| Date |
Text |
| 2020-10-08 17:11:48 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| | MANUAL REVISED 2017 |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION |
| | FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH |
| | EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION |
| | NFPA 99 = HEALTH CARE FACILITIES CODE |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | |
| | 1ST REVIEW |
| | MEDICAL GAS COMMENTS: DENIED |
| | |
| | 1.NOTE O2, AIR (MEDICAL CA MANIFOLD AND CYLINDERS), |
| | VACUUM AND N2 ON PLANS. PROJECT SPECS SPECIFICATION |
| | 22-60-00 SECTION 1.1 DOES NOT REFERENCE N2. |
| | |
| | 2.PER NFPA 99-15 SECTION 5.1.3.1.8, PROVIDE NOTE |
| | REQUIRING SIGNAGE ON THE ENTRY DOOR TO THE ROOM |
| | CONTAINING THE MEDICAL GAS MANIFOLDS/CYLINDERS STATING |
| | ?POSITIVE PRESSURE GASES |
| | NO SMOKING OR OPEN FLAME |
| | ROOM MAY HAVE INSUFFICIENT OXYGEN |
| | OPEN DOOR AND ALLOW ROOM TO VENTILATE BEFORE ENTERING? |
| | |
| | 3.PLAN SHEET A9.21; ELEVATION OF HEADWALL NOTES A, O |
| | AND V OUTLETS. LEGEND ONLY IDENTIFIES O AND V. PER WPB |
| | FBC 107.2, CLARIFY. |
| | |
| | 4.PER WPB 107.2.1, PROVIDE SECOND FLOOR PLAN SHOWING |
| | MED GAS PIPING CONNECTING FIRST AND THIRD FLOORS. |
| | |
| | 5.PROVIDE MANUFACTURER?S SPECIFICATION |
| | SHEETS/INSTALLATION MANUAL FOR MEDICAL GAS EQUIPMENT |
| | AND COMPONENTS. AS THE ACTUAL EQUIPMENT MANUFACTURER |
| | (SEE 20032 PALM BEACH INTERNATIONAL SC SPECS DIVISION |
| | 22-60-00 SUPPORTING DOCUMENT) MAY NOT HAVE BEEN |
| | SELECTED AT THIS TIME, SAID DOCUMENTS MAY BE SUBMITTED |
| | AS A DEFERRED SUBMITTAL IN ACCORDANCE WITH WPB FBC |
| | 107.2.1 AND 107.3.4.1. SEE WPB FBC 107.3.4.2 DEFERRED |
| | SUBMITTALS; FOR THE PURPOSES OF THIS SECTION, DEFERRED |
| | SUBMITTALS ARE DEFINED AS THOSE PORTIONS OF THE DESIGN |
| | THAT ARE NOT SUBMITTED AT THE TIME OF THE APPLICATION |
| | AND THAT ARE TO BE SUBMITTED TO THE BUILDING OFFICIAL |
| | WITHIN A SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL |
| | ITEMS SHALL HAVE THE PRIOR APPROVAL OF THE BUILDING |
| | OFFICIAL. THE REGISTERED DESIGN PROFESSIONAL IN |
| | RESPONSIBLE CHARGE SHALL LIST THE DEFERRED SUBMITTALS |
| | ON THE CONSTRUCTION DOCUMENTS FOR REVIEW BY THE |
| | BUILDING OFFICIAL. THIS MAY BE DONE BY NOTING SUCH IN |
| | THE RESPONSE LETTER TO THIS REVIEW. |
| | |
| | 6.DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE |
| | SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN |
| | RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD |
| | THEM TO THE BUILDING OFFICIAL WITH A NOTATION |
| | INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE |
| | BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO |
| | THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL |
| | ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED |
| | SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING |
| | OFFICIAL. |
| | |
| | 7.PER WPB FBC 107.2.1, PROVIDE RISER DIAGRAM OF PIPING |
| | SYSTEMS FROM SOURCE TO OUTLETS, INCLUDE ALL IN-LINE |
| | COMPONENTS |
| | |
| | 8.RE: 22-60-00, SECTION 2.7 (C) VACUUM PUMP RECEIVER IS |
| | PROVIDED WITH AUTOMATIC TANK DRAIN. PER NFPA 99-15 |
| | SECTION 5.1.3.7.3(4), RECEIVER SHALL BE PROVIDED WITH A |
| | MANUAL DRAIN. THE AUTOMATIC TANK DRAIN MAY BE PROVIDED |
| | IN ADDITION TO THE MANUAL DRAIN. |
| | |
| | 9.PER WPB FBC 107.2.1, PROVIDE LOCATION AND DETAIL |
| | TERMINATION OF GAS MANIFOLD RELIEF VENT INCLUDING |
| | ELEVATION AND ANCHORING DETAILS. SPECIFY MATERIAL AND |
| | JOINTS FOR VENT. |
| | |
| | 10.PER WPB FBC 107.2.1, PROVIDE LOCATION AND DETAIL |
| | TERMINATION OF VACUUM PUMP EXHAUST VENT INCLUDING |
| | ELEVATION AND ANCHORING DETAILS. COMPLY WITH ALL |
| | REQUIREMENTS OF NFPA 99-15, SECTIONS 5.1.3.7.6.2 |
| | THROUGH 5.1.3.7.6.5. SPECIFY MATERIAL AND JOINTS FOR |
| | VENT TO COMPLY WITH SECTION 5.1.3.7.6.6. |
| | |
| | 11.PER WPB FBC 107.2.1, PROVIDE DETAILS SHOWING HOW |
| | VACUUM SYSTEM IS MONITORED FOR OXYGEN CONTENT THAT IS |
| | ACQUIRED THROUGH THE WAGD TO SHOW COMPLIANCE WITH NFPA |
| | 99-15, SECTION 5.1.3.8.1.2(2) AND 5.1.3.8.3.1. |
| | |
| | 12.RE: 22-60-00, SECTION 2.2 SUB SECTIONS |
| | (B) TUBE SHALL BE ASTM B819 ACR/OXY PER NFPA 99-15 |
| | SECTION 5.1.10.1.4. TUBE COMPLYING WITH ASTM B88 AND |
| | B280 IS NOT ACCEPTABLE. |
| | (C) DELETE |
| | (D) PER NFPA 99-15 SECTION 5.1.10.2.1(1) MAY BE ASTM |
| | B88, B280 OR B819. IF NOT B819, COMPLY WITH SECTION |
| | 5.1.10.2.2.1. |
| | |
| | 13.REQUIRE DOCUMENTATION ON ALL PIPE, VALVES AND |
| | FITTINGS PER NFPA 99-15 SECTION 5.1.10.1.6 |
| | |
| | 14.REQUIRE BRAZING TECHNICIANS TO BE QUALIFIED AND |
| | CERTIFIED IN ACCORDANCE WITH NFPA 99-15 SECTION |
| | 5.1.10.11.11 |
| | |
| | 15.RE: 22-60-00, SECTION 3.1 (D); NFPA 99-15 DOES NOT |
| | ALLOW FOR TUBE BENDING. SEE SECTION 5.1.10.4.1 GENERAL |
| | CONDITIONS. MAKE DIRECTIONAL CHANGES WITH APPROVED |
| | FITTINGS AND JOINTS. |
| | |
| | 16.PROVIDE VALVE ID/SYSTEM IDENTIFICATION/COLOR CODING |
| | SPECIFICATION PER NFPA 99-15 SECTION 5.1.11 THROUGH |
| | 5.1.11.4. |
| | |
| | 17.PROVIDE NOTE ON PLANS TO REFER TO 20032 PALM BEACH |
| | INTERNATIONAL SC SPECS DIVISION 22-60-00 FOR WRITTEN |
| | MEDICAL GAS SPECIFICATIONS (PROVIDED IN SUPPORTING |
| | DOCUMENTS) |
| | |
| | END OF COMMENTS. |
| | |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | ALL PLANS TO BE SIGNED AND SEALED/DIGITALLY SIGNED AND |
| | SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| | |
| | |
| | JERALD SMITH |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | EMAIL [email protected] |
| | PHONE 561-246-0882 MOBILE |
| | |
| | 20090500 5325 GREENWOOD AVE |
| | |