Plan Review Notes
Plan Review Notes For Permit 20090500
Permit Number 20090500
Review Stop B
Sequence Number 2
Notes
Date Text
2020-11-17 10:23:31WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20090500
 ADD: 5325 GREENWOOD AVE. SUITE: 300
 CONT: DPR CONSTRUCTION
 TEL: 858-210-9600
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: TUES. 17TH/2020
 ACTION: DENIED
  
 1A-B) COMPLIED
  
 1C) BUILDING PROVISO/ FUTURE REVISION REQUIRED. THE 1ST
 FLOOR LIFE SAFETY PLAN SHOWS NEW MED GAS, NEW VACUUM
 PUMP EQUIPMENT, BUT NO NEW WORK ON THE 2ND FLOOR, HOW
 ARE THESE LINES GOING TO THE NEW AMBULATORY SURGICAL
 CENTER ON THE 3RD FLOOR. 107/2/1/2 ADDITIONAL
 INFORMATION IS REQUIRED.
  
 1D) NOTICE ONLY. NO ACTION NEEDED AT THIS TIME. THE
 INSTALLATION OF A GENERATOR WILL BE UNDER A SEPARATE
 PERMIT, NOT INCLUDED IN THIS REVIEW. SEPARATE PERMIT,
 REVIEW AND ASSOCIATED FEES REQUIRED FOR NEW GENERATOR,
 AND OR FENCING.
  
 2) COMPLIED.
  
 3) COMPLIED.
  
 4A)SEMI- COMPLIED. SHEET A-153 DOES INDICATE RATED
 WALLS AND IDENTIFIES DOOR. SHEET A-701 DOES SHOW THE
 DOOR SCHEDULE, IT APPEARS THERE ARE 2 DOORWAYS IN 1
 HOUR RATED WALLS WITH NO RATING, DOOR 3023 AND 3033-B.
 2017 FBC-B TABLE 716,5,
  
 4B) COMPLIED.
  
 5) COMPLID.
  
 6) COMPLIED AND OR DEFERRED SUBMITTALS.
  
 7A) COMPLIED.
  
 7B)BUILDING PROVISO: FOR WELDED & BOLTED CONNECTIONS.
 THE CONTRACTOR IS REQUIRED TO PROVIDE WELD PROCEDURE
 SPECIFICATIONS & WELDER OPERATOR PERFORMANCE
 QUALIFICATION RECORDS IN ACCORDANCE WITH THE REFERENCED
 STANDARDS AT TIME OF INSPECTION FOR FIELD WIELDING, ON
 THE JOB-SITE WIELDING. THIRD PARTY CERTIFICATION WILL
 BE REQUIRED. REPORTS SUBMITTED TO BUILDING INSPECTOR AT
 TIME OF FRAMING INSPECTION.
 2017 FBC-B 2204.1 WELDING
 1. WELD PROCEDURES SPECIFICATIONS
 2. QUALIFICATIONS OF WELDING PERSONAL
 2017 FBC-B 2204.2 BOLTING.
 IF FURTHER CLARIFICATION AND OR QUESTIONS IS REQUIRED,
 PLEASE CONTACT THE CHIEF BUILDING INSPECTOR KEN CONRAD
 AT
 561-805-6666.
  
 8) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  