| 2020-09-16 15:59:12 | 1ST REVIEW FBC-2017 FUEL GAS |
| | PERMIT- 20090600 |
| | 9/16/2020 |
| | |
| | CODES IN EFFECT: |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | I HAVE RESEARCHED THE LICENSURE OF AMAURY GONZALEZ, |
| | WHOSE NAME AND SIGNATURE APPEARS AS THE QUALIFIER AND |
| | DESIGNER OF RECORD FOR THE PROJECT PLANS, AND I WAS NOT |
| | ABLE TO VERIFY THAT THE LICENSE #14826 LISTED ON THE |
| | PLAN IS VALID FOR USE IN PALM BEACH COUNTY AND |
| | QUALIFIES HIM TO DESIGN THE PLANS FOR THE PROJECT. MR. |
| | GONZALEZ'S LICENSE IN PALM BEACH COUNTY- #17356 EXPIRED |
| | ON 10/31/2018. I COULD NOT FIND LICENSE #14826 ON THE |
| | PB CONTRACTOR LICENSE CERTIFICATION WEBSITE. THE |
| | LICENSING PORTAL AT THE DBPR IDENTIFIES MR. GONZALEZ AS |
| | A CONSTRUCTION FINANCIAL OFFICER. PLEASE NOTE THE |
| | PERMIT APPLICATION DOES NOT PROVIDE THE REQUIRED |
| | LICENSED CONTRACTOR INFORMATION WHICH IS "TO BE |
| | DETERMINED" AT A LATER DATE PRIOR TO PERMIT ISSUANCE. |
| | THE PLANS HAVE FAILED FIRST REVIEW AT THIS TIME FOR THE |
| | DEFICIENCIES LISTED BELOW. REVISED PLANS SHALL EITHER |
| | BEAR THE INSTALLING CONTRACTOR'S FL. OR PB COUNTY |
| | LICENSE, TITLE BLOCK AND SIGNATURE; OR SHALL BEAR THE |
| | ELECTRONIC SIGNATURE AND SEAL OF A FL. LICENSED |
| | ENGINEER- FL. STATUTES 471.003, 471.025 AND FLORIDA |
| | ADMINISTRATIVE CODE SECTION 61G15-23.005. |
| | |
| | 1) SHEET 1: SUBMIT MANUFACTURER'S SPECIFICATIONS FOR |
| | THE 250-GALLON UG LP TANK AND TRAFFIC DOME SHOWING THE |
| | TANK AND DOME HAVE BEEN DESIGNED, FABRICATED, TESTED |
| | AND MARKED (STAMPED) IN ACCORDANCE WITH THE REGULATIONS |
| | AS REQUIRED BY THE REGULATORY AGENCIES AND COMPLIANCE |
| | STANDARDS LISTED IN SECTION 5.2.1.1 NFPA 58. |
| | |
| | 2) SHEET 1: PROVIDE A REVISED SURVEY DRAWING MARKED UP |
| | TO SHOW THE REQUIRED 10 FT. UG LP TANK CLEARANCE |
| | DISTANCES TO THE BUILDINGS AND ADJACENT PROPERTY LINES- |
| | TABLE 6.3.1.1 NFPA 58. PLEASE NOTE THAT IF THE TANK IS |
| | LOCATED WITHIN 10 FT. OF A PUBLIC VEHICULAR |
| | THOROUGHFARE OR PARKING LOCATION, THE SHELL FOR THE |
| | TANK SHALL BE 18 IN. BELOW GRADE OR VEHICULAR BARRIER |
| | PROTECTION WILL BE REQUIRED- SECTIONS 6.6.1.1 & 6.6.6.1 |
| | (A). THE SUBMITTED SITE PLAN SHALL ALSO BE REVISED TO |
| | SHOW COMPLIANCE. |
| | |
| | 3) SHEET 1: THE UG LP TANK ANCHORING DETAIL WITH |
| | HYDROSTATIC LIFT CALCULATION SHALL BE SIGNED AND SEALED |
| | BY THE FL. LICENSED ENGINEER WHO PREPARED THE |
| | CALCULATIONS AND DRAWING- SECTION 6.6.1.6 NFPA 58, AND |
| | FLORIDA STATUTE 471.003. PLEASE NOTE THAT THERE IS |
| | MISSING INFORMATION IN THE DETAIL INCLUDING THE TYPE, |
| | SIZE AND NUMBER OF CABLES OR STRAPS; PROTECTION FOR THE |
| | TANKS FROM THE STRAPS OR TIES; THE TYPE, SIZE, AND |
| | NUMBER OF ANCHOR; AND THE DEPTH OF ANCHOR EMBEDMENT. |
| | MANUFATURER'S SPECS FOR THE PRE-FAB SLAB SHALL ALSO BE |
| | SUBMITTED |
| | |
| | 4) SHEET 1: THE UG LP TANK SHALL BE PROTECTED AGAINST |
| | CORROSION BY INSTALLATION OF A CATHODIC PROTECTION |
| | SYSTEM CONSISTING OF A SACRIFICIAL ANODE OR AN |
| | IMPRESSED CURRENT ANODE PER SECTIONS 5.2.1.11 & |
| | 6.6.6.1(I) NFPA 58. INDICATE THE TYPE OF PROTECTION, |
| | SUBMIT MANUFACTURER'S SPECIFICATIONS, AND INDICATE HOW |
| | IT WILL BE TESTED- SECTION 6.17.1. |
| | |
| | 5) SHEET 1: SUBMIT MANUFACTURER'S SPECIFICATIONS FOR |
| | THE BBQ GRILLS AND THE FIRETABLES- SECTION 305.1 FBC |
| | FG. THE SPECS SHALL BE MARKED OR HIGHLIGHTED TO SHOW |
| | THE APPLIANCE'S LISTING, BTUH LOADS, AND REQUIRED GAS |
| | INPUT PRESSURES. |
| | |
| | 6) SHEET 1 & 2: NO ARCHITECTURAL PLANS HAVE BEEN |
| | SUBMITTED FOR THE PROJECT UNDER THIS PERMIT. |
| | ARCHITECTURAL PLANS SHALL BE SUBMITTED THAT IDENTIFY |
| | THE STRUCTURE AND INDICATE IF IT IS OPEN OR ENCLOSED, |
| | THE TYPE OF CONSTRUCTION- NON-COMBUSTIBLE OR |
| | COMBUSTIBLE, AND IF THE APPLIANCES ARE BEING INSTALLED |
| | UNDER A ROOF OR OVERHEAD CONSTRUCTION. COMPLETE |
| | DIMENSIONED DETAILS FOR CONSTRUCTION OF THE BARS, |
| | COUNTERS, OR TABLES THE APPLIANCES WILL BE INSTALLED IN |
| | SHALL BE PROVIDED INCLUDING FRONT AND SIDE ELEVATION |
| | VIEWS- SECTION 107.2.1 WPB. PLEASE NOTE THAT A COMPLETE |
| | REVIEW OF THE APPLIANCE INSTALLATIONS AND REQUIRED |
| | VENTING SYSTEMS CANNOT BE ACCOMPLISHED AT THIS TIME, |
| | AND THAT A COMPLETE REVIEW MAY INCLUDE ACCESSIBILITY |
| | COMPLIANCES IIN ACCORDANCE WITH THE FLORIDA |
| | ACCESSIBILITY CODE-2017. |
| | |
| | 7) SHEET 2, GAS ISOMETRIC DRAWING: |
| | A) THE REGULATOR AT THE TANK IS A 1ST STAGE REGULATOR- |
| | REMOVE THE NOTE INDICATING 2ND STAGE REGULATOR WHICH |
| | ARE LOCATED AT THE APPLIANCES- SECTIONS 410.1 AND 410.2 |
| | FBC FG. |
| | B) INDICATE THE MAKES AND MODEL NUMBERS OF THE |
| | REGULATORS AND SHOW THE OUTLET PRESSURE (IN. WC.) AT |
| | EACH APPLIANCE. SUBMIT MANUFACTURER'S SPECS FOR THE |
| | REGULATORS MARKED UP TO SHOW THE SELECTED MODELS, INLET |
| | AND OUTLET PIPE SIZES AND PRESSURES, AND ORIFICE SIZES- |
| | SECTION 410.1 & 410.2 FBC FG. |
| | C) INDICATE THE BURIAL DEPTH OF THE PE PIPING PER |
| | SECTION 404.12 AND SHOW A TRACER WIRE WILL BE INSTALLED |
| | ADJACENT TO THE PIPE- SECTION 404.17.3 FBC FG. PLEASE |
| | NOTE THAT THE PE MAY BE INSTALLED WITHOUT CONDUIT UNDER |
| | A PATIO OR DRIVEWAY BUT MUST BE ENCASED IN A CONDUIT IF |
| | INSTALLED UNDER A BUILDING- SEE SECTION 404.14. |
| | D) SHOW HOW THE PE PIPING RISER WILL CONNECT TO THE |
| | SCHEDULE 40 METALLIC PIPE PER SECTION 404.17.2 FBC FG. |
| | PLEASE NOTE THAT SPECS FOR ANODELESS RISERS AND |
| | PE/METALLIC PIPE CONNECTORS SHALL BE ASTM D2513 |
| | CATEGORY 1 OR ASTM F1973 LISTED AND LABELED. |
| | E) PLEASE CLEARLY SHOW THE LOCATIONS OF THE REGULATORS |
| | AND SHUTOFF VALVES AT THE TANK AND THE APPLIANCES- THEY |
| | ARE BARELY VISIBLE ON THE DRAWING- SECTIONS 409.1 & |
| | 410.1 & 410.2 FBC FG. SHOW THE LOCATIONS OF THE |
| | REQUIRED PIPE UNIONS WITHIN 1 FT. EACH SIDE OF THE |
| | REGULATORS- SECTION 410.2(7). |
| | |
| | 8) THE $10,000 APPEARS LOW FOR THE SCOPE OF THE |
| | PROJECT. PLEASE PROVIDE A COPY OF A CONTRACT AND/OR |
| | ESTIMATES AND INVOICES TO VERIFY THE TOTAL COST OF THE |
| | PROJECT INCLUDING LABOR, MATERIALS, EQUIPMENT, |
| | APPLIANCES, SITE WORK, ARCHITECTURAL AND STRUCTURAL |
| | WORK, DESIGN FEES, AND OVERHEAD AND PROFIT- SECTION |
| | 109.3 WPB. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |