Plan Review Notes
Plan Review Notes For Permit 20090410
Permit Number 20090410
Review Stop P
Sequence Number 1
Notes
Date Text
2020-10-21 17:15:5210/21/20 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. A SUB PLUMBING PERMIT IS REQUIRED BY A LICENSED
 CONTRACTOR FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS
 TO THE FBC SEC. 105.1.
  
 2. PLUMBING RISER DIAGRAM REQUIRED PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.3.5.3 (11) RESIDENTIAL
 PLUMBING.
  
 3. YOUR PERMIT SAYS A PROPOSED PATIO BUT YOU HAVE A
 DRAWING FOR A BATHROOM AND A BEDROOM PLEASE PROVIDE A
 SCOPE OF WORK TO BE DONE PER THE WPB AMENDMENTS TO THE
 FBC SEC. 107.2.1.4 QUALITY OF BUILDING PLANS.
  
 4. SIGNED AND SEALED DRAWINGS NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW - OR -
 IF YOUR ENGINEER DOES NOT HAVE AN ELECTRONIC OR DIGITAL
 SIGNATURE - PLEASE DROP OFF (CITY HALL DROPBOX) THE
 ORIGINAL SIGNED AND SEALED DOCUMENT ALONG WITH A "PLAN
 REVIEW REQUEST FORM" EXPLAINING THE REASON FOR
 SUBMITTING THE DOCUMENT OR DRAWINGS. THE PLAN REVIEW
 REQUEST FORM CAN BE OBTAINED BY EMAILING [email protected] AND
 ASKING FOR THE FORM.
  
 5. PLEASE PROVIDE THE SIGNATURE OF ALL INFORMATION,
 DRAWINGS, SPECIFICATIONS, AND ACCOMPANYING DATA THAT
 SHALL BEAR THE PRINTED NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE DESIGN PER THE WPB AMENDMENTS TO
 THE FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 6. PLEASE PROVIDE WHERE THE SOURCE OF HOT WATER IS
 COMING FROM PER THE 2017 FBC SEC. R 2722.2.
  
 7. IN FRONT OF A WATER CLOSET TO A FIXTURE, THERE SHALL
 BE A CLEARANCE OF NOT LESS THAN 21 INCHES CLEARANCE PER
 THE 2017 FBC SEC. R P2705.1.
  
 8. THE CLAIMED VALUE APPEARS TO BE UNDERESTIMATED ON
 THE APPLICATION, PLEASE PROVIDE A BONA FIDE SIGNED
 CONTRACT PER THE WPB AMENDMENTS TO THE FBC SEC. 109.3
 BUILDING PERMIT VALUATIONS.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  