2021-03-04 09:55:52WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20090622
 ADD: 428 CLEMATIS ST.
 CONT: FOREMOST GENERAL CONTRACTING INC.
 TEL: 954-953-7991
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: THURS. MARCH 04TH/ / 2021
 ACTION: DENIED
  
 1) LIFE SAFETY PLAN LS1 & A2:
 1A)2ND REVIEW. THIS TENANT SPACE THE DESIGNER OF RECORD
 LABELS AS AN A2 OCCUPANCY FOR THE 2ND REVIEW. PLEASE
 REVIEW IN THE 2017 FBC-B SECTION 303.1.2 SMALL ASSEMBLY
 SPACES A ROOM WITH LESS THAN 750 SQ. FT. AND OCCUPANT
 LOAD OF 50 IS TO BE CLASSIFIED AS AN BUSINESS
 OCCUPANCY. UPDATE PLANS.
  
 1B)NOTE ONLY FOR OCCUPANT LOAD DESIGN. THE OCCUPANT
 LOAD FACTOR TAKEN FOR THE BUSINESS OCCUPANCY IS TAKEN
 AT 100 GROSS AREA. FLOOR AREA, GROSS. THE FLOOR AREA
 WITHIN THE INSIDE PERIMETER OF THE EXTERIOR WALLS OF
 THE BUILDING UNDER CONSIDERATION, EXCLUSIVE OF VENT
 SHAFTS AND COURTS, WITHOUT DEDUCTION FOR CORRIDORS,
 STAIRWAYS, CLOSETS, THE THICKNESS OF INTERIOR WALLS,
 COLUMNS OR OTHER FEATURES. THE FLOOR AREA OF A
 BUILDING, OR PORTION THEREOF, NOT PROVIDED WITH
 SURROUNDING EXTERIOR WALLS SHALL BE THE USABLE AREA
 UNDER THE HORIZONTAL PROJECTION OF THE ROOF OR FLOOR
 ABOVE.
  
 1C)(1) COMPLIED. THE OFFICE AREA WAS TAKEN 15 GROSS.
 PLEASE NOTE TABLE 1004.1.2 THE OCCUPANT LOAD FACTOR IS
 TAKEN AT 100 SQ. FT./ OCCUPANT. 48 SQ. FT./ 100= 1
 OCCUPANT.
  
 1C)(2) 2ND REQUEST. THE KITCHEN AREA IS INCREASED.
 KITCHEN AREA CALCULATIONS IS TAKEN AT 200 GROSS (2017
 FBC-B TABLE 1004.1.2) MAY VARY IN THE FIRE CODES,440
 SQ. FT. /200= 3 OCCUPANTS NOT 2, PLEASE UPDATE THE
 FLOOR PLAN.
  
 1C)(3) COMPLIED. RESTROOM 61 SQ. FT./ 100= 1 OCCUPANT.
  
 1C)(4)COMPLIED. STORAGE 6X10= 60 SQ. FT./ 300= 1
 OCCUPANT.
  
 1C)(5) COMPLIED. STANDING AND SEATING AREA 364 SQ. FT.
 LESS THAN 750 SQ. FT. CONSIDERED BUSINESS OCCUPANCY.
 364/ 100=4 OCCUPANTS.
 PLEASE NOTE SHEET A2 SHOWS 5 INDOOR SEATS AND 8
 SEASONAL SEATS.
  
 1C)(6) COMPLIED. THE TOTAL OCCUPANT LOAD FOR EGRESS
 WOULD BE 10 PLUS , BUT FOR PLUMBING FIXTURE YOU COUNT
 THE EXTERIOR SEASONAL SEATING (8) THE OCCUPANT LOAD
 WOULD BE 18 OCCUPANTS. IN THE 2017 FBC-B TABLE 1006.2.1
 SPACES WITH ONE EXIT ACCESS DOORWAY WITHOUT FIRE
 SPRINKLERS ALLOWS 100 FEET COMMON PATH OF TRAVEL WHEN
 THERE IS AN OCCUPANT LOAD OF 30 OR LESS.
  
 1D) COMPLIED. PLEASE CORRECT WITHIN THE BLOCK LABELED
 OCCUPANT LOAD CALCULATION THE STATEMENT READS: NUMBER
 OF REQUIRED EXITS 2, NUMBER OF EXITS 2.
  
 1E) COMPLIED. PLEASE REVIEW IN THE 2017 FBC-B TABLE
 1006.2.1 SPACES WITH ONE EXIT OR EXIT ACCESS DOORWAY,
 THIS TABLE IS TO BE USED ONLY AT GRADE LEVEL!!!! FOR A
 BUSINESS OCCUPANCY, WITHOUT SPRINKLERS, 30 OR LESS
 OCCUPANTS THE COMMON PATH OF EGRESS TRAVEL IS 100 FT.
 PLEASE USE THIS LANGUAGE TO CORRECT COMMENT (1D) FOR
 CODE COMPLIANCE.
  
 2) SHEET A2 THE FLOOR PLAN SHOWS SEATING AND COUNTER
 SALES AREA & CASHIER, BUT THE PLAN DOES NOT SHOW
 ACCESSIBLE ELEMENTS:
 2A) COMPLIED. THE ENTRANCE NEEDS TO SHOW COMPLIANCE
 WITH: ACCESS. CODE 404.2.5. THRESHOLDS. THRESHOLDS, IF
 PROVIDED AT DOORWAYS, SHALL BE ? INCH HIGH MAXIMUM.
 RAISED THRESHOLDS AND CHANGES IN LEVEL AT DOORWAYS
 SHALL COMPLY WITH 302 & 303.
  
 2B) 2ND REQUEST. THE ENTRANCE ALSO NEEDS TO SHOW
 COMPLIANCE WITH: ACCESS. CODE 404.2.4 MANEUVERING
 CLEARANCES. DOORS.
 MINIMUM MANEUVERING CLEARANCES AT DOORS AND GATES SHALL
 COMPLY WITH 404.2.4. MANEUVERING CLEARANCES SHALL
 EXTEND THE FULL WIDTH OF THE DOORWAY AND THE REQUIRED
 LATCH SIDE FOR SIDE CLEARANCE. FIGURE 404.2.4.1(A).
  
 2C) COMPLIED. SHEET A2 NOR THE LIFE SAFETY SHEET SHOW
 COMPLIANCE WITH THE 2017 FBC-ACCESSIBILITY CODE;
 1) 226.1 WHERE DINING SURFACES ARE PROVIDED FOR THE
 CONSUMPTION OF FOOD OR DRINK, AT LEAST 5 PERCENT OF THE
 SEATING SPACES AND STANDING SPACES AT THE DINING
 SURFACES SHALL COMPLY WITH 902.
  
 2D) COMPLIED. 226.2 DISPERSION. DINING SURFACES AND
 WORK SURFACES REQUIRED TO COMPLY WITH 902 SHALL BE
 DISPERSED THROUGHOUT THE SPACE OR FACILITY CONTAINING
 DINING SURFACES AND WORK SURFACES.
  
 2E) COMPLIED. 206.2.5 206.2.5 RESTAURANTS AND
 CAFETERIAS. IN RESTAURANTS AND CAFETERIAS, AN
 ACCESSIBLE ROUTE SHALL BE PROVIDED TO ALL DINING AREAS,
 INCLUDING RAISED OR SUNKEN DINING AREAS, AND OUTDOOR
 DINING AREAS.
  
 2F) COMPLIED. 902.1. DINING SURFACES AND WORK SURFACES
 SHALL COMPLY WITH 902.2 AND 902.3. ADVISORY 902.1
 GENERAL. DINING SURFACES INCLUDE, BUT ARE NOT LIMITED
 TO, BARS, TABLES, LUNCH COUNTERS, AND BOOTHS. EXAMPLES
 OF WORK SURFACES INCLUDE WRITING SURFACES, STUDY
 CARRELS, STUDENT LABORATORY STATIONS, BABY CHANGING AND
 OTHER TABLES OR FIXTURES FOR PERSONAL GROOMING, COUPON
 COUNTERS, AND WHERE COVERED BY THE ADA SCOPING
 PROVISIONS, EMPLOYEE WORK STATIONS.
  
 2F)(1) COMPLIED. 902.2 CLEAR FLOOR OR GROUND SPACE. A
 CLEAR FLOOR SPACE COMPLYING WITH 305 POSITIONED FOR A
 FORWARD APPROACH SHALL BE PROVIDED. KNEE AND TOE
 CLEARANCE COMPLYING WITH 306 SHALL BE PROVIDED.
  
 2F)(2) COMPLIED.902.3 HEIGHT. THE TOPS OF DINING
 SURFACES AND WORK SURFACES SHALL BE 28 INCHES MINIMUM
 AND 34 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 2G) 2ND REQUEST. THE TOPS OF WORK SURFACES SHALL BE 28
 INCHES (710 MM) MINIMUM AND 34 INCHES (865 MM) MAXIMUM
 ABOVE THE FINISH FLOOR OR GROUND.
  
 2H) COMPLIED. SHOW COMPLIANCE WITH THE ACCESS. CODE
 305.5 POSITION. UNLESS OTHERWISE SPECIFIED, CLEAR FLOOR
 OR GROUND SPACE SHALL BE POSITIONED FOR EITHER A
 FORWARD OR PARALLEL APPROACH TO AN ELEMENT.
  
 2I) 2ND REQUEST. 904.4 SALES AND SERVICE COUNTERS.
 SALES COUNTERS AND SERVICE COUNTERS SHALL COMPLY WITH
 904.4.1 OR 904.4.2. THE ACCESSIBLE PORTION OF THE
 COUNTERTOP SHALL EXTEND THE SAME DEPTH AS THE SALES OR
 SERVICE COUNTERTOP.
  
 2J) 2ND REQUEST. (1) 2017 FBC-ACCESSIBILITY CODE. 211.2
 MINIMUM NUMBER. NO FEWER THAN TWO DRINKING FOUNTAINS
 SHALL BE PROVIDED. ONE DRINKING FOUNTAIN SHALL COMPLY
 WITH 602.1 THROUGH 602.6 AND ONE DRINKING FOUNTAIN
 SHALL COMPLY WITH 602.7.
  
 2J)(2) 2ND REQUEST. PROTRUDING OBJECTS 307.2 PROTRUSION
 LIMITS 307.2. OBJECTS WITH LEADING EDGES MORE THAN 27
 INCHES AND NOT MORE THAN 80 INCHES ABOVE THE FLOOR
 SHALL NOT PROTRUDE MORE THAN 4 INCHES HORIZONTALLY INTO
 THE CIRCULATION PATH.
  
 2J)(3) 2ND REQUEST. 602.2 CLEAR FLOOR SPACE. A CLEAR
 FLOOR SPACE COMPLYING WITH 305, POSITIONED FOR A
 FORWARD APPROACH, AND KNEE AND TOE CLEARANCE COMPLYING
 WITH 306 SHALL BE PROVIDED.
  
 2K) EXISTING RESTROOM ELEVATIONS DO NOT PROVIDE WALL
 FINISHES. 2017 FBC-B 1210.2.2. WALLS & PARTITIONS. THIS
 COMMENT IS A RESULT OF THE BUILDING OFFICIAL
 INTERPRETATION. IN RESTROOMS EPOXY PAINT IS NO LONGER
 CONSIDERED A SMOOTH HARD, NON-ABSORBENT SURFACE. WALLS
 & PARTITIONS WITHIN 2 FEET OF SERVICE SINKS, URINALS,
 AND WATER CLOSETS SHALL HAVE A SMOOTH, HARD,
 NON-ABSORBENT SURFACE TO A HEIGHT OF NOT LESS THAN 4
 FEET ABOVE THE FLOOR, EXCEPT FOR STRUCTURAL ELEMENTS,
 THE MATERIAL USED IN SUCH WALLS SHALL BE OF A TYPE THAT
 IS NOT ADVERSELY AFFECTED BY MOISTURE.
  
 2K)(1) FBC-B2509.1. WET AREAS. SHOWERS AND PUBLIC
 TOILET WALLS SHALL COMPLY WITH 1210.2.
  
 2K)(2) FBC-B1210.2. FINISH MATERIALS. WALLS, FLOORS AND
 PARTITIONS IN TOILET AND BATHROOMS SHALL COMPLY WITH
 SECTIONS 1210.1 THROUGH 1210.4.
  
 2L-2M) COMPLIED.
  
 2N) 2ND REQUEST. 603.3 MIRRORS. 2017 FBC-ACCESSIBILITY
 CODE. MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS
 SHALL BE INSTALLED WITH THE BOTTOM EDGE OF THE
 REFLECTING SURFACE 40 INCHES MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND.
  
 3) NEW COMMENT. THE LS-1 AND A-2 FLOOR PLAN SHOW A RAMP
 THE HEIGHT AND SLOPE OF THE RAMP ARE NOT GIVEN SHOW
 COMPLIANCE WITH THE 2017 FBC-B SECTIONS:
 3A) 1012.2 SLOPE.
  
 3B) 1012.5 MINIMUM DIMENSIONS. THE MINIMUM DIMENSIONS
 OF MEANS OF EGRESS RAMPS SHALL COMPLY WITH SECTIONS
 1012.5.1
 THROUGH 1012.5.3. 1012.5.1 WIDTH AND CAPACITY. THE
 MINIMUM WIDTH AND REQUIRED CAPACITY OF A MEANS OF
 EGRESS RAMP SHALL BE NOT LESS THAN THAT REQUIRED FOR
 CORRIDORS BY SECTION 1020.2. THE CLEAR WIDTH OF A RAMP
 BETWEEN HANDRAILS, IF PROVIDED, OR OTHER PERMISSIBLE
 PROJECTIONS SHALL BE 36 INCHES MINIMUM.
  
 3C) 1012.6 LANDINGS. RAMPS SHALL HAVE LANDINGS AT THE
 BOTTOM AND TOP OF EACH RAMP, POINTS OF TURNING,
 ENTRANCE, EXITS AT
 DOORS AND IN ACCORDANCE WITH THE FLORIDA BUILDING CODE,
 ACCESSIBILITY. LANDINGS SHALL COMPLY WITH SECTIONS
 1012.6.1
 THROUGH 1012.6.5.
  
 (152 MM) SHALL HAVE HANDRAILS ON BOTH SIDES. HANDRAILS
 SHALL COMPLY WITH SECTION 1014. 1012.9 GUARDS. GUARDS
 SHALL BE PROVIDED WHERE REQUIRED BY SECTION 1015 AND
 SHALL BE CONSTRUCTED IN ACCORDANCE WITH SECTION 1015.
  
 3D) 1012.10 EDGE PROTECTION. EDGE PROTECTION COMPLYING
 WITH SECTION 1012.10.1 OR 1012.10.2 SHALL BE PROVIDED
 ON EACH
 SIDE OF RAMP RUNS AND AT EACH SIDE OF RAMP LANDINGS.
  
 4) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  