| 2020-10-23 11:28:33 | SFR ADDITION |
| | REVIEWED BY ROGER MCPHERSON |
| | 561-805-6716 |
| | [email protected]. |
| | CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1 |
| | AMENDMENTS |
| | |
| | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 |
| | 1) BUILDING PERMIT APPLICATION NEEDS TO BE REVISED TO |
| | MATCH THE DRAWINGS - JOB DESCRIPTION SHOULD STATE |
| | BEDROOM ADDITION NOT PATIO - JOB VALUE FOR THE ADDITION |
| | SHOULD BE SHOWN AS IF BEING BUILT BY A CONTRACTOR |
| | (INCLUDE ALL LABOR AND MATERIAL PRICING). |
| | 2) PLEASE SHOW THE EXISTING HOUSE FLOOR PLAN - NEEDED |
| | TO DETERMINE IF THE ADDITION IS BLOCKING A REQUIRED |
| | EXISTING BEDROOM EMERGENCY EGRESS. |
| | 3) DRAWINGS NEED TO BE SIGNED AND DATED BY THE ENGINEER |
| | SHOWN. FBC 107.2.1 |
| | 4) DRAWINGS NEED TO SHOW THE WIND DESIGN CRITERIA USED |
| | FOR DESIGN FBC R301.2.1 |
| | 5) PROVIDE A WINDOW AND DOOR SCHEDULE SHOWING SIZES. |
| | 6) SHOW THE EXTERIOR WALL COVERING TO COMPLY WITH FBC |
| | R703.1 (CANNOT BE DRYWALL AS SHOWN) |
| | 7) PLEASE PROVIDE STRUCTURAL CALCULATIONS THAT SHOWS |
| | FOUNDATIONS, BEARING WALLS, ROOF FRAMING SYSTEMS AND |
| | EXTERIOR SHEATHINGS SHOWN COMPLY WITH FBC 1601 |
| | 8) PROVIDE A ROOF FRAMING PLAN SHOWING ALL REQUIRED |
| | WIND UPLIFT STRAPPING DETAILS, SHEATHING DETAILS ETC TO |
| | COMPLY WITH FBC CHAPTER 23 |
| | 9) PLEASE PROVIDE ROOFING SYSTEM PRODUCT APPROVAL. |
| | 10) PLEASE SHOW ROOF SLOPE. |
| | 11) PLEASE SHOW WALL AND CEILING INSULATION "R" VALUE |
| | TO COMPLY WITH FBC ENERGY CODE. |
| | 12) PLEASE PROVIDE A SITE PLAN SHOWING THE FOLLOWING - |
| | 107.2.5 SITE PLAN. THE CONSTRUCTION DOCUMENTS SUBMITTED |
| | WITH THE APPLICATION FOR PERMIT |
| | SHALL BE ACCOMPANIED BY A SITE PLAN SHOWING TO SCALE |
| | THE SIZE AND LOCATION OF NEW |
| | CONSTRUCTION AND EXISTING STRUCTURES ON THE SITE, |
| | DISTANCES FROM LOT LINES, THE ESTABLISHED |
| | STREET GRADES AND THE PROPOSED FINISHED GRADES, |
| | DEPICTING THE PROPOSED LOT DRAINAGE AND, |
| | AS APPLICABLE, FLOOD HAZARD AREAS, FLOODWAYS, AND |
| | DESIGN FLOOD ELEVATIONS; AND IT SHALL BE |
| | DRAWN IN ACCORDANCE WITH AN ACCURATE AND INCLUDED ON A |
| | BOUNDARY LINE SURVEY. |
| | 13) PLEASE PROVIDE COMPLETE MIAMI DADE OR FLORIDA STATE |
| | PRODUCT APPROVALS FOR THE EXTERIOR WINDOWS, DOORS, |
| | ROOFING SYSTEMS (FRONT PAGES AND THE INSTALLATION |
| | INSTRUCTIONS). |
| | 14) SHOW SMOKE DETECTORS TO COMPLY WITH FBC R314 |
| | 15) MAY NOT BE A COMPLETE LIST OF CORRECTIONS - |
| | DRAWINGS ARE NOT COMPLETE SEE FBC WPB AMENDMENTS |
| | 107.3.5.3 |
| | |