Plan Review Notes
Plan Review Notes For Permit 20090598
Permit Number 20090598
Review Stop E
Sequence Number 4
Notes
Date Text
2020-12-21 09:39:20ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 VALUE OF WORK IS NOT $15,000 PLEASE SUBMIT A REASONABLE
 VALUE OF THE WORK.
  
 PERMIT STILL STATES IT IS FOR RESTRIPING OF PARKING
 GARAGE.
  
 ELECTRICAL PERMIT REQUIRED FOR ELECTRICAL WORK.
  
 PLEASE SHOW WHERE POWER IS COMING FROM ON THE RISER
 DIAGRAM, SHOW DISCONNECT AT POINT OF FEEDER ENTERING
 THE GARAGE FACITILTY. SHOW OTHER BUILDING, FEEDER,
 DISCONNECT, TRANSFORMER, AND THE PANEL........ SHOW
 THESE ON A PLAN FOR LAYOUT OF JOB.
  
 PLEASE SUBMIT A PANEL SCHEDULE FOR PANEL CS
  
 PLEASE SUBMIT SIGNAGE COPY OF SIGNS FOR SERVICE AND
 FEEDERS IN SAME BUILDING FROM DIFFERENT SOURCES. FOR
 FIRE DEPT. SHOWING LOCATION OF MAINS