| 2020-10-05 17:34:12 | 1ST REVIEW FBC-2017 RES. FUEL GAS |
| | PERMIT- 20090559 |
| | 10/5/2020 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SURVEY: PLEASE SHOW THE CLEARANCE DISTANCE FROM THE |
| | TANK LP TANK TO THE DRIVEWAY- SECTIONS 6.6.1.1 & |
| | 6.6.6.1 NFPA 54. |
| | |
| | 2) SHEET 1: THE UG LP TANK INSTALLATION DETAIL HAS A |
| | COPIED ENGINEER'S SEAL AND SIGNATURE FROM 7/11/10. |
| | PLEASE SUBMIT AN UPDATED DOCUMENT WITH AN ELECTRONIC |
| | SEAL AND SIGNATURE, OR IF THE EOR DOES NOT HAVE AN |
| | ELECTRONIC SEAL AND SIGNATURE, A HARD PAPER COPY WITH A |
| | RAISED OR INK SEAL AND WET SIGNATURE CAN BE DROPPED OFF |
| | IN THE DROP BOX AT WPB CITY HALL WITH AN ATTACHED PLAN |
| | REVIEW REQUEST FORM- FL. STATUTE 471.025 AND SECTIONS |
| | 61G15-23.002-23.005 FAC. PLEASE SHOW ON THE DETAIL HOW |
| | THE TANK WILL BE PROTECTED FROM ABRASION AND CORROSION |
| | FROM THE TIE DOWN CABLES. |
| | |
| | 3) SUBMIT SPECS FOR THE NEW GAS RANGE THAT INDICATE THE |
| | BTUH LOAD AND GAS INPUT PRESSURE- SECTION 107.2.1 WPB. |
| | |
| | 4) INDICATE HOW COMBUSTION AIR WILL BE PROVIDED TO THE |
| | NEW RANGE AND PROVIDE COMBUSTION AIR CALCULATIONS- |
| | SECTION G2407.1 FBC RES. PLEASE NOTE IF USING INDOOR |
| | AIR SEE SECTION G2407.5. |
| | |
| | 5) INDICATE HOW THE NEW RANGE WILL BE VENTED. CLARIFY |
| | IF THERE IS AN EXISTING RANGE HOOD OR IF A NEW HOOD AND |
| | EXHAUST SYSTEM WILL BE INSTALLED- SECTION M1503 FBC |
| | RES. AND SECTION 107.2.1 WPB. PLEASE NOTE THAT NEW |
| | RANGE HOODS AND EXHAUST DUCTS WILL REQUIRE PLANS AND |
| | SPECIFICATIONS TO BE SUBMITTED, AND A MECHANICAL SUB OR |
| | PRIMARY PERMIT MUST BE OBTAINED- SECTION 105.1 WPB. |
| | |
| | 6) THE CONTRACTOR OR QUALIFIER WHO PREPARED THE GAS |
| | RISER DRAWING SHALL PROVIDE HIS/HER SIGNATURE ON IT- |
| | SECTION 107.2.1 WPB, AND FLORIDA STATUTES 471.003(2)(H) |
| | & 471.025. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |