Plan Review Notes
Plan Review Notes For Permit 20090380
Permit Number 20090380
Review Stop B
Sequence Number 2
Notes
Date Text
2020-11-05 16:23:43RESIDENTIAL (R3) SECOND BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 NOTE:
 BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO
 MEANS CONTRACTOR WILL SUBMIT REQUIRED INFORMATION AFTER
 THE PERMIT IS ISSUED BUT BEFORE INSPECTIONS TO AVOID
 CONFLICTS/DELAYS. REVISION FEES APPLY. CONTRACTOR TO
 ADVICE IF PROVISO OPTION IS PREFERRED AT THIS TIME OR
 IF RE-SUBMITTING REQUIRED INFORMATION BEFORE PERMIT
 ISSUANCE.
  
  
 ***IMPORTANT***
 ENERGY CALCULATIONS NEED TO BE CERTIFIED BY THE OWNER
 OR AUTHORIZED AGENT BEFORE ISSUING THE PERMIT.
  
  
 ORIGINAL COMMENT:
 1- BASED ON THE SCOPE OF WORK SHOWN ON PLANS. THIS IS
 AN ALTERATION LEVEL 3 AND PARTIAL CHANGE OF USE
 (CHANGING USE OF EXISTING GARAGE). SEC. 505 AND SECTION
 506 FBC-EXISTING BUILDING.
 NEED TO PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC.
 908 FBC-EXISTING BUILDING AND SEC. R101.5.1 FBC-ENERGY
 CONSERVATION. PLEASE HAVE FORM PROPERLY SIGNED BY THE
 OWNER OR AUTHORIZED AGENT TO HELP EXPEDITE THE REVIEW
 PROCESS.
 NOTE: THIS BUILDING IS CONSIDERED A "RENOVATED
 BUILDING". THEREFORE, IT IS NOT EXEMPT FROM THE ENERGY
 CODE. SEE SEC. R101.4.2 FBC-ENERGY CONSERVATION.
  
 RESPONSE TO ENERGY CALCULATIONS SUBMITTED:
 A)ENERGY CALCULATIONS FORM IS REQUIRED TO BE CERTIFIED
 AT THE BOTTOM OF THE FORM BY THE OWNER, THE OWNER'S
 ARCHITECT OR OTHER AUTHORIZED AGENT LEGALLY DESIGNED BY
 THE OWNER PRIOR TO RECEIVE THE PERMIT AS REQUIRED BY
 SEC. R103.1.1.2 FBC-ENERGY CONSERVATION, 6TH EDITION
 (2017).
  
 B)PROVIDE COMPLETE AND CORRECT INFORMATION ON TOP OF
 FORM. THE ZIP CODE FOR THIS ADDRESS IS 33405 NOT 33409.
 NEED OWNER'S NAME, BUILDER'S NAME. SEC. R101.5.1.1.2
 FBC-ENERGY CONSERVATION.
  
 C)THIS IS NOT AN ADDITION. THIS IS EXISTING
 CONSTRUCTION. REVISE ITEM #1 ON PAGE 1 OF 4. SEE PLANS
 AND REVISE.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 D)SQUARE FEET OF CONDITIONED FLOOR AREA SHOWN ON ITEM
 #6 ON PAGE 1 OF 4 DOESN'T MATCH PLANS AND PROPERTY
 APPRAISER. WHERE IS THE 1721 S.F. TAKEN FROM?. SEE
 PLANS AND REVISE AS REQUIRED. PROVIDE SKETCH SHOWING
 THE SPECIFIED SQUARE FOOTAGE.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 E)ROOF MATERIAL SPECIFIED ON PAGE 2 OF 4 IS INCORRECT.
 THIS HOUSE HAS CONCRETE TILE NOT SHINGLES. REVISE AS
 REQUIRED.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]