| 2020-09-23 18:23:16 | 09/23/20 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. PLEASE SHOW THE ISOMETRIC DRAWING BY ITSELF AS THE |
| | WAY IT IS DRAWN TO MANY LINES. WE CANNOT DETERMINE WHAT |
| | GOES WERE PER THE WEST PALM BEACH AMENDMENTS TO FBC |
| | SEC. 107.2.1. |
| | |
| | 2. ON THE ISOMETRIC, THE SANITARY LINE THAT GOES TO |
| | PICK UP THE KITCHEN AND WASHING MACHINE SHOULD BE |
| | DOWNSTREAM FROM THE WET VENT OF THE BATHROOM GROUPS PER |
| | THE 2017 FBC SEC. R 3108.1. |
| | |
| | 3. THE WASHING MACHINE IS ON A TWO INCHES SANITARY LINE |
| | AND PER MOST MANUFACTURER'S SPECIFICATIONS IT REQUIRES |
| | A THREE-INCH DRAIN LINE UP TO THE SANITARY TEE PLEASE |
| | CHANGE PER THE PER THE WEST PALM BEACH AMENDMENTS TO |
| | FBC SEC. 107.2.1. |
| | |
| | 4. THE AIR CONDITION DRAIN LINE CANNOT DUMP INTO THE |
| | SANITARY LINE IT MUST BE DRAINED OUTSIDE THE STRUCTURE |
| | A FOOT AWAY FROM THE STRUCTURE PER THE 2017 FBC SEC. |
| | R318.5. |
| | |
| | 5. THE WASHING MACHINE VALVES SHALL BE ACCESSIBLE |
| | WITHOUT MOVING OF THE UNITS AND WITHIN REACH PER THE |
| | 2017 FBC SEC. R 2903.9.3. |
| | |
| | 6. SUBMIT A SLAB REPAIR DETAIL AND SHOW THE WIDTH OF |
| | THE REPAIR, THE MINIMUM THICKNESS OF THE CONCRETE TO BE |
| | REPLACED, AND THE PSI OF THE CONCRETE. SHOW THE SIZE |
| | AND LENGTH OF THE DOWELS, THE MINIMUM EMBEDMENT DEPTH |
| | INTO THE EXISTING SLAB, THE ANCHORING MATERIAL FOR THE |
| | DOWELS, AND THE SPACING OF THE DOWELS ON CENTER. THE |
| | REPAIR SHALL ALSO INCLUDE TERMITE TREATMENT OF THE SOIL |
| | AND THE REQUIRED VAPOR BARRIER OVER WELL-COMPACTED |
| | SOIL. A COPY OF THE TERMITE CERTIFICATE SHALL BE ONSITE |
| | FOR A FINAL INSPECTION. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |