2020-09-25 14:15:54SFR REMODEL
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) PLEASE SHOW THE CEILING HEIGHT AT THE BOTTOM OF THE
 AC SOFFIT TO COMPLY WITH FBC R305.1MINIMUM HEIGHT.(7
 FEET)
 2) PLEASE SHOW THE REQUIRED DRYWALL AT THE AC CLOSET
 CEILING AND WALLS TO COMPLY WITH FBC R302.7UNDER-STAIR
 PROTECTION.
 ENCLOSED ACCESSIBLE SPACE UNDER STAIRS SHALL HAVE
 WALLS, UNDER-STAIR SURFACE AND ANY SOFFITS PROTECTED ON
 THE ENCLOSED SIDE WITH 1/2-INCH (12.7 MM) GYPSUM BOARD.
 3) PLEASE PROVIDE A COMPLETE MIAMI DADE OR FLORIDA
 STATE PRODUCT APPROVAL FOR THE NEW EXTERIOR WINDOW.
 (FRONT PAGES AND THE INSTALLATION INSTRUCTIONS)
 4) PLEASE SHOW THE WIND DESIGN DATA USED FOR THE WIND
 DESIGN. FBC R301.2.1
 5) PLEASE SHOW THE REQUIRED WIND PRESSURES FOR THE NEW
 WINDOW OPENING.
 6) PLEASE PROVIDE FIREPLACE DETAILS TO COMPLY WITH FBC
 R CHAPTER 10.