| 2020-10-02 11:50:07 | ZONING PLAN REVIEW |
| | ________________________________________ |
| | |
| | DATE OF REVIEW: 10/2/2020 |
| | ________________________________________ |
| | |
| | REVIEW STATUS: FAILED |
| | ________________________________________ |
| | |
| | PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN |
| | REVIEW COMMENTS: |
| | |
| | 1. PLEASE PROVIDE THE SETBACKS OFTHE GENERATOR TO THE |
| | SIDE ROPERTY SETBACK. PURSUANT TO THE CITY OF WEST PALM |
| | BEACH ZONING AND LAND DEVELOPMENT REGULATIONS (ZLDR), |
| | SECTION 94-305(B)(4): MECHANICAL EQUIPMENT MAY NOT |
| | PROJECT MORE THAN 4 FEET INTO A REQUIRED SETBACK. THE |
| | REQUIRED SIDE SETBACK IS 5 FEET, THE GENERATOR MUST BE |
| | A MINIMUM OF 1 FOOT FROM THE SIDE PROPERTY LINE. |
| | ________________________________________ |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |
| | IF YOU SUBMITTED A PAPER APPLICATION, AND YOU WOULD |
| | LIKE TO RESUBMIT ELECTRONICALY, EMAIL |
| | [email protected] AND REQUEST TO HAVE YOUR |
| | PROJECT CONVERTED TO PROJECTDOX. YOU WILL RECEIVE LOGIN |
| | INFORMATION AND A LINK TO UPLOAD YOUR RESUBMITTAL. |
| | PLEASE BE SURE TO ?COMPLETE THE UPLOAD TASK? WHEN YOU |
| | ARE FINISHED UPLOADING. |
| | |
| | ________________________________________ |
| | |
| | QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING: |
| | |
| | RAFAELA THERMIDOR, ASSOCIATE PLANNER |
| | CITY OF WEST PALM BEACH |
| | DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION |
| | 401 CLEMATIS STREET - P.O. BOX 3147 |
| | WEST PALM BEACH, FLORIDA 33402 |
| | |
| | TTY: 800.955.8771 |
| | E: [email protected] |
| | W: WPB.ORG |
| | |