPC
 NFPA 101.
  
 PER TABLE 7.3.1.2 THE OCCUPANCY LOAD FACTOR IS 15.
 364/15= 24.2666 ROUNDED UP TO 25; TOTAL 30.
  
 PLEASE REVIEW AND CORRECT.
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  