2020-12-03 15:27:48ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
  
 1) A DISCONNECT SHALL BE INSTALLED AT THE POINT OF
 ENTRANCE TO THE BUILDING FOR THE FEEDER FROM THE OTHER
 BUILDING.
  
 2) PLEASE SUPPLY A RISER DIAGRAM SHOWING MAIN TO
 TRANSFORMER, LOCATION OF PANEL CS, LOCATION OF
 TRANSFORMER TX-CS PLEASE SHOW BREAKERS SIZE AND SIZE OF
 WIRES. SIGNS SHALL BE PLACED AT BOTH THE FEEDER
 DISCONNECT'S ENTRANCE INTO THE GARAGE AND ANOTHER SIGN
 LOCATED AT THE MAIN SERVICE FOR THE GARAGE INDICATING
 THAT ANOTHER MEANS OF DISCONNECT IS LOCATED ON THE
 PREMISES AND WHERE IT IS LOCATED. POWER DISCONNECT HAVE
 TO READILLY AVAILABLE IN ORDER TO DISCONNECT THE ENTIRE
 ELECTRICAL SYSTEM TO THE GARAGE.
  
 3) VALUE OF JOB IS TO INCLUDE THE CHARGERS PLUS ALL
 MATERIALS AND LABOR FOR A COMPLETE JOB. (25000)
  
 4) AIC RATING FOR THE SERVICE TO THIS PROJECT 110.9,
 110.10
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER
 561-805-6713
 [email protected]
  
  