| 2020-10-05 10:54:51 | 1) THE PLANS SHOW NEW WALLS FOR THE TOILET ROOM.SINCE |
| | NEW WALLS WILL BE CONSTRUCTED THE GRAB BARS WILL HAVE |
| | TO MEET THE REQUIREMENTS FORNEWCONSTRUCTION. |
| | 2) THE HEIGHT OF TE GRAB BARS SHALL BE LOCATED 33-36 |
| | INCHES ABOVE THE FINISH FLOOR MEASURED TO THE TOP OF |
| | THE GRIPPING SURFAE PER FBC-ACCESSIBILITY SEC. 609.4. |
| | 3) MIRRORS SHALL BE LOCATED WITH THE BOTTOM EDGE OF THE |
| | REFLECTING SURFACE 40 INCHES MAXIMUM ABOVE THE FINISH |
| | FLOOR. FBC-ACCESS. SEC.603.3. |
| | 4) THE LOCATION OF THE GRAB BARS SHALL COMPLY WITH |
| | FBC-ACCESS. SECS.604.5.1, 604.5.2. |
| | 5) THE LOCATION OF THE TOILET PAPER DISPNSER SHALL |
| | COMPLY WITH FBC-ACCESS. SEC. 604.7. |
| | 6) SHOW THE FLUSH CONTROLS FOR THE WATER CLOSET. THE |
| | FLUSH CONTROLS SHALL COMPLY WITH FBC-ACCESS. SEC. |
| | 604.6. |
| | 7) THE FAUCET SHALL COMPLY WITH FBC-ACCESS. SEC.606.4, |
| | 309. |
| | 8) THE FLOOR DRAIN IN THE TOILET ROOM CANNOT DISHARGE |
| | TO THE GREASE INTERCEPTOR.FBC-PLUMBING SEC. 1003.2. |
| | 9) SUBMIT MANUFACTURER'S SPECIFICATIONS AND SIZING |
| | CALCULATIONS FOR THE GREASE INTERCEPTOR. FBC-PLUMBING |
| | SEC. 1003.2. |
| | 10) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE YOGURT |
| | MACHINES.WPB AMEND. TO FBC SEC. 107.2.1. |
| | 11) THE TRAP SEAL IN THE FLOOR DRAINS SHALL BE |
| | PROTECTED PER FBC-PLUMBING SEC.1002.4.1. |
| | 12) THE GREASE INTERCEPTOR SHALLL HAVE A SAMPLING PORT |
| | ON THE DISCHARGE SIDE OF THE INTERCEPTOR. A 4-INCH |
| | TWO-WAY CLEANOUT WILL SUFFICE. SHOW THIS ON THE RISER |
| | DIAGRAM. |
| | |
| | |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | PLUMBING PLAN REVIEW |
| | 561-805-6692 |
| | [email protected] |
| | |