| 2020-11-05 16:23:43 | RESIDENTIAL (R3) SECOND BUILDING REVIEW COMMENTS |
| | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| | |
| | NOTE: |
| | BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO |
| | MEANS CONTRACTOR WILL SUBMIT REQUIRED INFORMATION AFTER |
| | THE PERMIT IS ISSUED BUT BEFORE INSPECTIONS TO AVOID |
| | CONFLICTS/DELAYS. REVISION FEES APPLY. CONTRACTOR TO |
| | ADVICE IF PROVISO OPTION IS PREFERRED AT THIS TIME OR |
| | IF RE-SUBMITTING REQUIRED INFORMATION BEFORE PERMIT |
| | ISSUANCE. |
| | |
| | |
| | ***IMPORTANT*** |
| | ENERGY CALCULATIONS NEED TO BE CERTIFIED BY THE OWNER |
| | OR AUTHORIZED AGENT BEFORE ISSUING THE PERMIT. |
| | |
| | |
| | ORIGINAL COMMENT: |
| | 1- BASED ON THE SCOPE OF WORK SHOWN ON PLANS. THIS IS |
| | AN ALTERATION LEVEL 3 AND PARTIAL CHANGE OF USE |
| | (CHANGING USE OF EXISTING GARAGE). SEC. 505 AND SECTION |
| | 506 FBC-EXISTING BUILDING. |
| | NEED TO PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC. |
| | 908 FBC-EXISTING BUILDING AND SEC. R101.5.1 FBC-ENERGY |
| | CONSERVATION. PLEASE HAVE FORM PROPERLY SIGNED BY THE |
| | OWNER OR AUTHORIZED AGENT TO HELP EXPEDITE THE REVIEW |
| | PROCESS. |
| | NOTE: THIS BUILDING IS CONSIDERED A "RENOVATED |
| | BUILDING". THEREFORE, IT IS NOT EXEMPT FROM THE ENERGY |
| | CODE. SEE SEC. R101.4.2 FBC-ENERGY CONSERVATION. |
| | |
| | RESPONSE TO ENERGY CALCULATIONS SUBMITTED: |
| | A)ENERGY CALCULATIONS FORM IS REQUIRED TO BE CERTIFIED |
| | AT THE BOTTOM OF THE FORM BY THE OWNER, THE OWNER'S |
| | ARCHITECT OR OTHER AUTHORIZED AGENT LEGALLY DESIGNED BY |
| | THE OWNER PRIOR TO RECEIVE THE PERMIT AS REQUIRED BY |
| | SEC. R103.1.1.2 FBC-ENERGY CONSERVATION, 6TH EDITION |
| | (2017). |
| | |
| | B)PROVIDE COMPLETE AND CORRECT INFORMATION ON TOP OF |
| | FORM. THE ZIP CODE FOR THIS ADDRESS IS 33405 NOT 33409. |
| | NEED OWNER'S NAME, BUILDER'S NAME. SEC. R101.5.1.1.2 |
| | FBC-ENERGY CONSERVATION. |
| | |
| | C)THIS IS NOT AN ADDITION. THIS IS EXISTING |
| | CONSTRUCTION. REVISE ITEM #1 ON PAGE 1 OF 4. SEE PLANS |
| | AND REVISE. |
| | SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| | |
| | D)SQUARE FEET OF CONDITIONED FLOOR AREA SHOWN ON ITEM |
| | #6 ON PAGE 1 OF 4 DOESN'T MATCH PLANS AND PROPERTY |
| | APPRAISER. WHERE IS THE 1721 S.F. TAKEN FROM?. SEE |
| | PLANS AND REVISE AS REQUIRED. PROVIDE SKETCH SHOWING |
| | THE SPECIFIED SQUARE FOOTAGE. |
| | SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| | |
| | E)ROOF MATERIAL SPECIFIED ON PAGE 2 OF 4 IS INCORRECT. |
| | THIS HOUSE HAS CONCRETE TILE NOT SHINGLES. REVISE AS |
| | REQUIRED. |
| | SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| | |
| | WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE |
| | ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF |
| | THE REVISION MADE, IDENTIFYING THE SHEET OR |
| | SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL |
| | HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| | ANTICIPATED COOPERATION. |
| | |
| | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| | QUESTIONS REGARDING THESE COMMENTS, |