| 2020-09-15 12:23:23 | 1ST REVIEW FBC-2017 PLUMBING |
| | PERMIT- 20090264 |
| | 9/15/2020 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) THE WORK DESCRIPTION INDICATES REPLACING THE BATHTUB |
| | WITH NEW BUT A SHOWER PAN DETAIL HAS BEEN SUBMITTED. IS |
| | THE BATHTUB BEING CONVERTED TO A SHOWER? THE |
| | DESCRIPTION ALSO INDICATES REPLACE SHOWER VALVE? PLEASE |
| | CLARIFY THE SCOPE OF PLUMBING WORK FOR THE PROJECT- |
| | SECTION 107.2.1 WPB. |
| | |
| | 2) ASSUMING A SHOWER IS TO BE INSTALLED PLEASE PROVIDE: |
| | A) SHOWER PAN DETAIL WITH A CONCRETE SLAB BASE. THE |
| | SUBMITTED DETAIL SHOWS WOOD FLOOR JOISTS- SECTION |
| | 4517.5 FBC P. |
| | B) DIMENSIONS OF THE NEW SHOWER- SECTION 417.4 FBC P. |
| | C) SANITARY RISER DRAWING. CLARIFY IF THE EXISTING TUB |
| | DRAIN IS TO BE USED OR IF THE DRAIN WILL BE RELOCATED |
| | TO THE CENTER OF THE SHOWER PAN AS SHOWN IN THE DETAIL- |
| | SECTION 107.2.1 WPB. PLEASE NOTE THAT THE HORIZONTAL |
| | DISTANCE FROM THE CENTERLINE OF THE NEW SHOWER DRAIN |
| | OUTLET TO THE CENTERLINE OF THE INLET OF THE EXISTING |
| | TRAP SHALL NOT EXCEED 30 IN. PER SECTION 1002.1 FBC P. |
| | D) PLEASE SEE BUILDING PLAN REVIEW COMMENTS FOR PIPE |
| | PENETRATION OF THE SLAB COMPLIANCES. |
| | |
| | 3) THE WORK DESCRIPTION AND THE FLOOR PLAN DRAWINGS DO |
| | NOT PROVIDE THE SCOPE OF WORK FOR PLUMBING IN THE |
| | KITCHEN, THE WASHER/DRYER, OR THE WATER HEATER. PLEASE |
| | REVISE THE NOTES AND PLANS TO PROVIDE THE INFORMATION |
| | AND DETAILS- SECTION 107.2.1 WPB. |
| | |
| | 4) A TANKLESS WATER HEATER SPEC SHEET HAS BEEN |
| | SUBMITTED BUT AS NOTED IN COMMENT #3, NO SCOPE OF WORK |
| | HAS BEEN PROVIDED. CLARIFY IF THE EXISTING STORAGE TANK |
| | WH IS BEING CONVERTED TO A TANKLESS WH. IF THIS IS THE |
| | CASE, PROVIDE THE MAKE AND MODEL NUMBER OF THE UNIT ON |
| | THE PLANS, AND SUBMIT COMPLETE SPECIFICATIONS AND |
| | INSTALLATION MANUAL. SEE PAGE 2 OF THE SUBMITTED SPECS |
| | WHICH PROVIDES A TEMPERATURE RISE CHART FOR SIZING THE |
| | WATER HEATER PER TEMPERATURE RISE AND REQUIRED GPM FLOW |
| | TO THE FIXTURES. PLEASE HIGHLIGHT OR MARKUP THE CHART |
| | TO SHOW THE SELECTED UNIT- SECTION 502.1 FBC P. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |