| 2020-10-22 09:30:40 | 2ND REVIEW FBC-2017 RES. |
| | PERMIT- 20090347 |
| | 10/22/2020 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | IT APPEARS NO CORRECTIONS WERE MADE TO THE GAS RISER |
| | DRAWING. PLEASE COMPLY WITH THE 1ST AND 2ND REVIEW |
| | COMMENTS LISTED BELOW. |
| | |
| | 1) GAS RISER DRAWING: RECORDS RESEARCH FOR 7945 VIA |
| | VILLAGIO SHOW GAS PERMIT #04040274 ISSUED 4/10/2004 FOR |
| | INTERIOR/EXTERIOR PIPE INSTALLATION. RECORD DRAWINGS |
| | INDICATE A TOTAL LOAD OF 564,000 BTU'S: POOL HEATER- |
| | 400,000. GRILL- 50,000. COOKTOP- 42,000. DRYER- 22,000. |
| | WATER HEATER- 50,000. REVISE THE RISER TO SHOW THE |
| | CORRECT TOTAL AND INDIVIDUAL LOADS OF THE SYSTEM- |
| | SECTIONS G2412.3, G2412.4, & G2413.2 FBC RES. PLEASE |
| | NOTE THAT THE TOTAL DEVELOPED LENGTH OF SYSTEM WAS |
| | INDICATED TO BE 88 FT. |
| | |
| | A) PROVIDE THE TOTAL LENGTH OF THE INTERIOR PIPING RUN |
| | AND THE TOTAL DEVELOPED LENGTH OF THE ENTIRE SYSTEM- |
| | SECTIONS G2413.4.1 AND G2413.4.2 FBC RES. |
| | |
| | B) SUBMIT UPDATED SPECS FOR THE 22KW GENERATOR. I HAVE |
| | CHECKED THE UPDATED SPECS FOR THE GENERAC 22KW MODEL |
| | AND THEY INDICATE A FULL LOAD OF 306,000 BTUH FOR |
| | NATURAL GAS. PLEASE CORRECT THE LOAD SHOWN ON THE RISER |
| | TO INDICATE 870,000 BTUH. |
| | |
| | C) USING THE PIPE SIZING TABLE 402.4(3) FBC FG SHOWN ON |
| | THE RISER, THE 3/4 IN. GALVANIZED MAIN RISER PIPE WILL |
| | SUPPLY A MAXIMUM 289,000 BTU'S. THE RISERS MUST BE |
| | INCREASED IN SIZE TO 1-1/4 IN. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL/PLUMBING PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |