| 2020-09-16 16:07:13 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT-20090291 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) THE SPECIFICATION SHEETS PROVIDED FOR THE NEW |
| | COOKING EQUIPMENT IS GENERIC FOR DIFFERENT MODELS THE |
| | BTU?S VARY ACCORDINGLY. IDENTIFY THE MODEL USED IN THIS |
| | PROJECT ON EACH APPLIANCE SPECIFICATION PACKAGE. FBC FS |
| | 107.2.1 |
| | |
| | 2) THE NEW TANKLESS WATER HEATER APPEARS TO BE |
| | INSTALLED OUTDOORS. PLEASE SHOW THE REGULATOR IS |
| | APPROVED FOR OUTDOOR INSTALLATION. FBC FG 410.1 |
| | |
| | 3) PLEASE SHOW HOW THE APPLIANCES WILL BE CONNECTED TO |
| | THE GAS SYSTEM. FBC FG 411.1.1 |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| | UPDATED. |
| | |
| | |