Plan Review Notes
Plan Review Notes For Permit 20090500
Permit Number 20090500
Review Stop P
Sequence Number 2
Notes
Date Text
2020-12-02 15:11:17CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 NFPA 99 = HEALTH CARE FACILITIES CODE
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
  
 20090500 5325 GREENWOOD AVE
  
 2ND REVIEW
 PLUMBING COMMENTS: DENIED
 A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS AS
 REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW
 PROCESS BUT IS TYPICALLY ADDRESSED ON THE ARCHITECTURAL
 PLANS. ANY COMMENTS CONCERNING THESE REQUIREMENTS MUST
 BE SATISFACTORILY ADDRESSED PRIOR TO A PLUMBING REVIEW
 APPROVAL.
  
 ORIGINAL COMMENT #1. IS THERE A STORM PIPING SYSTEM IN
 THE BUILDING OR IS THE BUILDING BEING DRAINED BY
 SCUPPERS AND A GUTTER SYSTEM. PER WPB FBC 107.2.1,
 INDICATE ON THE ROOF PLAN HOW THE REQUIREMENTS OF FBC
 PL CHAPTER 11 ARE BEING MET. SHOW EXISTING ROOF DRAINS,
 OVERFLOW DRAINS AND/OR EXISTING GUTTERS. IF THERE IS AN
 EXISTING STORM PIPING SYSTEM, THEN PROVIDE FOR
 REFERENCE A COPY OF RECORD DRAWINGS FOR THE
 INSTALLATION.
 COMPLIED; PROVIDE A REFERENCE COPY OF RECORD DRAWINGS
 FOR SHELL BUILDING.
  
 ORIGINAL COMMENT #2. COMPLIED
  
 ORIGINAL COMMENT #3. COMPLIED
  
 ORIGINAL COMMENT #4. COMPLIED: RE: PLAN G4.01, ADA
 STANDARDS;
 NEW COMMENT: G4.01, ADA STANDARDS; TYP. ACCESSIBLE
 TOILET ELEVATIONS. SPACE BETWEEN SIDE WALL AND REAR
 HAND RAIL SHALL BE 6 INCHES MAXIMUM, NOT 9 INCHES.
  
 ORIGINAL COMMENT #5. COMPLIED
  
 ORIGINAL COMMENT #6. PER WPB FBC 107.2.1 AND
 107.3.5.1.3, PROVIDE SIZED DOMESTIC WATER, SANITARY,
 COMPRESSED AIR AND CLEAR WASTE WATER RISER DIAGRAMS.
 PARTIALLY COMPLIED; SEE BELOW
 A.WATER RISER DIAGRAM SHALL SHOW ALL VALVES, BACKFLOW
 DEVICES, IN-LINE EQUIPMENT (I.E. RECIRCULATING PUMP,
 THERMAL MIXING VALVE), WATER HEATER, POINTS OF
 CONNECTION TO FIXTURES/EQUIPMENT AND OWNER SUPPLIED
 EQUIPMENT AND TO EXISTING SOURCE OF COLD WATER.
 PARTIALLY COMPLIED. SIZE ALL BRANCHES. PROVIDE FULL
 OPEN VALVE AT TOP OF ALL WATER DOWNFEEDS PER FBC PL
 606.1(5).
 B.SANITARY RISER DIAGRAM SHALL SHOW ALL TRAPS, FLOOR
 DRAINS, HUB DRAINS, TRAP PRIMER CONNECTIONS, CLEANOUTS,
 VENTS, POINTS OF CONNECTION TO FIXTURES/EQUIPMENT AND
 OWNER SUPPLIED EQUIPMENT AND TO EXISTING SANITARY
 RISER. IF AN EQUIPMENT ITEM SUCH AS AN ICE MACHINE
 REQUIRES A DRAIN, THEN A WASTE RECEPTACLE AND INDIRECT
 WASTE AND AIR GAP SHALL BE PROVIDED TO COMPLY WITH THE
 PROVISIONS OF FBC PL CHAPTER 8.
 PARTIALLY COMPLIED. SIZE ALL BRANCHES. FIXTURE DRAIN
 SIZES NOT REQUIRED AS LONG AS THE SIZE IS NOTED ON
 P0.01 FIXTURE CONNECTION SCHEDULE. IT IS NOTED HOWEVER
 ON P0.01 FIXTURE CONNECTION SCHEDULE P-16 FLOOR SINK
 THAT WASTE CONNECTION SIZE SHALL BE AS SHOWN. NO SIZING
 OF P-16 FLOOR SINK(S) IS SHOWN. PER WPB FBC 107.2.1,
 PROVIDE SIZING. PROVIDE NOTES SIMILAR TO WHAT WAS DONE
 FOR THE WATER CONNECTIONS TO OWNER SUPPLIED EQUIPMENT
 STATING HOW EQUIPMENT IS TO BE DRAINED (I.E. SIZED
 INDIRECT WASTE TO FLOOR ADJACENT FLOOR SINK WITH AIR
 GAP).
 C.COMPRESSED AIR TO SHOW PIPE, VALVES, REGULATORS,
 FILTERS AND FITTINGS, SOURCE COMPRESSOR AND POINT OF
 CONNECTION TO EQUIPMENT BEING SERVICED.
 PARTIALLY COMPLIED. SIZE ALL BRANCHES. SHOW ALL VALVES,
 REGULATORS, FILTERS, SOURCE COMPRESSOR. ADDITIONALLY,
 SHOW HOW OWNER SUPPLED AIR COMPRESSOR WILL BE DRAINED
 OF CONDENSATE. PROVIDE DETAIL(S) FOR EQUIPMENT
 CONNECTIONS AT SOURCE AND AT POINT OF USE. REFERENCE
 ORIGINAL REVIEW COMMENT 17. RESPONSE THAT THERE IS NO
 COMPRESSED AIR OTHER THAN MEDICAL GAS DOES NOT
 CORRESPOND WITH THE SUBMITTED PLUMBING PLANS. P2.00
 WATER RISER DIAGRAM AND P1.03 BOTH SHOW COMPRESSED AIR
 PIPING. P1.03 NOTES 1, 4, 13, 14, 15, 16, 17 AND 18
 ADDRESSES THE COMPRESSED AIR AS WELL AND NOTE 15
 REFERENCES AN OWNER SUPPLIED AIR COMPRESSOR. IF THERE
 IS NO COMPRESSED AIR AS YOUR RESPONSE INDICATED, THEN
 REMOVE ALL REFERENCE FROM THE PLAN.
 D.CLEAR WASTEWATER RISER DIAGRAM SHALL SHOW ALL
 EQUIPMENT POINTS OF CONNECTION, TRAPS, VENTS AND POINT
 OF DISPOSAL. SECOND REQUEST: SIZED CLEAR WASTEWATER A/C
 CONDENSATE DRAIN RISER DIAGRAM REQUIRED.
  
 ORIGINAL COMMENT #7. COMPLIED
  
 ORIGINAL COMMENT #8. COMPLIED
  
 ORIGINAL COMMENT #9. REQUIRE THIS REFERENCED DEFERRED
 SUBMITTAL FOR OWNER PROVIDED EQUIPMENT SCHEDULE AND
 MANUFACTURER'S SPECIFICATION/INSTALLATION MANUAL SHALL
 BE ADDED TO THE LIST OF DEFERRED SUBMITTALS NOTE IN
 G1.01; DEFERRED SUBMITTALS
  
 ORIGINAL COMMENT #10. COMPLIED
  
 ORIGINAL COMMENT #11. COMPLIED
  
 ORIGINAL COMMENT #12.RE: P0.01 PLUMBING FIXTURE
 SCHEDULE; P-7 RECESSED BOX. WHAT KIND OF EQUIPMENT IS
 BEING SERVICED? A COFFEE MAKER OR ICE MACHINE REQUIRES
 A BACKFLOW PREVENTION DEVICE TO COMPLY WITH THE
 REQUIREMENTS OF FBC PL 608 AND IN INSTANCES WHERE QUICK
 CLOSING VALVES ARE UTILIZED, A WATER HAMMER ARRESTOR
 CONFORMING TO ASSE 1010 SHALL BE INSTALLED. PER WPB FBC
 107.2.1, ANY REQUIRED BACKFLOW DEVICE AND/OR WATER
 HAMMER ARRESTOR SHALL BE SPECIFIED AND SCHEDULED.
 PARTIALLY COMPLIED; TO BE CLEAR, THERE ARE EIGHT (8)
 EACH P-7 RECESSED OATEY 39151 WALL BOXES FOR
 REFRIGERATOR ICE OR COFFEE MAKER COLD WATER
 CONNECTIONS. CONNECTIONS TO COFFEE MAKERS REQUIRE
 BACKFLOW PREVENTERS TO COMPLY WITH FBC PL 608. PER WPB
 FBC 107.2.1, IDENTIFY THE PIECE OF EQUIPMENT THAT EACH
 P-7 WILL SERVICE. PROVIDE NOTE REQUIRING BACKFLOW
 PREVENTER FOR COFFEE MAKER CONNECTIONS OR ANY OTHER
 EQUIPMENT THAT WOULD REQUIRE A BACKFLOW PREVENTER TO
 COMPLY WITH FBC PL 608. SPECIFY SAID BACKFLOW
 PREVENTER(S).
  
 ORIGINAL COMMENT #13. SECOND REQUEST: PROVIDE NOTE
 REQUIRING INSULATION OF HOT WATER PER FBC EC C404.4.
 REFER TO 20032 PALM BEACH INTERNATIONAL SC SPECS
 SECTION 22-07-00 FOR INSULATION SPECIFICATIONS
 (PROVIDED IN SUPPORTING DOCUMENTS)
 PLEASE NOTE, I FOUND A NOTE ON P1.03, MEDICAL GAS
 GENERAL NOTE REFERENCING SPECIFICATIONS, BUT NOTHING ON
 PLUMBING PLANS REGARDING THE REQUIREMENT FOR HOT WATER
 INSULATION.
  
 ORIGINAL COMMENT #14. SECOND REQUEST: PROVIDE NOTE:
 "REFER TO 20032 PALM BEACH INTERNATIONAL SC SPECS
 DIVISION 22-PLUMBING FOR PLUMBING SPECIFICATIONS"
 (PROVIDED IN SUPPORTING DOCUMENTS)
 PLEASE NOTE, I FOUND A NOTE ON P1.03, MEDICAL GAS
 GENERAL NOTE REFERENCING SPECIFICATIONS, BUT NOTHING ON
 PLUMBING PLANS REGARDING "REFER TO 20032 PALM BEACH
 INTERNATIONAL SC SPECS DIVISION 22-PLUMBING FOR
 PLUMBING SPECIFICATIONS"
  
 ORIGINAL COMMENT #15. PARTIALLY COMPLIED: PER WPB FBC
 107.2.1, SHOW (PLAN VIEW AND RISER DIAGRAM) HOW
 DISPOSAL OF WASTEWATER FROM THE MEDICAL GAS VACUUM PUMP
 RECEIVER TANK ON THE FIRST FLOOR WILL BE ACHIEVED;
 PROVIDE DETAIL. COMPLY WITH FBC PL CHAPTERS 7,8 AND 9.
 IF CONCRETE SLAB IS TO BE CUT AND REMOVED THEN PROVIDE
 A SLAB REPAIR DETAIL ON THE PLANS. SHOW THE WIDTH OF
 THE REPAIR, THE MINIMUM THICKNESS AND PSI OF THE
 CONCRETE TO BE REPLACED. SHOW SIZE, LENGTH, SPACING (ON
 CENTER), MINIMUM EMBEDMENT AND ANCHORING/ADHESIVE
 MATERIAL FOR DOWELS. THE REPAIR SHALL ALSO INCLUDE
 TERMITE TREATMENT OF THE SOIL AS WELL AS THE REQUIRED
 VAPOR BARRIER OVER WELL COMPACTED SOIL. A COPY OF THE
 TERMITE CERTIFICATE SHALL BE ONSITE FOR FINAL
 INSPECTION. PROVIDE SANITARY AND WATER RISER DIAGRAMS.
 A.SECOND REQUEST: PER WPB FBC 107.2.1, PROVIDE SIZED
 SANITARY AND WATER RISER DIAGRAMS. SHOW REQUIRED TRAPS,
 VALVES, ETC.
 B.SECOND REQUEST: PER WPB FBC 107.2.1, IT SEEMS
 APPARENT THAT CONCRETE SLAB IS TO BE CUT AND REMOVED;
 PROVIDE A SLAB REPAIR DETAIL ON THE PLANS. SHOW THE
 WIDTH OF THE REPAIR, THE MINIMUM THICKNESS AND PSI OF
 THE CONCRETE TO BE REPLACED. SHOW SIZE, LENGTH, SPACING
 (ON CENTER), MINIMUM EMBEDMENT AND ANCHORING/ADHESIVE
 MATERIAL FOR DOWELS. THE REPAIR SHALL ALSO INCLUDE
 TERMITE TREATMENT OF THE SOIL AS WELL AS THE REQUIRED
 VAPOR BARRIER OVER WELL COMPACTED SOIL. A COPY OF THE
 TERMITE CERTIFICATE SHALL BE ONSITE FOR FINAL
 INSPECTION.
  
 ORIGINAL COMMENT #16. COMPLIED
  
 ORIGINAL COMMENT #17. PER WPB FBC 107.2.1, PROVIDE
 MATERIAL SPECIFICATION FOR CLEAR WASTEWATER AND FOR THE
 COMPRESSED AIR SYSTEM. PARTIALLY COMPLIED; REQUEST FOR
 WASTEWATER IS COMPLIANT. RESPONSE THAT THERE IS NO
 COMPRESSED AIR OTHER THAN MEDICAL GAS DOES NOT
 CORRESPOND WITH THE SUBMITTED PLUMBING PLANS. P2.00
 WATER RISER DIAGRAM AND P1.03 BOTH SHOW COMPRESSED AIR
 PIPING. P1.03 NOTES 1, 4, 13, 14, 15, 16, 17 AND 18
 ADDRESSES THE COMPRESSED AIR AS WELL AND NOTE 15
 REFERENCES AN OWNER SUPPLIED AIR COMPRESSOR. PER WPB
 FBC 107.2.1, CLARIFY.
  
  
 END OF COMMENTS.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
 ALL PLANS TO BE SIGNED AND SEALED/DIGITALLY SIGNED AND
 SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-246-0882 MOBILE
  
 20090500 5325 GREENWOOD AVE


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved