| 2020-10-01 11:07:27 | 2ND REVIEW FBC-2017 FUEL GAS |
| | PERMIT- 20090600 |
| | 10/1/2020 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | COMMENTS FROM THE 1ST REVIEW LISTED BELOW HAVE NOT BEEN |
| | COMPLETED ADDRESSED. NOTES HAVE BEEN ADDED TO THESE |
| | REMAINING COMMENTS. |
| | |
| | 2) SHEET 1: PROVIDE A REVISED SURVEY DRAWING MARKED UP |
| | TO SHOW THE REQUIRED 10 FT. UG LP TANK CLEARANCE |
| | DISTANCES TO THE BUILDINGS AND ADJACENT PROPERTY LINES- |
| | TABLE 6.3.1.1 NFPA 58. PLEASE NOTE THAT IF THE TANK IS |
| | LOCATED WITHIN 10 FT. OF A PUBLIC VEHICULAR |
| | THOROUGHFARE OR PARKING LOCATION, THE SHELL FOR THE |
| | TANK SHALL BE 18 IN. BELOW GRADE OR VEHICULAR BARRIER |
| | PROTECTION WILL BE REQUIRED- SECTIONS 6.6.1.1 & 6.6.6.1 |
| | (A). THE SUBMITTED SITE PLAN SHALL ALSO BE REVISED TO |
| | SHOW COMPLIANCE. FOR CLARITY PLEASE NOTE OR SHOW THE |
| | DISTANCE OF THE LP TANK TO THE POOL PAVILION AND TO ANY |
| | PERMANENT CONSTRUCTION ONSITE SUCH AS SHADE STRUCTURES. |
| | |
| | 3) SHEET 1: THE UG LP TANK ANCHORING DETAIL WITH |
| | HYDROSTATIC LIFT CALCULATION SHALL BE SIGNED AND SEALED |
| | BY THE FL. LICENSED ENGINEER WHO PREPARED THE |
| | CALCULATIONS AND DRAWING- SECTION 6.6.1.6 NFPA 58, AND |
| | FLORIDA STATUTE 471.003. PLEASE NOTE THAT THERE IS |
| | MISSING INFORMATION IN THE DETAIL INCLUDING THE TYPE, |
| | SIZE AND NUMBER OF CABLES OR STRAPS; PROTECTION FOR THE |
| | TANKS FROM THE STRAPS OR TIES; THE TYPE, SIZE, AND |
| | NUMBER OF ANCHORS; AND THE DEPTH OF ANCHOR EMBEDMENT. |
| | MANUFACTURER'S SPECS FOR THE PRE-FAB SLAB SHALL ALSO BE |
| | SUBMITTED. PROTECTIVE SLEEVES FOR THE CABLES NOT SHOWN. |
| | |
| | 5) SHEET 1: SUBMIT MANUFACTURER'S SPECIFICATIONS FOR |
| | THE BBQ GRILLS AND THE FIRETABLES- SECTION 305.1 FBC |
| | FG. THE SPECS SHALL BE MARKED OR HIGHLIGHTED TO SHOW |
| | THE APPLIANCE'S LISTING, BTUH LOADS, AND REQUIRED GAS |
| | INPUT PRESSURES. THE REQUESTED SPECS WERE NOT |
| | SUBMITTED. SUBMIT CUT SHEETS SHOWING LISTINGS, BTUH |
| | LOADS, INPUT PRESSURES, AND INSTALLATION GUIDELINES. |
| | THE EQUIPMENT SHALL BE INSTALLED PER MANUFACTURER'S |
| | SPECIFICATIONS WITH REQUIRED CLEARANCES TO |
| | COMBUSTIBLES, OVERHEAD CONSTRUCTION, AND WITH PROPER |
| | VENTING. PLEASE SUBMIT ONLY THE RELATIVE DOCUMENTS FROM |
| | THE INSTALLATION MANUAL AND NOT THE ENTIRE MANUAL. |
| | |
| | 6) SHEET 1 & 2: NO ARCHITECTURAL PLANS HAVE BEEN |
| | SUBMITTED FOR THE PROJECT UNDER THIS PERMIT. |
| | ARCHITECTURAL PLANS SHALL BE SUBMITTED THAT IDENTIFY |
| | THE STRUCTURE AND INDICATE IF IT IS OPEN OR ENCLOSED, |
| | THE TYPE OF CONSTRUCTION- NON-COMBUSTIBLE OR |
| | COMBUSTIBLE, AND IF THE APPLIANCES ARE BEING INSTALLED |
| | UNDER A ROOF OR OVERHEAD CONSTRUCTION. COMPLETE |
| | DIMENSIONED DETAILS FOR CONSTRUCTION OF THE BARS, |
| | COUNTERS, OR TABLES THE APPLIANCES WILL BE INSTALLED IN |
| | SHALL BE PROVIDED INCLUDING FRONT AND SIDE ELEVATION |
| | VIEWS- SECTION 107.2.1 WPB. PLEASE NOTE THAT A COMPLETE |
| | REVIEW OF THE APPLIANCE INSTALLATIONS AND REQUIRED |
| | VENTING SYSTEMS CANNOT BE ACCOMPLISHED AT THIS TIME, |
| | AND THAT A COMPLETE REVIEW MAY INCLUDE ACCESSIBILITY |
| | COMPLIANCES IIN ACCORDANCE WITH THE FLORIDA |
| | ACCESSIBILITY CODE-2017. SHEET A-5.4 SHOWS A VERTICAL |
| | PROPANE TANK. CLARIFY IF THIS TANK IS EXISTING OR TO BE |
| | INCLUDED IN THIS GAS PERMIT. WHAT APPLIANCES OR |
| | EQUIPMENT IS BEING SUPPLIED BY THE TANK- NO |
| | INFORMATION, NOTES OR DETAILS HAVE BEEN PROVIDED. |
| | LOCATION OF NOTE #14 NOT SHOWN ON THE DRAWINGS. |
| | |
| | 7) SHEET 2, GAS ISOMETRIC DRAWING. SHEET 1 & 2: THE |
| | REVISED GAS RISER IS SHOWING HIGHER INDIVIDUAL BTUH |
| | LOADS FOR THE BBQ GRILLS AND FIRETABLES THAN THE LOADS |
| | SHOWN IN THE NOTES ON EACH SHEET: GRILLS- 120,000 BTUH |
| | EA., FIRETABLES- 100,000 EA. PLEASE CORRECT THE LOADS |
| | IN THE NOTES TO MATCH THE RISER. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |