| Plan Review Notes For Permit 20090530 |
| Permit Number |
20090530 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2020-09-24 13:26:38 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE DRAWING THAT WAS SUBMITTED SHOWS THE DOOR | | | OPENING AS 164" X 96". THE MAXIMUM WIDTH OF THE DOOR IN | | | THE PRODUCT APPROVAL IS 151.5" WHICH IS TOO SMALL FOR | | | THE OPENING. PLEASE CLARIFY. CITY AMENDMENTS FBC 107.1 |
|