| Date |
Text |
| 2020-12-02 15:11:17 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| | MANUAL REVISED 2017 |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION |
| | FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH |
| | EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION |
| | NFPA 99 = HEALTH CARE FACILITIES CODE |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | |
| | 20090500 5325 GREENWOOD AVE |
| | |
| | 2ND REVIEW |
| | PLUMBING COMMENTS: DENIED |
| | A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS AS |
| | REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW |
| | PROCESS BUT IS TYPICALLY ADDRESSED ON THE ARCHITECTURAL |
| | PLANS. ANY COMMENTS CONCERNING THESE REQUIREMENTS MUST |
| | BE SATISFACTORILY ADDRESSED PRIOR TO A PLUMBING REVIEW |
| | APPROVAL. |
| | |
| | ORIGINAL COMMENT #1. IS THERE A STORM PIPING SYSTEM IN |
| | THE BUILDING OR IS THE BUILDING BEING DRAINED BY |
| | SCUPPERS AND A GUTTER SYSTEM. PER WPB FBC 107.2.1, |
| | INDICATE ON THE ROOF PLAN HOW THE REQUIREMENTS OF FBC |
| | PL CHAPTER 11 ARE BEING MET. SHOW EXISTING ROOF DRAINS, |
| | OVERFLOW DRAINS AND/OR EXISTING GUTTERS. IF THERE IS AN |
| | EXISTING STORM PIPING SYSTEM, THEN PROVIDE FOR |
| | REFERENCE A COPY OF RECORD DRAWINGS FOR THE |
| | INSTALLATION. |
| | COMPLIED; PROVIDE A REFERENCE COPY OF RECORD DRAWINGS |
| | FOR SHELL BUILDING. |
| | |
| | ORIGINAL COMMENT #2. COMPLIED |
| | |
| | ORIGINAL COMMENT #3. COMPLIED |
| | |
| | ORIGINAL COMMENT #4. COMPLIED: RE: PLAN G4.01, ADA |
| | STANDARDS; |
| | NEW COMMENT: G4.01, ADA STANDARDS; TYP. ACCESSIBLE |
| | TOILET ELEVATIONS. SPACE BETWEEN SIDE WALL AND REAR |
| | HAND RAIL SHALL BE 6 INCHES MAXIMUM, NOT 9 INCHES. |
| | |
| | ORIGINAL COMMENT #5. COMPLIED |
| | |
| | ORIGINAL COMMENT #6. PER WPB FBC 107.2.1 AND |
| | 107.3.5.1.3, PROVIDE SIZED DOMESTIC WATER, SANITARY, |
| | COMPRESSED AIR AND CLEAR WASTE WATER RISER DIAGRAMS. |
| | PARTIALLY COMPLIED; SEE BELOW |
| | A.WATER RISER DIAGRAM SHALL SHOW ALL VALVES, BACKFLOW |
| | DEVICES, IN-LINE EQUIPMENT (I.E. RECIRCULATING PUMP, |
| | THERMAL MIXING VALVE), WATER HEATER, POINTS OF |
| | CONNECTION TO FIXTURES/EQUIPMENT AND OWNER SUPPLIED |
| | EQUIPMENT AND TO EXISTING SOURCE OF COLD WATER. |
| | PARTIALLY COMPLIED. SIZE ALL BRANCHES. PROVIDE FULL |
| | OPEN VALVE AT TOP OF ALL WATER DOWNFEEDS PER FBC PL |
| | 606.1(5). |
| | B.SANITARY RISER DIAGRAM SHALL SHOW ALL TRAPS, FLOOR |
| | DRAINS, HUB DRAINS, TRAP PRIMER CONNECTIONS, CLEANOUTS, |
| | VENTS, POINTS OF CONNECTION TO FIXTURES/EQUIPMENT AND |
| | OWNER SUPPLIED EQUIPMENT AND TO EXISTING SANITARY |
| | RISER. IF AN EQUIPMENT ITEM SUCH AS AN ICE MACHINE |
| | REQUIRES A DRAIN, THEN A WASTE RECEPTACLE AND INDIRECT |
| | WASTE AND AIR GAP SHALL BE PROVIDED TO COMPLY WITH THE |
| | PROVISIONS OF FBC PL CHAPTER 8. |
| | PARTIALLY COMPLIED. SIZE ALL BRANCHES. FIXTURE DRAIN |
| | SIZES NOT REQUIRED AS LONG AS THE SIZE IS NOTED ON |
| | P0.01 FIXTURE CONNECTION SCHEDULE. IT IS NOTED HOWEVER |
| | ON P0.01 FIXTURE CONNECTION SCHEDULE P-16 FLOOR SINK |
| | THAT WASTE CONNECTION SIZE SHALL BE AS SHOWN. NO SIZING |
| | OF P-16 FLOOR SINK(S) IS SHOWN. PER WPB FBC 107.2.1, |
| | PROVIDE SIZING. PROVIDE NOTES SIMILAR TO WHAT WAS DONE |
| | FOR THE WATER CONNECTIONS TO OWNER SUPPLIED EQUIPMENT |
| | STATING HOW EQUIPMENT IS TO BE DRAINED (I.E. SIZED |
| | INDIRECT WASTE TO FLOOR ADJACENT FLOOR SINK WITH AIR |
| | GAP). |
| | C.COMPRESSED AIR TO SHOW PIPE, VALVES, REGULATORS, |
| | FILTERS AND FITTINGS, SOURCE COMPRESSOR AND POINT OF |
| | CONNECTION TO EQUIPMENT BEING SERVICED. |
| | PARTIALLY COMPLIED. SIZE ALL BRANCHES. SHOW ALL VALVES, |
| | REGULATORS, FILTERS, SOURCE COMPRESSOR. ADDITIONALLY, |
| | SHOW HOW OWNER SUPPLED AIR COMPRESSOR WILL BE DRAINED |
| | OF CONDENSATE. PROVIDE DETAIL(S) FOR EQUIPMENT |
| | CONNECTIONS AT SOURCE AND AT POINT OF USE. REFERENCE |
| | ORIGINAL REVIEW COMMENT 17. RESPONSE THAT THERE IS NO |
| | COMPRESSED AIR OTHER THAN MEDICAL GAS DOES NOT |
| | CORRESPOND WITH THE SUBMITTED PLUMBING PLANS. P2.00 |
| | WATER RISER DIAGRAM AND P1.03 BOTH SHOW COMPRESSED AIR |
| | PIPING. P1.03 NOTES 1, 4, 13, 14, 15, 16, 17 AND 18 |
| | ADDRESSES THE COMPRESSED AIR AS WELL AND NOTE 15 |
| | REFERENCES AN OWNER SUPPLIED AIR COMPRESSOR. IF THERE |
| | IS NO COMPRESSED AIR AS YOUR RESPONSE INDICATED, THEN |
| | REMOVE ALL REFERENCE FROM THE PLAN. |
| | D.CLEAR WASTEWATER RISER DIAGRAM SHALL SHOW ALL |
| | EQUIPMENT POINTS OF CONNECTION, TRAPS, VENTS AND POINT |
| | OF DISPOSAL. SECOND REQUEST: SIZED CLEAR WASTEWATER A/C |
| | CONDENSATE DRAIN RISER DIAGRAM REQUIRED. |
| | |
| | ORIGINAL COMMENT #7. COMPLIED |
| | |
| | ORIGINAL COMMENT #8. COMPLIED |
| | |
| | ORIGINAL COMMENT #9. REQUIRE THIS REFERENCED DEFERRED |
| | SUBMITTAL FOR OWNER PROVIDED EQUIPMENT SCHEDULE AND |
| | MANUFACTURER'S SPECIFICATION/INSTALLATION MANUAL SHALL |
| | BE ADDED TO THE LIST OF DEFERRED SUBMITTALS NOTE IN |
| | G1.01; DEFERRED SUBMITTALS |
| | |
| | ORIGINAL COMMENT #10. COMPLIED |
| | |
| | ORIGINAL COMMENT #11. COMPLIED |
| | |
| | ORIGINAL COMMENT #12.RE: P0.01 PLUMBING FIXTURE |
| | SCHEDULE; P-7 RECESSED BOX. WHAT KIND OF EQUIPMENT IS |
| | BEING SERVICED? A COFFEE MAKER OR ICE MACHINE REQUIRES |
| | A BACKFLOW PREVENTION DEVICE TO COMPLY WITH THE |
| | REQUIREMENTS OF FBC PL 608 AND IN INSTANCES WHERE QUICK |
| | CLOSING VALVES ARE UTILIZED, A WATER HAMMER ARRESTOR |
| | CONFORMING TO ASSE 1010 SHALL BE INSTALLED. PER WPB FBC |
| | 107.2.1, ANY REQUIRED BACKFLOW DEVICE AND/OR WATER |
| | HAMMER ARRESTOR SHALL BE SPECIFIED AND SCHEDULED. |
| | PARTIALLY COMPLIED; TO BE CLEAR, THERE ARE EIGHT (8) |
| | EACH P-7 RECESSED OATEY 39151 WALL BOXES FOR |
| | REFRIGERATOR ICE OR COFFEE MAKER COLD WATER |
| | CONNECTIONS. CONNECTIONS TO COFFEE MAKERS REQUIRE |
| | BACKFLOW PREVENTERS TO COMPLY WITH FBC PL 608. PER WPB |
| | FBC 107.2.1, IDENTIFY THE PIECE OF EQUIPMENT THAT EACH |
| | P-7 WILL SERVICE. PROVIDE NOTE REQUIRING BACKFLOW |
| | PREVENTER FOR COFFEE MAKER CONNECTIONS OR ANY OTHER |
| | EQUIPMENT THAT WOULD REQUIRE A BACKFLOW PREVENTER TO |
| | COMPLY WITH FBC PL 608. SPECIFY SAID BACKFLOW |
| | PREVENTER(S). |
| | |
| | ORIGINAL COMMENT #13. SECOND REQUEST: PROVIDE NOTE |
| | REQUIRING INSULATION OF HOT WATER PER FBC EC C404.4. |
| | REFER TO 20032 PALM BEACH INTERNATIONAL SC SPECS |
| | SECTION 22-07-00 FOR INSULATION SPECIFICATIONS |
| | (PROVIDED IN SUPPORTING DOCUMENTS) |
| | PLEASE NOTE, I FOUND A NOTE ON P1.03, MEDICAL GAS |
| | GENERAL NOTE REFERENCING SPECIFICATIONS, BUT NOTHING ON |
| | PLUMBING PLANS REGARDING THE REQUIREMENT FOR HOT WATER |
| | INSULATION. |
| | |
| | ORIGINAL COMMENT #14. SECOND REQUEST: PROVIDE NOTE: |
| | "REFER TO 20032 PALM BEACH INTERNATIONAL SC SPECS |
| | DIVISION 22-PLUMBING FOR PLUMBING SPECIFICATIONS" |
| | (PROVIDED IN SUPPORTING DOCUMENTS) |
| | PLEASE NOTE, I FOUND A NOTE ON P1.03, MEDICAL GAS |
| | GENERAL NOTE REFERENCING SPECIFICATIONS, BUT NOTHING ON |
| | PLUMBING PLANS REGARDING "REFER TO 20032 PALM BEACH |
| | INTERNATIONAL SC SPECS DIVISION 22-PLUMBING FOR |
| | PLUMBING SPECIFICATIONS" |
| | |
| | ORIGINAL COMMENT #15. PARTIALLY COMPLIED: PER WPB FBC |
| | 107.2.1, SHOW (PLAN VIEW AND RISER DIAGRAM) HOW |
| | DISPOSAL OF WASTEWATER FROM THE MEDICAL GAS VACUUM PUMP |
| | RECEIVER TANK ON THE FIRST FLOOR WILL BE ACHIEVED; |
| | PROVIDE DETAIL. COMPLY WITH FBC PL CHAPTERS 7,8 AND 9. |
| | IF CONCRETE SLAB IS TO BE CUT AND REMOVED THEN PROVIDE |
| | A SLAB REPAIR DETAIL ON THE PLANS. SHOW THE WIDTH OF |
| | THE REPAIR, THE MINIMUM THICKNESS AND PSI OF THE |
| | CONCRETE TO BE REPLACED. SHOW SIZE, LENGTH, SPACING (ON |
| | CENTER), MINIMUM EMBEDMENT AND ANCHORING/ADHESIVE |
| | MATERIAL FOR DOWELS. THE REPAIR SHALL ALSO INCLUDE |
| | TERMITE TREATMENT OF THE SOIL AS WELL AS THE REQUIRED |
| | VAPOR BARRIER OVER WELL COMPACTED SOIL. A COPY OF THE |
| | TERMITE CERTIFICATE SHALL BE ONSITE FOR FINAL |
| | INSPECTION. PROVIDE SANITARY AND WATER RISER DIAGRAMS. |
| | A.SECOND REQUEST: PER WPB FBC 107.2.1, PROVIDE SIZED |
| | SANITARY AND WATER RISER DIAGRAMS. SHOW REQUIRED TRAPS, |
| | VALVES, ETC. |
| | B.SECOND REQUEST: PER WPB FBC 107.2.1, IT SEEMS |
| | APPARENT THAT CONCRETE SLAB IS TO BE CUT AND REMOVED; |
| | PROVIDE A SLAB REPAIR DETAIL ON THE PLANS. SHOW THE |
| | WIDTH OF THE REPAIR, THE MINIMUM THICKNESS AND PSI OF |
| | THE CONCRETE TO BE REPLACED. SHOW SIZE, LENGTH, SPACING |
| | (ON CENTER), MINIMUM EMBEDMENT AND ANCHORING/ADHESIVE |
| | MATERIAL FOR DOWELS. THE REPAIR SHALL ALSO INCLUDE |
| | TERMITE TREATMENT OF THE SOIL AS WELL AS THE REQUIRED |
| | VAPOR BARRIER OVER WELL COMPACTED SOIL. A COPY OF THE |
| | TERMITE CERTIFICATE SHALL BE ONSITE FOR FINAL |
| | INSPECTION. |
| | |
| | ORIGINAL COMMENT #16. COMPLIED |
| | |
| | ORIGINAL COMMENT #17. PER WPB FBC 107.2.1, PROVIDE |
| | MATERIAL SPECIFICATION FOR CLEAR WASTEWATER AND FOR THE |
| | COMPRESSED AIR SYSTEM. PARTIALLY COMPLIED; REQUEST FOR |
| | WASTEWATER IS COMPLIANT. RESPONSE THAT THERE IS NO |
| | COMPRESSED AIR OTHER THAN MEDICAL GAS DOES NOT |
| | CORRESPOND WITH THE SUBMITTED PLUMBING PLANS. P2.00 |
| | WATER RISER DIAGRAM AND P1.03 BOTH SHOW COMPRESSED AIR |
| | PIPING. P1.03 NOTES 1, 4, 13, 14, 15, 16, 17 AND 18 |
| | ADDRESSES THE COMPRESSED AIR AS WELL AND NOTE 15 |
| | REFERENCES AN OWNER SUPPLIED AIR COMPRESSOR. PER WPB |
| | FBC 107.2.1, CLARIFY. |
| | |
| | |
| | END OF COMMENTS. |
| | |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | ALL PLANS TO BE SIGNED AND SEALED/DIGITALLY SIGNED AND |
| | SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| | |
| | |
| | JERALD SMITH |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | EMAIL [email protected] |
| | PHONE 561-246-0882 MOBILE |
| | |
| | 20090500 5325 GREENWOOD AVE |