| Plan Review Notes For Permit 20090622 |
| Permit Number |
20090622 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2020-10-21 15:48:52 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | FLORIDA BUILDING CODE 2017 6TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | | NFPA 70 2014 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | 1) SIGN CURCUIT MISSING FROM LOADS | | | | | | SIGN AND OUTLINE LIGHTING. SIGN AND OUTLINE LIGHTING | | | OUTLETS SHALL BE CALCULATED AT A MINIMUM OF 1200 | | | VOLT-AMPERES FOR EACH REQUIRED BRANCH CIRCUIT SPECIFIED | | | IN 600.5(A | | | | | | 2) SHOW WINDOW OUTLETS MISSING. | | | | | | SHOW WINDOWS. SHOW WINDOWS SHALL BE CALCULATED IN | | | ACCORDANCE WITH EITHER OF THE FOLLOWING: (1) THE UNIT | | | LOAD PER OUTLET AS REQUIRED IN OTHER PROVISIONS OF THIS | | | SECTION (2) AT 200 VOLT-AMPERES PER 300 MM (1 FT) OF | | | SHOW WINDOW | | | | | | 3) RISER DIAGRAM REQUIRED TO SHOW SIZE OF MAIN 215.5 | | | | | | PROVIDE RISER DIAGRAM OF EXISTING SERVICE. NEC 215.5; | | | FBC 107.2.1 | | | | | | 4) AIC RATING OF MAIN AND PANEL BREAKERS PER 110.9, | | | 110,10 LABEL REQUIRED BY 110.24 | | | | | | PROVIDE CALCULATION FOR AVAILABLE SHORT CIRCUIT CURRENT | | | AT NEW PANEL TO CONFIRM AIC RATING IS ADEQUATE. NEC | | | 110.10 | | | | | | 5) LOADS LISTED AS DISPENSER IN THE KITCHEN AREA? GFCI | | | PROTECTION. | | | | | | 6) LIGHTING CONTROL PER FBC ENERGY CONDERVATION CODE | | | | | | PROVIDE LIGHTING CONTROL PER FBC ENERGY CODE. FBC CE | | | 405.2.2.2 | | | | | | |
|