2020-10-23 11:28:33SFR ADDITION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) BUILDING PERMIT APPLICATION NEEDS TO BE REVISED TO
 MATCH THE DRAWINGS - JOB DESCRIPTION SHOULD STATE
 BEDROOM ADDITION NOT PATIO - JOB VALUE FOR THE ADDITION
 SHOULD BE SHOWN AS IF BEING BUILT BY A CONTRACTOR
 (INCLUDE ALL LABOR AND MATERIAL PRICING).
 2) PLEASE SHOW THE EXISTING HOUSE FLOOR PLAN - NEEDED
 TO DETERMINE IF THE ADDITION IS BLOCKING A REQUIRED
 EXISTING BEDROOM EMERGENCY EGRESS.
 3) DRAWINGS NEED TO BE SIGNED AND DATED BY THE ENGINEER
 SHOWN. FBC 107.2.1
 4) DRAWINGS NEED TO SHOW THE WIND DESIGN CRITERIA USED
 FOR DESIGN FBC R301.2.1
 5) PROVIDE A WINDOW AND DOOR SCHEDULE SHOWING SIZES.
 6) SHOW THE EXTERIOR WALL COVERING TO COMPLY WITH FBC
 R703.1 (CANNOT BE DRYWALL AS SHOWN)
 7) PLEASE PROVIDE STRUCTURAL CALCULATIONS THAT SHOWS
 FOUNDATIONS, BEARING WALLS, ROOF FRAMING SYSTEMS AND
 EXTERIOR SHEATHINGS SHOWN COMPLY WITH FBC 1601
 8) PROVIDE A ROOF FRAMING PLAN SHOWING ALL REQUIRED
 WIND UPLIFT STRAPPING DETAILS, SHEATHING DETAILS ETC TO
 COMPLY WITH FBC CHAPTER 23
 9) PLEASE PROVIDE ROOFING SYSTEM PRODUCT APPROVAL.
 10) PLEASE SHOW ROOF SLOPE.
 11) PLEASE SHOW WALL AND CEILING INSULATION "R" VALUE
 TO COMPLY WITH FBC ENERGY CODE.
 12) PLEASE PROVIDE A SITE PLAN SHOWING THE FOLLOWING -
 107.2.5 SITE PLAN. THE CONSTRUCTION DOCUMENTS SUBMITTED
 WITH THE APPLICATION FOR PERMIT
 SHALL BE ACCOMPANIED BY A SITE PLAN SHOWING TO SCALE
 THE SIZE AND LOCATION OF NEW
 CONSTRUCTION AND EXISTING STRUCTURES ON THE SITE,
 DISTANCES FROM LOT LINES, THE ESTABLISHED
 STREET GRADES AND THE PROPOSED FINISHED GRADES,
 DEPICTING THE PROPOSED LOT DRAINAGE AND,
 AS APPLICABLE, FLOOD HAZARD AREAS, FLOODWAYS, AND
 DESIGN FLOOD ELEVATIONS; AND IT SHALL BE
 DRAWN IN ACCORDANCE WITH AN ACCURATE AND INCLUDED ON A
 BOUNDARY LINE SURVEY.
 13) PLEASE PROVIDE COMPLETE MIAMI DADE OR FLORIDA STATE
 PRODUCT APPROVALS FOR THE EXTERIOR WINDOWS, DOORS,
 ROOFING SYSTEMS (FRONT PAGES AND THE INSTALLATION
 INSTRUCTIONS).
 14) SHOW SMOKE DETECTORS TO COMPLY WITH FBC R314
 15) MAY NOT BE A COMPLETE LIST OF CORRECTIONS -
 DRAWINGS ARE NOT COMPLETE SEE FBC WPB AMENDMENTS
 107.3.5.3
  