Plan Review Notes
Plan Review Notes For Permit 20090378
Permit Number 20090378
Review Stop B
Sequence Number 1
Notes
Date Text
2020-10-21 17:50:38RESIDENTIAL (R3)ADDITION, BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 1-ENERGY CALCULATIONS SUBMITTED:
 ENERGY CALCULATIONS FORM IS REQUIRED TO BE CERTIFIED AT
 THE BOTTOM OF THE FORM BY THE OWNER, THE OWNER'S
 ARCHITECT OR OTHER AUTHORIZED AGENT LEGALLY DESIGNED BY
 THE OWNER PRIOR TO RECEIVE THE PERMIT AS REQUIRED BY
 SEC. R103.1.1.2 FBC-ENERGY CONSERVATION, 6TH EDITION
 (2017).
 SEC. 507, SEC. 1106 FBC-EXISTING BUILDING
  
 2- SHEET A-4:
 A)WINDOW AND DOORS WERE REMOVED TO ALLOW FOR THE
 PROPOSED ADDITION. PLANS DON'T SHOW LAYOUT OF THE
 EXISTING ROOMS ADJACENT TO THE PROPOSED ADDITION.
 PROVIDE LAYOUT OF THE EXISTING AREA ADJACENT TO THE
 PROPOSED ADDITION. SHOW THE SCOPE OF WORK ON THE
 EXISTING ROOMS. ARE THERE ANY BEDROOMS? IF SO, HOW IS
 THE EGRESS AFFECTED. SPECIFY TYPE AND SIZE OF EGRESS
 WINDOWS.
 SEC. 107.2.1 CITY AMENDMENTS. SEC. 507, SEC. 1101.1
 FBC-EXISTING BUILDING. SEC. R310.2 FBC-RESIDENTIAL.
  
 B)IF EXISTING WINDOW IS IN A BATHROOM AND WAS CLOSED TO
 ALLOW FOR ADDITION, THEN NEED VENTILATION FOR EXISTING
 BATHROOM. SPECIFY EXHAUST FAN AS REQUIRED BY THE
 EXCEPTION ON SEC. R303.3 FBC-RESIDENTIAL.
 SEC. 107.2.1 CITY AMENDMENTS. SEC. 507, SEC. 1101.1
 FBC-EXISTING BUILDING.
  
 3- PROPERTY IS LOCATED IN QUESTIONABLE SOIL. NEED TO
 PROVIDE SOIL TEST REPORT AS REQUIRED BY SEC. R401.4
 BC-RESIDENTIAL.
 SEC. 507, SEC. 1101.1 FBC-EXISTING BUILDING.
  
 4- PLANS AND DETAILS DON'T PROVIDE INFORMATION FOR NEW
 SOFFITS. PROVIDE COMPLETE DETAILS AND SPECIFICATIONS
 FOR THE SOFFIT INSTALLATION SHOWING COMPLIANCE WITH
 SEC. R703.1.2.1 FBC-RESIDENTIAL. SPECIFY MATERIALS AND
 FASTENING.
 SEC. 507, SEC. 1101.1 FBC-EXISTING BUILDING.
  
 5- SPECIFY SIZE AND LOCATION OF SOFFIT VENTS SHOWING
 COMPLIANCE WITH SEC. R806 FBC-RESIDENTIAL. PLANS AND
 DETAILS DON'T PROVIDE THIS INFORMATION.
 SEC. 507, SEC. 1101.1 FBC-EXISTING BUILDING.
  
 6- PROVIDE PRODUCT APPROVAL FOR WINDOW MULLIONS AS
 SHOWN ON PLANS. AND REQUIRED: CLEARLY SPECIFY MULLION
 SIZE TO BE USED TO VERIFY COMPLIANCE WITH THE
 CALCULATED DESIGN PRESSURES.
 FAC 61G20.3001
  
 7-ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,