2020-10-27 15:13:29ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PLANS FOR THIS JOB ARE VERY HARD TO UNDERSTAND. YOUR
 PLANS ARE NOT CLEAR AND HARD TO READ. I JUST NOW
 REALIZED THAT YOU ARE BRINGING ANOTHER FEEDER FROM
 ANOTHER SERVICE INTO THE GARAGE. PLEASE INDICATE NEC
 COMPLIANCE.
  
 1) SERVICE FOR CHARGERS WILL NEED TO BE GROUPED WITH
 THE MAINS FOR THE GARAGE. 230.2, 225.30
  
 2) PLEASE SUPPLY A RISER DIAGRAM SHOWING MAIN TO
 TRANSFORMER, LOCATION OF PANEL CS, LOCATION OF
 TRANSFORMER TX-CS
  
 3) VALUE OF JOB IS TO INCLUDE THE CHARGERS PLUS ALL
 MATERIALS AND LABOR FOR A COMPLETE JOB. (25000)
  
 4) AIC RATING FOR THE SERVICE TO THIS PROJECT 110.9,
 110.10
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  