| Date |
Text |
| 2020-12-03 15:27:48 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | FLORIDA BUILDING CODE 2017 6TH EDITION |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED |
| | NFPA 70 2014 EDITION |
| | |
| | JAKE LEAHY BN, BU, PX |
| | ELECTRICAL PLANS EXAMINER II |
| | 561-805-6713 |
| | [email protected] |
| | |
| | |
| | 1) A DISCONNECT SHALL BE INSTALLED AT THE POINT OF |
| | ENTRANCE TO THE BUILDING FOR THE FEEDER FROM THE OTHER |
| | BUILDING. |
| | |
| | 2) PLEASE SUPPLY A RISER DIAGRAM SHOWING MAIN TO |
| | TRANSFORMER, LOCATION OF PANEL CS, LOCATION OF |
| | TRANSFORMER TX-CS PLEASE SHOW BREAKERS SIZE AND SIZE OF |
| | WIRES. SIGNS SHALL BE PLACED AT BOTH THE FEEDER |
| | DISCONNECT'S ENTRANCE INTO THE GARAGE AND ANOTHER SIGN |
| | LOCATED AT THE MAIN SERVICE FOR THE GARAGE INDICATING |
| | THAT ANOTHER MEANS OF DISCONNECT IS LOCATED ON THE |
| | PREMISES AND WHERE IT IS LOCATED. POWER DISCONNECT HAVE |
| | TO READILLY AVAILABLE IN ORDER TO DISCONNECT THE ENTIRE |
| | ELECTRICAL SYSTEM TO THE GARAGE. |
| | |
| | 3) VALUE OF JOB IS TO INCLUDE THE CHARGERS PLUS ALL |
| | MATERIALS AND LABOR FOR A COMPLETE JOB. (25000) |
| | |
| | 4) AIC RATING FOR THE SERVICE TO THIS PROJECT 110.9, |
| | 110.10 |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |
| | SINCERELY, |
| | |
| | JAKE LEAHY |
| | ELECTRICAL PLANS EXAMINER |
| | 561-805-6713 |
| | [email protected] |
| | |
| | |