Plan Review Notes
Plan Review Notes For Permit 20090500
Permit Number 20090500
Review Stop MEDGAS
Sequence Number 2
Notes
Date Text
2020-12-02 17:25:26CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 NFPA 99 = HEALTH CARE FACILITIES CODE
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 20090500 5325 GREENWOOD AVE
  
 2ND REVIEW
 MEDICAL GAS COMMENTS: DENIED
  
 ORIGINAL COMMENT #1. COMPLIED
  
 ORIGINAL COMMENT #2. SECOND REQUEST: PER NFPA 99-15
 SECTION 5.1.3.1.8, PROVIDE NOTE REQUIRING SIGNAGE ON
 THE ENTRY DOOR TO THE ROOM CONTAINING THE MEDICAL GAS
 MANIFOLDS/CYLINDERS STATING
 "POSITIVE PRESSURE GASES
 NO SMOKING OR OPEN FLAME
 ROOM MAY HAVE INSUFFICIENT OXYGEN
 OPEN DOOR AND ALLOW ROOM TO VENTILATE BEFORE ENTERING"
 TO BE CLEAR, PROVIDE SAID NOTE MAKING THE STATEMENT ON
 THE PLAN.
  
 ORIGINAL COMMENT #3. SECOND REQUEST: PLAN SHEET A9.21;
 ELEVATION OF HEADWALL NOTES A, O AND V OUTLETS. LEGEND
 ONLY IDENTIFIES O AND V. PER WPB FBC 107.2, CLARIFY.
  
 ORIGINAL COMMENT #4. COMPLIED
  
 ORIGINAL COMMENT #5. COMPLIED; FURTHER ACTION REQUIRED.
 PER WPB FBC 107.2.1, THIS REFERENCED DEFERRED SUBMITTAL
 FOR MEDICAL GAS EQUIPMENT SHALL BE ADDED TO THE LIST OF
 DEFERRED SUBMITTALS NOTE IN G1.01; DEFERRED SUBMITTALS.
  
 ORIGINAL COMMENT #6. COMPLIED
  
 ORIGINAL COMMENT #7. COMPLIED
  
 ORIGINAL COMMENT #8. COMPLIED
  
 ORIGINAL COMMENT #9. COMPLIED
  
 ORIGINAL COMMENT #10. COMPLIED
  
 ORIGINAL COMMENT #11. COMPLIED:FURTHER ACTION REQUIRED.
 PER WPB FBC 107.2.1, PROVIDE PROVIDE NOTE ON PLAN
 SHOWING VACUUM SYSTEM IS MONITORED FOR OXYGEN CONTENT
 THAT IS ACQUIRED THROUGH THE WAGD TO COMPLY WITH NFPA
 99-15, SECTION 5.1.3.8.1.2(2) AND 5.1.3.8.3.1. SEE
 PROJECT SPECIFICATION 22-60-00, SECTION 3.1, SUB
 SECTION (S)
  
 ORIGINAL COMMENT #12. COMPLIED
  
 ORIGINAL COMMENT #13. COMPLIED: FURTHER ACTION
 REQUIRED. PER WPB FBC 107.2.1, PROVIDE PROVIDE NOTE ON
 PLAN TO REQUIRE DOCUMENTATION ON ALL PIPE, VALVES AND
 FITTINGS PER NFPA 99-15 SECTION 5.1.10.1.6. SEE PROJECT
 SPECIFICATION 22-60-00, SECTION 1.6, SUB SECTION (E)
  
 ORIGINAL COMMENT #14.COMPLIED: FURTHER ACTION REQUIRED.
 PER WPB FBC 107.2.1, PROVIDE PROVIDE NOTE ON PLAN TO
 REQUIRE BRAZING TECHNICIANS TO BE QUALIFIED AND
 CERTIFIED IN ACCORDANCE WITH NFPA 99-15 SECTION
 5.1.10.11.11. SEE PROJECT SPECIFICATION 22-60-00,
 SECTION 1.7, SUB SECTION (E)
  
 ORIGINAL COMMENT #15.COMPLIED
  
 ORIGINAL COMMENT #16. COMPLIED: FURTHER ACTION
 REQUIRED. PER WPB FBC 107.2.1, PROVIDE PROVIDE NOTE ON
 PLAN TO PROVIDE VALVE ID/SYSTEM IDENTIFICATION/COLOR
 CODING SPECIFICATION PER NFPA 99-15 SECTION 5.1.11
 THROUGH 5.1.11.4. COMPLIED; SEE PROJECT SPECIFICATION
 22-60-00, SECTION 3.1, SUB SECTION (T)
  
 ORIGINAL COMMENT #17.COMPLIED
  
 END OF COMMENTS.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
 ALL PLANS TO BE SIGNED AND SEALED/DIGITALLY SIGNED AND
 SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-246-0882 MOBILE
  
 20090500 5325 GREENWOOD AVE
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved