| 2020-10-02 17:28:02 | RESIDENTIAL (R3) BUILDING REVIEW COMMENTS |
| | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| | |
| | NOTE: SEC. 801.3 FBC-EXISTING BUILDING. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE. |
| | |
| | 1- BASED ON THE SCOPE OF WORK SHOWN ON PLANS. THIS IS |
| | AN ALTERATION LEVEL 3 AND PARTIAL CHANGE OF USE |
| | (CHANGING USE OF EXISTING GARAGE). SEC. 505 AND SECTION |
| | 506 FBC-EXISTING BUILDING. |
| | NEED TO PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC. |
| | 908 FBC-EXISTING BUILDING AND SEC. R101.5.1 FBC-ENERGY |
| | CONSERVATION. PLEASE HAVE FORM PROPERLY SIGNED BY THE |
| | OWNER OR AUTHORIZED AGENT TO HELP EXPEDITE THE REVIEW |
| | PROCESS. |
| | NOTE: THIS BUILDING IS CONSIDERED A "RENOVATED |
| | BUILDING". THEREFORE, IT IS NOT EXEMPT FROM THE ENERGY |
| | CODE. SEE SEC. R101.4.2 FBC-ENERGY CONSERVATION. |
| | |
| | 2- SHEET 1.0A: |
| | A)DESIGN PROFESSIONAL SPECIFIES CONSTRUCTION TYPE IIIB |
| | AT THE BOTTOM RIGHT OF THIS DRAWING. ACCORDING TO TABLE |
| | 601 FBC-BUILDING CONSTRUCTION TYPE IIIB REQUIRES |
| | EXTERIOR BEARING WALLS TO BE 2 HOUR FIRE RATED. PROVIDE |
| | PROOF THAT EXISTING EXTERIOR BEARING WALLS ARE 2 HOUR |
| | FIRE RATED OR REVISE CONSTRUCTION TYPE TO MATCH ACTUAL |
| | CONSTRUCTION. (NOTE: TYPICALLY, ONE AND TWO FAMILY |
| | RESIDENCES ARE CONSTRUCTION TYPE VB). |
| | |
| | B)DESIGN PROFESSIONAL SPECIFIES OCCUPANCY TYPE "R". |
| | THERE ARE MANY TYPES OF "R" OCCUPANCIES. CLEARLY |
| | SPECIFY WHICH "R" OCCUPANCY IS THIS BUILDING. |
| | SEC. 310 FBC-BUILDING. |
| | |
| | WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE |
| | ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF |
| | THE REVISION MADE, IDENTIFYING THE SHEET OR |
| | SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL |
| | HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| | ANTICIPATED COOPERATION. |
| | |
| | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| | QUESTIONS REGARDING THESE COMMENTS, |