Plan Review Notes
Plan Review Notes For Permit 20090500
Permit Number 20090500
Review Stop MEDGAS
Sequence Number 1
Notes
Date Text
2020-10-08 17:11:48CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 NFPA 99 = HEALTH CARE FACILITIES CODE
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
  
 1ST REVIEW
 MEDICAL GAS COMMENTS: DENIED
  
 1.NOTE O2, AIR (MEDICAL CA MANIFOLD AND CYLINDERS),
 VACUUM AND N2 ON PLANS. PROJECT SPECS SPECIFICATION
 22-60-00 SECTION 1.1 DOES NOT REFERENCE N2.
  
 2.PER NFPA 99-15 SECTION 5.1.3.1.8, PROVIDE NOTE
 REQUIRING SIGNAGE ON THE ENTRY DOOR TO THE ROOM
 CONTAINING THE MEDICAL GAS MANIFOLDS/CYLINDERS STATING
 ?POSITIVE PRESSURE GASES
 NO SMOKING OR OPEN FLAME
 ROOM MAY HAVE INSUFFICIENT OXYGEN
 OPEN DOOR AND ALLOW ROOM TO VENTILATE BEFORE ENTERING?
  
 3.PLAN SHEET A9.21; ELEVATION OF HEADWALL NOTES A, O
 AND V OUTLETS. LEGEND ONLY IDENTIFIES O AND V. PER WPB
 FBC 107.2, CLARIFY.
  
 4.PER WPB 107.2.1, PROVIDE SECOND FLOOR PLAN SHOWING
 MED GAS PIPING CONNECTING FIRST AND THIRD FLOORS.
  
 5.PROVIDE MANUFACTURER?S SPECIFICATION
 SHEETS/INSTALLATION MANUAL FOR MEDICAL GAS EQUIPMENT
 AND COMPONENTS. AS THE ACTUAL EQUIPMENT MANUFACTURER
 (SEE 20032 PALM BEACH INTERNATIONAL SC SPECS DIVISION
 22-60-00 SUPPORTING DOCUMENT) MAY NOT HAVE BEEN
 SELECTED AT THIS TIME, SAID DOCUMENTS MAY BE SUBMITTED
 AS A DEFERRED SUBMITTAL IN ACCORDANCE WITH WPB FBC
 107.2.1 AND 107.3.4.1. SEE WPB FBC 107.3.4.2 DEFERRED
 SUBMITTALS; FOR THE PURPOSES OF THIS SECTION, DEFERRED
 SUBMITTALS ARE DEFINED AS THOSE PORTIONS OF THE DESIGN
 THAT ARE NOT SUBMITTED AT THE TIME OF THE APPLICATION
 AND THAT ARE TO BE SUBMITTED TO THE BUILDING OFFICIAL
 WITHIN A SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL
 ITEMS SHALL HAVE THE PRIOR APPROVAL OF THE BUILDING
 OFFICIAL. THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE SHALL LIST THE DEFERRED SUBMITTALS
 ON THE CONSTRUCTION DOCUMENTS FOR REVIEW BY THE
 BUILDING OFFICIAL. THIS MAY BE DONE BY NOTING SUCH IN
 THE RESPONSE LETTER TO THIS REVIEW.
  
 6.DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 7.PER WPB FBC 107.2.1, PROVIDE RISER DIAGRAM OF PIPING
 SYSTEMS FROM SOURCE TO OUTLETS, INCLUDE ALL IN-LINE
 COMPONENTS
  
 8.RE: 22-60-00, SECTION 2.7 (C) VACUUM PUMP RECEIVER IS
 PROVIDED WITH AUTOMATIC TANK DRAIN. PER NFPA 99-15
 SECTION 5.1.3.7.3(4), RECEIVER SHALL BE PROVIDED WITH A
 MANUAL DRAIN. THE AUTOMATIC TANK DRAIN MAY BE PROVIDED
 IN ADDITION TO THE MANUAL DRAIN.
  
 9.PER WPB FBC 107.2.1, PROVIDE LOCATION AND DETAIL
 TERMINATION OF GAS MANIFOLD RELIEF VENT INCLUDING
 ELEVATION AND ANCHORING DETAILS. SPECIFY MATERIAL AND
 JOINTS FOR VENT.
  
 10.PER WPB FBC 107.2.1, PROVIDE LOCATION AND DETAIL
 TERMINATION OF VACUUM PUMP EXHAUST VENT INCLUDING
 ELEVATION AND ANCHORING DETAILS. COMPLY WITH ALL
 REQUIREMENTS OF NFPA 99-15, SECTIONS 5.1.3.7.6.2
 THROUGH 5.1.3.7.6.5. SPECIFY MATERIAL AND JOINTS FOR
 VENT TO COMPLY WITH SECTION 5.1.3.7.6.6.
  
 11.PER WPB FBC 107.2.1, PROVIDE DETAILS SHOWING HOW
 VACUUM SYSTEM IS MONITORED FOR OXYGEN CONTENT THAT IS
 ACQUIRED THROUGH THE WAGD TO SHOW COMPLIANCE WITH NFPA
 99-15, SECTION 5.1.3.8.1.2(2) AND 5.1.3.8.3.1.
  
 12.RE: 22-60-00, SECTION 2.2 SUB SECTIONS
 (B) TUBE SHALL BE ASTM B819 ACR/OXY PER NFPA 99-15
 SECTION 5.1.10.1.4. TUBE COMPLYING WITH ASTM B88 AND
 B280 IS NOT ACCEPTABLE.
 (C) DELETE
 (D) PER NFPA 99-15 SECTION 5.1.10.2.1(1) MAY BE ASTM
 B88, B280 OR B819. IF NOT B819, COMPLY WITH SECTION
 5.1.10.2.2.1.
  
 13.REQUIRE DOCUMENTATION ON ALL PIPE, VALVES AND
 FITTINGS PER NFPA 99-15 SECTION 5.1.10.1.6
  
 14.REQUIRE BRAZING TECHNICIANS TO BE QUALIFIED AND
 CERTIFIED IN ACCORDANCE WITH NFPA 99-15 SECTION
 5.1.10.11.11
  
 15.RE: 22-60-00, SECTION 3.1 (D); NFPA 99-15 DOES NOT
 ALLOW FOR TUBE BENDING. SEE SECTION 5.1.10.4.1 GENERAL
 CONDITIONS. MAKE DIRECTIONAL CHANGES WITH APPROVED
 FITTINGS AND JOINTS.
  
 16.PROVIDE VALVE ID/SYSTEM IDENTIFICATION/COLOR CODING
 SPECIFICATION PER NFPA 99-15 SECTION 5.1.11 THROUGH
 5.1.11.4.
  
 17.PROVIDE NOTE ON PLANS TO REFER TO 20032 PALM BEACH
 INTERNATIONAL SC SPECS DIVISION 22-60-00 FOR WRITTEN
 MEDICAL GAS SPECIFICATIONS (PROVIDED IN SUPPORTING
 DOCUMENTS)
  
 END OF COMMENTS.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
 ALL PLANS TO BE SIGNED AND SEALED/DIGITALLY SIGNED AND
 SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-246-0882 MOBILE
  
 20090500 5325 GREENWOOD AVE
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved