| Plan Review Notes For Permit 20090347 |
| Permit Number |
20090347 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2020-11-03 07:30:48 | PETER E VALENTI | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561?805?6673 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | FBC M = FBC MECHANICAL | | | FBC FG = FBC FUEL GAS | | | | | | 2ND BUILDING REVIEW DENIED: | | | FBC B 107.2.1, FBC M 401 & GENERAC SPECIFICATIONS (SITE | | | SELECTIONS), THE LOCATION OF EXHAUST TERMINATION SHOULD | | | BE INDICATED ON PLAN, MUST BE AT NO LESS THAN 10' | | | HORIZONTALLY OR 3' VERTICALLY ABOVE THE OPERABLE | | | OPENINGS OF THE STRUCTURE. |
|