| 2020-09-24 16:44:05 | 1ST REVIEW FBC-2017 RES. |
| | PERMIT- 20090347 |
| | 9/24/2020 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) GAS RISER DRAWING: RECORDS RESEARCH FOR 7945 VIA |
| | VILLAGIO SHOW GAS PERMIT #04040274 ISSUED 4/10/2004 FOR |
| | INTERIOR/EXTERIOR PIPE INSTALLATION. RECORD DRAWINGS |
| | INDICATE A TOTAL LOAD OF 564,000 BTU'S: POOL HEATER- |
| | 400,000. GRILL- 50,000. COOKTOP- 42,000. DRYER- 22,000. |
| | WATER HEATER- 50,000. REVISE THE RISER TO SHOW THE |
| | CORRECT TOTAL AND INDIVIDUAL LOADS OF THE SYSTEM- |
| | SECTIONS G2412.3, G2412.4, & G2413.2 FBC RES. PLEASE |
| | NOTE THAT THE TOTAL DEVELOPED LENGTH OF SYSTEM WAS |
| | INDICATED TO BE 88 FT. |
| | |
| | A) PROVIDE THE TOTAL LENGTH OF THE INTERIOR PIPING RUN |
| | AND THE TOTAL DEVELOPED LENGTH OF THE ENTIRE SYSTEM- |
| | SECTIONS G2413.4.1 AND G2413.4.2 FBC RES. |
| | |
| | B) SUBMIT UPDATED SPECS FOR THE 22KW GENERATOR. I HAVE |
| | CHECKED THE UPDATED SPECS FOR THE GENERAC 22KW MODEL |
| | AND THEY INDICATE A FULL LOAD OF 306,000 BTUH FOR |
| | NATURAL GAS. PLEASE CORRECT THE LOAD SHOWN ON THE RISER |
| | TO INDICATE 870,000 BTUH. |
| | |
| | C) PIPE SIZING SHALL BE IN ACCORDANCE WITH SECTION |
| | G2413.3 FBC RES. TABLE 402.4(3) FBC FG WITH A 3.0 IN. |
| | PRESSURE DROP LISTED ON THE PLANS IS NOT A SIZING TABLE |
| | FOUND IN THE FBC RES. TYPICALLY PRESSURE DROP IN |
| | RESIDENTIAL LOW PRESSURE SYSTEMS IS 0.5 IN. W.C. PLEASE |
| | REVIEW SECTION G2413.5 (402.5 ) ALLOWABLE PRESSURE DROP |
| | WHICH INDICATES: THE DESIGN PRESSURE LOSS IN ANY PIPING |
| | SYSTEM UNDER MAXIMUM PROBABLE FLOW CONDITIONS, FROM THE |
| | POINT OF DELIVERY TO THE INLET CONNECTION OF THE |
| | APPLIANCE, SHALL BE SUCH THAT THE SUPPLY PRESSURE AT |
| | THE APPLIANCE IS GREATER THAN OR EQUAL TO THE MINIMUM |
| | PRESSURE REQUIRED BY THE APPLIANCE. |
| | |
| | D) PLEASE INDICATE THE SIZING METHOD USED PER SECTIONS |
| | G2413.4.1 LONGEST LENGTH, OR G2413.4.2 BRANCH LENGTH. |
| | INDICATE THE TABLES USED TO SIZE THE SCHEDULE 40 |
| | METALLIC- SEE TABLES G2413.4(1)- G2413.4(8). PLEASE |
| | NOTE IF USING THE LONGEST LENGTH METHOD TO SIZE THE |
| | SCHED. 40 METALLIC, THE MAIN PIPE FROM THE METER TO THE |
| | 1ST TEE, ACCORDING TO TABLE G2413.4(1) [402.4(2)] SHALL |
| | BE MINIMUM 2 IN. FOR A 870,000 BTUH LOAD AT 88 FT. |
| | DEVELOPED LENGTH. THE BRANCH LEG FROM THE TEE TO THE |
| | GENERATOR REGULATOR SHALL BE 1-1/4 IN., AND THE BRANCH |
| | LEG TO THE EXISTING APPLIANCES SHALL BE 1-1/2 IN. |
| | |
| | 2) SURVEY: THE GENERATOR SHALL BE INSTALLED A MINIMUM |
| | OF 5 FT. AWAY FROM COMBUSTIBLE WALLS- SEC. 4.1.4 NFPA |
| | 37, AND A MINIMUM OF 10 FT. FROM MECHANICAL OR GRAVITY |
| | AIR INTAKES (WINDOW AND DOOR OPENINGS) INTO THE |
| | BUILDING- SEC. R303.5.1 FBC RES. CORRECT THE NOTES ON |
| | THE DRAWING. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |