| Date |
Text |
| 2020-11-18 16:29:05 | 2ND REVIEW FBC-2017 RES. FUEL GAS |
| | PERMIT- 20090559 |
| | 11/18/2020 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | COMMENT #2 FROM THE 1ST REVIEW WAS NOT ADDRESSED- |
| | PLEASE COMPLY. |
| | |
| | 2) SHEET 1: THE UG LP TANK INSTALLATION DETAIL HAS A |
| | COPIED ENGINEER'S SEAL AND SIGNATURE FROM 7/11/10. |
| | PLEASE SUBMIT AN UPDATED DOCUMENT WITH AN ELECTRONIC |
| | SEAL AND SIGNATURE, OR IF THE EOR DOES NOT HAVE AN |
| | ELECTRONIC SEAL AND SIGNATURE, A HARD PAPER COPY WITH A |
| | RAISED OR INK SEAL AND WET SIGNATURE CAN BE DROPPED OFF |
| | IN THE DROP BOX AT WPB CITY HALL WITH AN ATTACHED PLAN |
| | REVIEW REQUEST FORM- FL. STATUTE 471.025 AND SECTIONS |
| | 61G15-23.002-23.005 FAC. PLEASE SHOW ON THE DETAIL HOW |
| | THE TANK WILL BE PROTECTED FROM ABRASION AND CORROSION |
| | FROM THE TIE DOWN CABLES. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL/PLUMBING PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |