| Plan Review Notes For Permit 20090566 |
| Permit Number |
20090566 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2020-10-01 10:50:44 | SFR REMODEL | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1 | | | AMENDMENTS | | | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | | 1) PLEASE PROVIDE COMPLETE MIAMI DADE OR FLORIDA STATE | | | PRODUCT APPROVALS FOR THE NEW EXTERIOR DOORS AND | | | WINDOWS. (COMPLETE = FRONT PAGES AND THE INSTALLATION | | | INSTRUCTIONS). ALL PRODUCT APPROVALS NEED TO BE | | | REVIEWED AND MARKED APPROVED BY THE BUILDING DESIGNER | | | OF RECORD OR BE MENTIONED ON THE DRAWING. | | | 2) R30 BATT INSULATION SHOWN IN THE 2X6 RAFTERS WILL | | | NOT GIVE YOU THE REQUIRED 1 INCH VENTILATION REQUIRED | | | FBC R806.3 VENT AND INSULATION CLEARANCE. | | | WHERE EAVE OR CORNICE VENTS ARE INSTALLED, INSULATION | | | SHALL NOT BLOCK THE FREE FLOW OF AIR. NOT LESS THAN A | | | 1-INCH (25 MM) SPACE SHALL BE PROVIDED BETWEEN THE | | | INSULATION AND THE ROOF SHEATHING AND AT THE LOCATION | | | OF THE VENT. | | | 3) PLEASE PROVIDE A COMPLETE MIAMI DADE OR FLORIDA | | | STATE PRODUCT APPROVAL FOR THE ROOFING SHINGLES. | | | |
|