| 2020-09-16 12:06:19 | 1ST REVIEW FBC-2017 PLUMBING |
| | PERMIT- 20090572 |
| | 9/16/2020 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PROVIDE A BASIC SITE PLAN TO SHOW THE LOCATIONS OF |
| | THE NEW TANKLESS WATER HEATER- SECTION 107.2.1 WPB. |
| | THIS IS A COMMERCIAL PROPERTY WITH PAVED DRIVE AND |
| | PARKING AREAS. SHOW HOW THE WATER HEATER WILL BE |
| | PROTECTED FROM VEHICULAR IMPACT- SECTION 303.4 FBC FG. |
| | |
| | 2) HIGHLIGHT THE GPM FLOW RATE SHOWN ON THE SPECS FOR |
| | THE SELECTED MODEL AND SUBMIT THE MANUFACTURER'S |
| | TEMPERATURE RISE CHART- SECTION 502.1 FBC P. PROVIDE A |
| | LIST OF PLUMBING FIXTURES AND THEIR REQUIRED FLOW RATES |
| | TO BE SUPPLIED BY THE WATER HEATER- SEE TABLE 604.3 FBC |
| | P. THE SPECS SHALL VERIFY THE INTEGRAL RECIRCULATION |
| | PUMP WILL HAVE THE CAPACITY TO PROVIDE ADEQUATE FLOW TO |
| | THE EXISTING FIXTURES. |
| | |
| | 3) PROVIDE A WATER DISTRIBUTION RISER DIAGRAM SHOWING |
| | THE WATER PIPING TIE-IN CONNECTIONS TO THE NEW WATER |
| | HEATER. INDICATE THE TYPES AND SIZES OF HOT, COLD, AND |
| | HOT WATER RECIRCULATION PIPES, AND LOCATIONS AND TYPES |
| | OF SHUT-OFF VALVES TO BE INSTALLED- SECTIONS 604.3 & |
| | 606.1 FBC P. CLARIFY IF A THERMOSTATIC MIXING VALVE IS |
| | EXISTING OR TO BE INSTALLED AND SHOW THE WHERE THE HOT |
| | WATER RETURN PIPE WILL MAKE CONNECTION BACK INTO THE |
| | SYSTEM- SECTION 607.2.2 FBC P. |
| | |
| | 4) INDICATE THE TYPE AND THICKNESS OF HOT WATER PIPE |
| | INSULATION TO BE INSTALLED- SECTION C404.4 FBC EC. |
| | |
| | 5) REFER TO TABLE C404.2 FBC EC AND HIGHLIGHT OR MARKUP |
| | THE EFFICIENCY RATING OF THE NEW WATER HEATER. |
| | |
| | 6) PROVIDE A PLUMBING SUB-PERMIT APPLICATION- SECTION |
| | 105.1 WPB. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |